一、电缆参数修正如下:,,,,,,
温度在20
℃,,JKJY、JKLYJ型绝缘架空电缆,,,,
标称面积,直径(mm),20℃导体最大支流R/km,,载流量,,
,,铜,铝,铜,铝,
35,7.0,0.54,0.868,190A,147A,
50,8.3,0.399,0.641,230A,178A,
70,10.0,0.276,0.443,298A,224A,
95,11.6,0.199,0.32,355A,275A,
120,13.0,0.158,0.253,411A,318A,
150,14.6,0.128,0.206,471A,366A,
185,16.2,0.1021,0.164,543A,421A,
240,18.4,0.0777,0.125,645A,501A,
,,,,,,,
二、温度在30
℃以上以铜、铝为基准载流量,,,,,,
标称面积,10KV,,35KV,,,
,铜,铝,铜,铝,,
35,192,149,,,,
50,232,180,260,206,,
70,291,226,317,247,,
95,357,276,377,295,,
120,413,320,433,339,,
150,473,366,492,386,,
185,545,423,557,437,,
240,647,503,650,512,,
300,749,583,740,586,,
三、温度在35℃以上,上列的数据乘以0.96的修正系数,,,,,,
四、温度在40℃乘系数0.91,,,,,,
五、温度在45℃乘系数0.87,,,,,,
六、温度在50℃乘系数0.67,,,,,,
,,,,,,,
载流量比较,,,,,,
标称面积,电缆在土壤中15℃(10KV),,在空气中25℃(10KV),,,
50,190A,,200A,,,
70,235A,,250A,,,
95,280A,,305A,,,
120,320A,,355A,,,
150,360A,,405A,,,
185,405A,,465A,,,
240,470A,,550A,,,
300,530A,,630A,,,
标称面积,电缆在土壤中15℃(35KV),,在空气中25℃(35KV),,,
,65℃,60℃,65℃,60℃,,
50,165A,157A,174A,164A,,
70,206A,196A,219A,206A,,
95,242A,230A,265A,249A,,
120,279A,265A,305A,287A,,
150,315A,300A,347A,326A,,
185,352A,334A,402A,378A,,
240,407A,387A,475A,447A,,
300,457A,434A,539A,507A,,
,,,,,,,
架空线允许载流量表,,,,,,
截面(mm2),导线型号,,,,,
,TJ型(M),LJ型(A),LGJ型(AC),LGJQ型(ACO),LGJJ型(ACY),
,长期连续负荷允许载流量(A),,,,,
16,130,105,105,,,
25,180,135,135,,,
35,220,170,170,,,
50,270,215,220,,,
70,340,265,275,,,
95,415,325,335,,,
120,485,370,380,,,
150,570,440,445,,465,
185,640,500,515,510,543,
240,770,585,610,610,629,
300,890,680,700,710,710,
400,1085,830,800,845,865,
500,,980,,966,,
600,,1100,,1090,,
注:1、导线最高允许工作温度70
℃。,,,,,,
2、环境温度以25
℃为标准,不是25
℃时应按实际温度,在下表查出校正系,,,,,,
数,乘以载流量得实际允许电流。,,,,,,
3、TJ-铜绞线,LJ-铝绞线,LGJ-钢芯铝绞线,LGJQ-轻型钢芯铝绞线,,,,,,,
LGJJ-加强型钢芯铝绞线。,,,,,,
环境温度(℃),-5,0,5,10,15,20
校正温度,1.29,1.24,1.20,1.15,1.11,1.04
环境温度(℃),25,30,35,40,45,
校正温度,1.00,0.94,0.88,0.81,0.7,
三芯铜电力电缆载流量表,,,,,,
(按设于地下土温15℃、25℃允许持续电流),,,,,,(单位:A)
铜芯截面(mm2),6KV,,10KV,,35KV,
,地下15℃,露天25℃,地下15℃,露天25℃,地下15℃,露天25℃
10,80,55,70,50,,
16,105,65,95,60,,
25,135,90,120,85,,
35,160,110,150,105,,
50,200,145,180,135,,
70,245,175,215,165,200,145
95,295,215,265,200,240,175
120,340,250,310,240,280,200
150,390,290,355,270,315,230
185,440,330,400,305,365,260
240,510,375,460,350,,
300,,,567,,,
三芯铝电力电缆载流量表,,,,,,
,,,(单位:A),,,
(按设于地下土温15℃、缆芯最高允许60℃),,,,,,
铝芯截面(mm2),6KV,10KV,35KV,,,
,6KV,10KV,35KV,,,
载流量(A),载流量(A),载流量(A),,,,
35,130,120,,,,
50,150,145,,,,
70,190,175,138,,,
95,230,215,165,,,
120,260,245,193,,,
150,300,280,220,,,
185,335,320,248,,,
电力电缆允许过负荷数值表,,,,,,
1、10千伏及以下的电缆在下表负荷范围内,其过负荷允许30分钟,,,,,,
,,,,,,,
,,过负荷前,过负荷前,过负荷前,,
,,5小时内,5小时内,5小时内,,
,,负荷率=0%,负荷率=50%,负荷率=70%,,
,,,,,,,
,,,,,,,
50-90,,15,-,-,,
120-240,,25,20,15,,
240以上,,45,40,30,,
架空线安全电流的温度校正系数,,,,,,
实际温度(℃),-5,0,5,10,15,20
修正系数,1.29,1.24,1.2,1.15,1.11,1.05
实际温度(℃),25,30,35,40,45,50
修正系数,1,0.95,0.88,0.81,0.74,0.67
常用型号的架空线安全电流,,,,,,
架空线型号,安全电流(安),架空线型号,安全电流(安),架空线型号,安全电流(安),
LGJ-35,170,,,,,
LGJ-50,220,LGJQ-150,,LGJJ-150,464,
LGJ-70,275,LGJQ-185,510,LGJJ-185,543,
LGJ-95,335,LGJQ-240,610,LGJJ-240,269,
LGJ-120,380,LGJQ-300,710,LGJJ-300,710,
LGJ-150,4
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 英语编制课程设计小学
- 石灰法烟气脱硫课程设计
- 英语兴趣班音标课程设计
- 挤压模课程设计
- 人教部编版七年级历史下册全册教案
- 椭球形塑料模课程设计
- 自制小乐器托班课程设计
- 幼儿园远足课程设计
- 电力行业前台服务总结
- 物流仓储行业配送优化建议
- GB/T 40428-2021电动汽车传导充电电磁兼容性要求和试验方法
- GB/T 32545-2016铁矿石产品等级的划分
- 七年级下册道德与法治复习资料
- 阿里云数字化转型生态介绍课件
- 初中语文人教八年级上册《诚信综合实践》PPT
- 奥齿泰-工具盒使用精讲讲解学习课件
- 最新MARSI-医用黏胶相关皮肤损伤课件
- 工程开工报审表范本
- 航空小镇主题乐园项目规划设计方案
- 保洁冬季防滑防冻工作措施
- 少儿美术课件-《我的情绪小怪兽》
评论
0/150
提交评论