生产装置工艺(DCS)或设备联锁联调确认表,,,,,,,,,,,,,,,,,

编号:LHXCLD-7.5-134,,,,,,,,,,,,,,,,,

序号,装置位号及名称,,联锁名称,,,,,联锁条件,,,联调给定值,联锁结果,,联调结论,联调日期,,备注

1,210主装置,,润滑油压力A低低,,,,,PI-2901ALL:0.08MPa,,,0.08MPa,开HV-2901、关HV-2902,,,,,

2,210主装置,,润滑油压力B低低,,,,,PI-2901BLL:0.08MPa,,,0.08MPa,开HV-2901、关HV-2902,,,,,

3,210主装置,,压气机轴承温度A高高,,,,,TI-2901AHH:85℃,,,85℃,开HV-2901、关HV-2902,,,,,

4,210主装置,,压气机轴承温度B高高,,,,,TI-2901BHH:85℃,,,85℃,开HV-2901、关HV-2902,,,,,

5,210主装置,,涡轮端轴承温度A高高,,,,,TI-2902AHH:85℃,,,85℃,开HV-2901、关HV-2902,,,,,

6,210主装置,,涡轮端轴承温度B高高,,,,,TI-2902BHH:85℃,,,85℃,开HV-2901、关HV-2902,,,,,

7,210主装置,,膨胀机转速A高高,,,,,ST-2901AHH:14000rpm,,,14000rpm,开HV-2901、关HV-2902,,,,,

8,210主装置,,膨胀机转速B高高,,,,,ST-2901BHH:14000rpm,,,14000rpm,开HV-2901、关HV-2902,,,,,

9,210主装置,,210T-2201上塔温度高高,,,,,210TIA-2201HH:58℃,,,58℃,开TV-2201、HV-2204,,,,,

10,210主装置,,210T-2201中塔温度高高,,,,,210TIA-2202HH:60℃,,,60℃,开TV-2202、HV-2205,,,,,

11,210主装置,,210T-2201下塔温度高高,,,,,210TIA-2203HH:60℃,,,60℃,开TV-2203、HV-2206,,,,,

12,210主装置,,210HS-01,,,,,210HS-01触发,,,触发,"停泵P-2102A/B、P-2201A/B、

P-2401A/B",,,,,

13,210主装置,,210AIA-2108氧含量高高,,,,,210AIA-2108HH:0.5%,,,0.50%,开HV-2101,,,,,

14,210主装置,,210V-2202B液位低低,,,,,210LIAS-2202LL:10%,,,10.00%,关LSV-2202,,,,,

15,210主装置,,210V-2103液位低低,,,,,210LIAS-2102LL:20%,,,20.00%,关HV-2104,,,,,

16,210主装置,,空气总管压力低低,,,,,210PIAS-2201LL:0.35MPa,,,0.35MPa,去SIS触发dsD-2109D,,,,,

17,210主装置,,氧化塔中塔空气进口压力低低,,,,,210PIAS-2202LL:0.30MPa,,,0.3MPa,去SIS触发dsD-2109D,,,,,

18,210主装置,,210V-2105液位高高,,,,,210LIAS-2103HH:80%,,,80.00%,停泵P-2401A/B,,,,,

19,210主装置,,210V-2401液位低低,,,,,210LIA-2403LL:0%,,,0.00%,关LSV-2403,,,,,

20,210主装置,,氧化尾气压力高高,,,,,210PIAS-2204HH:300KPa,,,300KPa,开PSV-2204,,,,,

21,231精制,,HS-914B,,,,,HS-914B触发,,,触发,停泵P-2606A/B,,,,,

22,231精制,,231HS-01,,,,,231HS-01触发,,,触发,"停泵P-2601A/B、P-2502A~C、

P-2602A/B",,,,,

23,231精制,,231HS-P2605,,,,,231HS-P2605触发,,,触发,停泵P-2605A/B,,,,,

24,231精制,,1-231-2809,,,,,1-231-I-2809触发,,,触发,停泵P-2605A/B,,,,,

25,231精制,,HS-P2609A/B,,,,,SIS停P-2609A/B泵,,,触发,停泵P-2609A/B,,,,,

26,232浓缩,,TICSA-0205温度高高,,,,,TICSA-0205HH:70℃,,,70℃,"关XV-0202、LV-0202、

开XV-0203、XV-0204、XV-0205",,,,,

27,232浓缩,,TICSA-0213温度高高,,,,,TICSA-0213HH:58℃,,,58℃,"关XV-0202、LV-0202、

开XV-0203、XV-0204、XV-0205",,,,,

28,232浓缩,,PISA-0213压力高高,,,,,PISA-0213HH:20KPaA,,,20KPaA,"关XV-0202、LV-0202、

开XV-0203、XV-0204、XV-0205",,,,,

29,232浓缩,,浓缩紧急停车,,,,,紧急停车按钮按下,,,按下,"关XV-0202、LV-0202、

开XV-0203、XV-0204、XV-0205",,,,,

30,200罐区,,200V-2003A液位低低,,,,,200LIA-2003ALL:0.1%,,,0.1%,关XV-2001A、停泵P-2003A/B,,,,,

31,200罐区,,200V-2003B液位低低,,,,,200LIA-2003BLL:0.1%,,,0.1%,关XV-2001A、停泵P-2003A/B,,,,,

32,200罐区,,200V-2001液位低低,,,,,200LIA-2001LL:5%,,,5%,关XV-2004、停泵P-2001,,,,,

33,200罐区,,手动急停P-2002,,,,,手动急停按下,,,按下,关XV-2006A、停泵P-2002,,,,,

34,200罐区,,手动急停P-2002,,,,,手动急停按下,,,按下,关XV-2006B、停泵P-2002,,,,,

35,200罐区,,手动急停进料,,,,,手动急停按下,,,按下,"关XV-2008、XV-

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论