文档简介

全厂负荷计算表(包括一期现有水厂负荷)序号用电设备名称每台容量(KW)安装台数工作台数需用系数COS计算负4荷备注P(KW)Q(Kvar)S(KVA)一、一期(现有)水厂负4荷(粗格栅、提升泵房、细格栅、沉砂池、加氯间)1粗格栅1.1220.70.701.51.6粗、提2螺旋输送机2.2110.70.801.51.2粗、提3启闭机1.5420.30.700.90.9粗、提4潜水排污泵45540.900.81162.0117.3粗、提5通风机0.25220.50.700.30.3粗、提6电动葫芦4.9110.30.701.51.5粗、提7照明1110.70.900.70.3粗、提8细格栅0.75220.70.701.11.1细、沉9螺旋输送机1.1110.70.700.80.8细、沉10螺旋压榨机3110.70.702.12.1细、沉11启闭机1.5420.30.700.90.9细、沉12砂水分离器0.37110.70.700.30.3细、沉13罗茨风机11210.70.807.75.8细、沉14旋流除砂器0.75220.80.701.21.2细、沉15渣浆泵4110.80.803.22.4细、沉16照明4110.70.902.81.4细、沉17加氯设备26.9110.700.7518.816.6加氯间18照明4110.700.902.81.4加氯间19变电所及路灯15110.700.9010.55.1小计220.5162.0273.6二、一期(现有)水厂负4荷(综合池、办公楼)1鼓风机90640.80.84288.0186.0综合池2行车式吸泥机32.2220.60.8038.629.0综合池3潜水搅拌机9440.900.8032.424.3综合池4潜水搅拌机7.5440.900.8027.020.3综合池5剩余污泥泵5.5220.700.807.75.8综合池6办公楼57110.750.9042.820.7小计436.5286.0三、粗细格栅及曝气沉砂池(二期)1粗格栅清污机1.5330.70.83.22.43潜水排污泵75540.850.82255.0178.04转鼓式格栅清污机3440.70.88.46.35无轴螺旋输送机1.5110.70.81.10.84手电两用启闭机1.1660.20.81.31.06螺旋式砂水分离器0.37110.70.80.30.27双槽吸砂机0.37220.70.80.50.48吸砂桥配套潜水泵1.4220.70.82.01.59罗茨鼓风机15210.80.812.09.0

10渣水分离机0.15110.70.70.10.111照明仪表15110.70.910.55.1小计294.3204.7四、AAO生化池、平流二沉池、絮凝沉淀池、翻板滤池(二期)1潜水搅拌器2.236360.850.867.3250.492潜水回流泵5640.90.818.013.53行车式刮吸泥机1.5220.70.82.11.64刮泥机配套水泵10880.70.8156.040.55框式搅拌机0.45440.80.81.41.16推式液压缸刮泥机4440.70.811.28.47反冲洗水泵48430.50.8272.050.38反冲洗风机90210.50.8445.029.19空压机7.5210.50.83.82.810曝气鼓风机110540.850.85374.0231.811恒压供水设备30110.80.824.018.012加药螺杆泵3540.70.88.46.313醋酸钠加药螺杆泵3320.70.84.23.214助凝剂加药螺杆泵3320.70.84.23.215计量泵3210.70.82.11.616紫外线消毒48220.90.8586.453.517推流器612120.850.861.245.918照明仪表40110.70.928.013.6小计869.32574.89五、污泥脱水间、污泥缓冲池(二期)1离心浓缩脱水机55320.70.877.057.82轴流风机0.25220.80.80.40.33照明仪表15110.70.910.55.1小计87.963.1六、生物除臭、中间提升泵池(二期)1除臭设备35110.800.8028.021.02一期水提升泵30320.900.8154.039.1合计82.060.1七、其它(二期)1变电所照明及自控30110.700.9021.010.22综合楼60110.700.9042.020.33厂区道路照明15110.600.909.04.44其它30110.800.8024.018.0小计96.052.9八、全厂负荷合计1负荷合计2040.21368.82456.92分变电所(一+三+六)596.8426.8733.7总需用系数Kxp=0.85;Kxq=0.9507.3384.1636.3COS=0.80.80

补偿后COS—=0.950.95补偿容量Qc=240Kvar217.4利用一期变电所两台400kVA变压器,同时工作。负荷率为67%。3总变所低压负荷(二+四+五+七)1489.7977总需用系数Kxp=0.85;Kxq=0.91266.29501583COSg0.820.82补偿后COS—=0.950.95补偿容量Qc=550Kvar5331333.1选用两台1000kVA变压器,同时

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论