文档简介

1、 霍霍尼尼韦韦尔尔燃燃烧烧控控制制器器故故障障代代码码故障代码序号Fault Code故障代码System Failure系统故障Fault 1 NO Purge Card无吹扫卡No card is plugged into thepurege card slot无卡插入吹扫卡槽Fault 2AC Frequen/noise交流频率/噪音Excess noise or device runningon slow ac.噪音过大或者设备在低频下运行Fault 3AC Line Dropout交流线路掉线Ac line dropout detected.检测到交流线路掉线Fault 4AC Fr

2、equency交流频率Device running on fast ac.设备在快频下运行Fault 5Low Line Voltage低电压Low ac line detected.检测到低压交流电路Fault 6Purge Card Error吹扫卡错Purge card timing changed sincecard was initially read.由于读了错误卡,吹扫时间改变Fault 7Flame Amplifier火焰放大器Flame sensed when flame notpresent.无火焰时,出现火焰信号Fault 8Flame Amp/Shutr火焰放大/关闭F

3、lame sensed when no signalexpected during shutter-check orAmpli-Check versions.在关闭检查或放大检查方式时,感应到了不该有的信号Fault 9Flame Detected火焰检测Flame sensed when no flame isexpected during STANDBY.在待机时,断路器打开状态,无火焰,出现了火焰信号Fault 10Pre-lIgntion ILK预点火连锁Pre-lIgntion interlock faultduring STANDBY.在待机状态,预点火连锁出错(仅指EC/RM78

4、00,7840,7838B)Fault 11Running ILK On运行连锁开Running interlock powered atimproper sequence point.在不合适的顺序点,运行连锁带电Fault 12Lockout ILK On停运连锁闭合Lockout interlock powered atimproper sequence point.在不合适的顺序点,停运信号带电13Airflow Sw. On空气开关闭合Cmobustion airflow interlockfault during STANDBY.在待机状态,燃烧空气连锁故障14High Fire

5、Sw.高火位火焰开关High Fire interlock Switchfailure to close duringPREPURGE.在预吹扫段,高火焰连锁开关不能关闭15Flame Detected火焰探测Flame sensed when no flame isexpected during STANDBY.在待机状态,无火焰时出现了火焰状态16Flame-Out Timer火焰熄灭No-flame detected during PilotFlame Establishing Period.在长明灯运行期间,检测不到火焰17Main Flame Fail主火焰失败Main flame

6、failure during Runafted flame is established an onofr at least 10 seconds.点火成功后并运行至少10秒后,主火焰熄灭18Flame Detected火焰探测Flame sensed when the shutter isopen and no flame is expectedduring PREPURGE.在预吹扫阶段,断路器打开,无火焰,但是探测到了火焰信号19Main Flame lgn.主火焰点燃Flame was lost during MFEP orthe first 10 seconds of the RUN

7、state.在MEEP或者运行状态最初的10秒钟内,火焰熄灭20Low Fire Sw. Off低位火焰开关断开Low Fire interlock switchfailure to close duringPREPURGE.在预吹扫阶段,低位火焰连锁开关不能闭合21Running ILK运行连锁Running interlock fault duringPREPURGE.在预吹扫阶段,运行连锁故障22Lockout ILK停机连锁Lockout interlock fault duringPREPURGE.在预吹扫阶段,停机连锁故障23Airflow Switch空气连锁Combustion

8、 airflow interlockfault during PREPURGE.在预吹扫阶段,燃烧空气连锁故障24Call Service报警The flame interlock (relaymodule)was on when it should beoff.火焰连锁(继电器)应断开时闭合25Call Service报警The flame interlock (relaymodule)was on when it should beon.火焰连锁(继电器),应闭合时断开26Man-Open Sw. Off手动开关打开The Manual Open Valve Switch wasoff w

9、hen it should be on(Devicespecific)手动开关应闭合时打开(RM7838B)27Start Switch On启动开关闭合Start Switch was on duringPREPURGE(Device specific).在预吹扫阶段,启动开关闭合(仅RM7838A,RM7838B)28Pilot Flame Fail点火火焰失败Pilot flame failure.点火火焰失败29Lockout ILK停机连锁Lockout interlock fault.停机连锁故障30Running ILK运行连锁Running interlock fault.运行

10、连锁故障31Low Fire Sw. Off低位火焰开关断开Low Fire interlock Switchfailure to close duringRUN(Device specific)在运行期间,低火焰连锁开关不能闭合32Airflow Switch空气开关Combustion Airflow interlockfault.燃烧空气开关连锁失败33Pre-Igntion ILK预点火连锁Pre-Igntion interlock fault.预点火连锁失败34Control On控制开CTL input was energized at thewrong time for the

11、relaymodule.This fault implies afield wiring error.在错误的时间,继电器模块控制回路激活35Call Service报警Safety relay was off when itshould be on or the internalfuse has blown.安全继电器应闭合时断开或者保险死熔断36Call Service报警Main valve terminal was off whenit should be on, or the internalfuse has blown.主阀端子应闭合时断开37Call Service报警Pilot

12、(Igntion)valve terminal wasoff when it should be on,or theinternal fuse has blown.燃烧器阀门端子应闭合时断开38Call Service报警Igntion terminal was off when itshould be on,or the internalfuse has blown.点火端子应闭合时断开39Call Service报警V2S valve terminal (usuallyterminal 21)was off when itshould be on,or the internalfuse h

13、as blown.V2S阀端子(通常端子21)应闭合时断开40Call Service报警Safety relay was on when itshould be off.安全继电器应断开时闭合41Main Valve On主阀闭合Main valve terminal was on whenit should be off.主阀端子应断开时闭合42Pilot Valve On点火阀门闭合Pilot(Igntion)Valve terminal wason when it should be off.点火阀端子应断开时闭合43Igntion On点火闭合IIgntion terminal wa

14、s on when itshould be off.点火端子应断开时闭合44Pilot Valve 2 On点火阀2闭合V2S valve terminal,used as apilot,is on when it should beoff.用作点火回路V2S阀端子,应断开时闭合45Low Fire Sw. Off低位火焰开关断开Low Fire interlock switchfailure to close or stay closed.低位火焰连锁开关不能闭合或闭合不开46Flame Amp Type 火焰放大器Device specific.a、当仪器带电时,来自放大器的FFRT或TY

15、PE的输入值改变b、标准的放大器用在了副阀上c、3秒火焰失败响应时间放大器与再点火选择一起用在RM7890继电模块上47Jumpers Changed端子连接卡改变The configuration jumpers differfrom the sample taken atstartup.端子连接卡不同于启动时所用的样品48Delayed MV On (2ndStage Valve)延迟主阀闭合V2S Valve terminal,used as adelayed main valve,was on whenit should be off.用作延迟主阀的VS2阀端子应断开时闭合49Man-

16、Open Sw. On手动开关闭合The manual open switch was onwhen it should be off.手动开关应断开时闭合50Jumpers Wrong连接卡错The sequence logic detected acombination of jumpers that isillegal ofr the sequence,e.g.,ifit is correct to clip jumper JR1or Jumper JR2,but not both,thisfault woould be used when bothare clipped(Device

17、specific).逻辑顺序探测到了不合法的连接卡组合51Flame Too Strong火焰信号太强Flame signal value is too highto be valid.火焰信号太强,以至于无效52Call Service报警Pilot Valve 2 (terminal 21)wasoff when it should be on.副阀2(端子21)应闭合时打开53Lockout Switch停机开关Lockout Input fault (EC/RM7850only)停机输入错误(EC/RM7810,7820,7830,7850)54Comb.Pressure燃烧压力Vom

18、bustion pressure switch fault(Fulton pulse only).燃烧压力故障(仅fulton pulse)55Purge Fan Sw.On吹扫风机开关闭合Purege fan switch is on when itshould be off (Fulton pulseonly).吹扫风机开关应断开时闭合(仅fulton pulse)56Block intake阻塞吸入Block intake fault(Fulton pulseonly).阻塞吸入故障(仅fulton pulse)57Purge Fan Sw. Off吹扫风机开关断开Purege Fan

19、Switch is off when itshould be on(Fulton pulse only).吹扫风机开关应闭合时断开(仅fulton pulse)58Comb. Press/Flame压力开关或传感器Combustion Pressure Switch orFlame Sense Fault (Fulton PulseOnly).压力开关或传感器故障(仅fultonpulse)59-60Call Service报警Unused faults.未用故障61MV1 Off(Terminal 9);should beON.MV1关闭(端子9)将要打开。62MV2 Off(Termina

20、l 17);should beON.MV2关闭(端子17)将要打开。63MV1 ON(Terminal 9);should beOFF.MV1打开(端子9)将要关闭。64MV2 ON(Terminal 17);should beOFF.MV2打开(端子17)将要闭合。65VPS OffValve Proving Switch (Terminal16)OFF;should be ON.(VPS HighTest).66VPS OnValve Proving Switch (Terminal16)ON;should be OFF.(VPS LowTest).67AC Phase交流相L1 and

21、L2 MIswired/exchanged(EC/RM7850 only).L1和L2相接错或交换(仅EC/RM7810,7820,7830,7850)68Pre-Igntion ILK预点火连锁Pre-Igntion Interlock fault.预点火连锁故障69-70Call Service报警Unused faults.未用故障71dynamic LFC动态LFCLow Fire Switch closed,High FireSwitch must be open (EC/RM 7850only).低压开关闭合时,高压开关必定打开(EC/RM7850)71Limits Complet

22、e极限完成Special Function 2 Input(terminal 17)is off when itshould be on (Device specific).极限输入(端子7)应闭合时打开(仅RM7888)72Dynamic HFS动态 HFCHighFire Switch closed;Low FireSwitch must open(EC/RM 7850only). 高压开关闭合,低压开关必定打开(仅EC/RM7850)72Spec.Func.2特殊功能2Special Function 2 Input(terminal 17)is off when itshould be

23、 on(Device specific).特殊功能2输入(端子17)应闭合时打开73Spec.Func.3特殊功能3Special Function 3 Input(terminal 19)is off when itshould be on(Device specific).特殊功能3输入(端子17)应闭合时打开75Flame ProvenFeedback火焰证明反馈Flame Indication Feedback(terminal 21)tither on when itshould be off or off when itshould be on (Device specific).

24、 火焰指示反馈(端子21)应断开时闭合,或者应闭合时断开76-87Accessory Fault报警88Accessory Fault报警T17 powered without RMprogrammed.89Accessory Fault报警T6 and T17 powered.90Accessory Fault报警T7 opens on RM7890 wotj VPSFeature91-93Accessory Fault报警94-104Call Service报警105Call Service报警Relay Module self-test failure.继电器模块自检失败106Call

25、Service报警Relay Module self-test failure.继电器模块自检失败107Call Service报警Relay Module flame signalcrosscheck failure.继电器模块火焰信号复检失败108Call ServiceLost E2 or device shippedunprogrammed.109Call Service报警Negative cycle test failed,earthground absent or line voltagephasing improper.负循环检测失败,没有接地或者线电压相间不合适110Call

26、 Service报警The configuration jumpers differfrom stored values.连接卡子形状与储存值不同111Call Service报警Relay Module configurationjumper test failure.继电器模块,连接卡测试失败112-126Call Service报警Relay Module self-test failure.继电器模块自检失败127Call Service报警Safety relay feedback circuitwas in an improper state.安全继电器反馈回路处于不合适状态解决措

27、施1、确保吹扫卡是正确安装的。2、观察吹扫卡和卡槽完好。3、重起和顺序启动延时模块。4、如果错误代码还出现,更换吹扫卡。5、重启和顺序启动延时模块。6、如果再出现,更换延时模块。1、检查延时模块和显示模块的连接。2、重起和顺序启动延时模块。检查延时模块的电压等,确保电压和频率都是在技术范围以内。1、确保吹扫卡是正确安装的。2、观察吹扫卡和卡槽完好。3、重起和顺序启动燃烧延时模块。4、如果错误代码还出现,更换吹扫卡。5、如果再出现,更换延时模块。1、检查接线,并纠正错误。确保火焰检测器的接线是隔离的。检查火焰检测器的引线正常。2、确保火焰检测器和放大器是兼容的。3、检查火焰放大器连接,重起。4、

28、重起和顺序启动延时模块。5、如果这个故障代码还出现,更换放大模块或者燃烧检测器。6、如果还出现故障,更换延时模块。 霍霍尼尼韦韦尔尔燃燃烧烧控控制制器器故故障障代代码码1、检查燃烧室的火焰,纠正存在的错误。2、检查接线。确保接线是隔离的,引线也正常。3、检查火焰放大器连接,重起。4、重起和顺序启动延时模块。5、如果这个故障代码还出现,更换放大模块或者燃烧检测器。6、如果还出现故障,更换延时模块。1、检查接线,并纠正错误。2、检查预点火连锁开关,确保功能正常。3、检查燃料阀开启。4、重起和顺序启动延时模块。观察连锁状态。5、如果故障还出现,更换延时模块。1、检查接线确保端子6和端子7的连锁是正常

29、的。2、重起并顺序启动延时模块。3、如果故障还出现,测量端子6和地线、端子7和地线间的电压。如果控制器关了,端子6还有线电压,那么控制器坏了或者短路了1、检查接线,并纠正错误。2、重起和顺序启动燃烧控制器。3、用手动马达电位计或者用“run /test ”选项使伺服电机到大火位置。4、在预吹扫到大火位置,确保在端子19和接地之间的电压。线电压应当呈现。如果没有,开关调节是错误或者开关有缺陷需要更换。重起和顺序启动燃烧控制器,如果有线电压,错误还出现,那么更换延时模块。1、检查接线,并纠正错误。确保火焰检测器的接线是隔离的。检查火焰检测器的引线正常。2、确保火焰检测器和放大器是兼容的。3、检查火

30、焰放大器连接,重起。4、重起和顺序启动延时模块。5、如果这个故障代码还出现,更换放大模块或者燃烧检测器。6、如果还出现故障,更换延时模块。1、检查 燃烧室没有出现火焰, 纠正错误。2、确保火焰放大器和火焰检测器是配套的。3、检查接线和纠正错误。4、移开火焰放大器,观察连接器,然后重新装上。5、重起和顺序燃烧控制器。6、如果代码还出现,更换火焰放大器或者火焰检测器。7、如果还出现错误,更换延时模块。1、确保火焰信号。如果有火焰,要确保火焰性能,保证燃烧器是按说明书调节的。2、确保火焰放大器和检测器是配套的。3、如果代码还出现,更换火焰放大器或者火焰检测器。4、如果还出现,更换延时模块。1、检查主

31、燃料阀和各种连接。2、确保燃料压力是正常的。3、检查火焰检测器可以探测到适当的火焰信号通过燃烧器的火焰的配比。1、检查燃烧室没有出现火焰。并纠正错误。2、确保火焰放大器和火焰检测器是配套的。3、检查接线和纠正错误。确保F和G的线为了保护,各自隔离。4、移开火焰放大器,观察连接器,然后装上。5、重起和顺序启动燃烧控制起。6、如果代码还出现,更换火焰放大器或者火焰检测器。7、如果故障还出现,更换延时模块。1、检查主燃料阀和各种连接。2、确保燃料压力是正常的。3、确保火焰检测器的位置可以得到火焰信号;1、检查接线,并纠正错误。2、重起和顺序启动燃烧控制器。3、用手动马达电位计或者用“run /tes

32、t ”选项使伺服电机到小火位置。4、在预吹扫到小火位置,确保在端子18和接地之间的电压。线电压应当呈现。如果没有,开关调节是错误或者开关有缺陷需要更换。5、重起和顺序启动燃烧控制器,如果有线电压,错误还出现,那么更换延时模块。1、检查接线和纠正错误。2、检查风机,确保风机正常。3、确保连锁开关都是OK的,开关接触器是干净无污染。4、重起和顺序启动燃烧控制器。测量端子7和接地之间的电压,应该有线电压。5、如果1到4步都已经纠正而故障仍然出现,那么更换延时模块。1、检查引线F,确保隔离1、检查接线和纠正错误。2、确保手动阀门完全打开。3、确保手动阀门功能OK,开关接触器是干净无污染的。4、重起和顺

33、序启动燃烧控制器。5、确保手动阀门关闭的时候可以提供一个电路,检查燃烧控制器在端子17上得到电源。6、如果1到5步纠正了,故障还出现,更换延时模块。1、启动开关保持时间过长。2、检查接线,检查启动开关正确连接。3、确保启动开关功能OK,接触器无污染。4、重起和顺序启动到预吹扫,设置run/test开关到test。确保在预吹扫的状态,端子6上无电源。5、如果1到3步都已纠正,故障还出现,那么更换延时模块。1、检查点火阀门的接线和运行。纠正错误。2、检查燃料供应。3、检查点火压力。4、检查点火变压器,火焰检测器,火焰检测器灯泡和火焰放大器。5、如果1到4步都已经纠正,鼓掌还出现,那么更换延时模块。

34、1、检查接线,纠正各种错误。2、检查风机,确保风机一切正常。确保连锁开关工作正常,开关接触器干净。3、重起和顺序启动燃烧控制器至预吹扫状态。4、测量端子和接地线的电压,应该有线电压。5、如果1到4步都已经纠正,故障还出现,更换延时模块。1、检查运行连锁,包括空气开关和连接器。2、确保运行连锁,空气开关等功能OK,接触器无污染。3、重起和 顺序启动延时模块至预吹扫状态。设置run/test开关,如果有用,至test 。测量端子和接地线之间的电压,应该有线电压。4、如果1到3步=都已经OK,故障还出现,更换延时模块 。1、检查接线;纠正各种错误。2、重起和顺序启动延时模块。3、用手动马达电位计或者

35、用“run /test ”选项使伺服电机到小火位置。如果有用,在test状态下,调到小火位置。调节小火开关在这个状态下。4、当run状态下,到小火位置,测量端子18和接地线间的电压。5、重起和顺序启动延时模块,如果线电压还有,故障出现,更换延时模块。1、检查接线并纠正各种错误。2、检查风机,确保风机一切正常。3、确保空气连锁开关运行良好,开关接触器无污染。4、重起和顺序启动至预吹扫状态。在test状态下运行,如果可用。测量端子和接地线之间的电压,应该有线电压。5、如果1到4步已经纠正,故障还出现,那么更换延时模块。1、检查接线并纠正各种错误。2、检查预点火连锁开关,确保一切正常。3、检查燃料阀

36、门,阀门可以栽秒内可以关闭。4、重起和顺序启动延时模块。5、在待机或着预吹扫状态,测量电压在端子20和接地线之间。对于型号EC/RM7810,7820,7830,7850,在端子17和接地线之间测量。应该有线电压。如果没有,预吹扫连锁开关可能损坏需要更换。6、如果故障还出现,需要更换延时模块。1、检查接线并纠正各种错误。2、重起和顺序启动延时模块。3、如果还出现故障,更换延时模块。1、重起和顺序启动延时模块。如果还出现,更换延时模块。但是要注意端子上有无超载,由于故障的出现。2、如果在第二次运行中,没有出现故障,象故障代码所描述的那样去检查接入延时模块的电压是否有电子干扰。3、如果故障还出现,

37、更换。警告! 爆炸危险可能导致爆炸、严重的伤害或者死亡。1、断开电源,切断燃料。2、检查接线并纠正各种错误。3、重新合上电源,重起和顺序启动延时模块。4、如果故障还出现,更换延时模块。5、当故障已经纠正,供应燃料。1、检查接线并纠正各种错误。2、重起和顺序启动延时模块。3、如果可以,用手动马达电位计或者用“run /test ”选项使伺服电机到小火位置。选择run,在test状态下到达小火位置。调节小火位置开关,确保慢慢关闭。4、当在run时,运行至小火位置,测量端子18和G之间的电压。应该有线电压。如果没有,开关调节是错误的或者开关损坏需要更换。5、如果1到4步都已经纠正,故障还出现,那么请

38、更换延时模块。1、切断电源。2、重装火焰放大器,然后重起延时模块。1、检查端子连接卡,确保其正常。2、重起延时模块。3、如果错误还继续,则需更换。警警告告! 爆炸危险可能导致爆炸、严重的伤害或者死亡。1、断开电源,切断燃料。2、检查接线并纠正各种错误。3、检查V2S燃料阀及其连接,确保连接都是正常的。4、重起。5、如果故障继续,则需更换。警警告告! 爆炸危险可能导致爆炸、严重的伤害或者死亡。1、断开电源,切断燃料。2、检查接线并纠正各种错误。3、检查受动阀及其连接,确保连接都是正常的。4、重起。5、如果故障继续,则需更换警告! 爆炸危险可能导致爆炸、严重的伤害或者死亡。1、断开电源,切断燃料。

39、2、检查接线并纠正各种错误。3、重新合上电源,重起和顺序启动延时模块。4、如果故障还出现,更换延时模块。5、当故障已经纠正,供应燃料。1、检查连接卡按照说明书,确保合适。2、确保其完全断开。3、重起。4、如果故障还出现,则需要更换。1、确保火焰放大器和火焰检测器是配套的。2、移开火焰放大器,检查连接,然后重装。3、重起和顺序启动延时模块。4、检查火焰检测器的观察位置。5、测量火焰强度。是否符合技术要求。5、确保没有干扰出现,由于接线造成的F引导。6、测量火焰强度。确保它达到特性。如果没有,参考火焰放大器和或火焰探测器检查步骤。7、如果代码重复出现,更换火焰放大器。8、如果代码重复重现,更换火焰

40、探测器。9、如果故障还出现,则需更换火焰放大器或者火焰检测器。1、检查端子21及其连接。确保阀门OK。2、重起和顺序启动延时模块。3、如果故障还出现,则需更换。1、检查接线并纠正各种错误。2、检查燃烧室压力是否正常。3、重起和顺序启动延时模块。在待机或者预吹扫时候,测量端子20和G之间的电压。应该存在电压。如果没有,检查连锁开关是否正常。4、如果还出现故障,则需更换。1、检查接线并纠正各种错误。2、检查燃烧室压力是否正常。3、重起和顺序启动延时模块。在待机或者预吹扫时候,测量端子20和G之间的电压。应该存在电压。如果没有,检查压力开关是否正常。4、如果还出现故障,则需更换。1、检查接线并纠正各种错误。2、检查端子18及其连接。确保开关正常。3、重起和顺序启动延时模块。4、如果该故障还出现,则需更换。1、检查接线。2、检查吸入开关正常。3、重起和顺序启动延时模块。4、在预吹扫状态,测量端子7和G 之间的电压。应该有电压,如果没有,检查该开关是否正常。5、如果该故障还出现,则需更换。1、检查端子18及其连接。确保该开关正常。2、重起和顺序启动延

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论