文档简介
商场空调系统的送风量与气流组织计算案例综述1送风量计算 图4-1空气处理过程以1001商铺为例进行设计计算。1.确定N点,hN=88.7kJ/kg,dN=21.1g/kg2.确定送风点O根据温差∆t,就能得到送风点O,tO=28℃,hO=843.送风量G=Q其他房间亦如上计算,见表4-1:表4-1各风量计算表房间号总冷负荷(W)新风量(m3/h)室内湿负荷(kg/h)送风量(m3/h)送风量(m3/s)回风量(m3/h)10014414.88201.62.9920.6310.256719.03110022528.4949.990.95766.9090.213716.91910032570.7855.540.94742.440.206686.910047873.46345.64.971673.570.4711327.9710057918.61345.64.971714.310.4761368.7110067873.46345.64.971673.570.4711327.9710077873.46345.64.971673.570.4711327.9710087918.61345.64.971714.310.4761368.7110097873.46345.64.971673.570.4711327.9710102528.4955.540.94742.440.206686.910112570.7849.990.95766.9090.213716.91910124414.88201.62.9920.6310.256719.03110134623.67501.471393.850.0141343.8510148949.74345.64.972113.790.5871768.1910157918.61345.64.971714.310.4761368.7110167873.46345.64.971673.570.4711327.9710178949.74345.64.972113.790.5871768.1910187918.61345.64.971714.310.4761368.7110198949.74345.64.972113.790.5871768.1910204623.670501.471393.850.0141343.851层小计126166.624861.4672.1629214.127.397824352.662风机盘管选型使用开利系列风机盘管机组,根据每个房间的回风量和冷负荷选择合适的风机盘管,以1001为例,房间的回风量为719.031m3/h,冷负荷为4414.88W,故选择型号为42CE006200A的风机盘管,风量(中速)为820m3/h,制冷量(中速)为4654.7W,其他房间选型见表4-2:表4-2各房间风机盘管选型房间号风机盘管型号风机盘管风量m³/h台数100142CE006200A1392.491100442CE012200A663.9852100542CE012200A684.3552100642CE012200A663.9852100742CE012200A663.9852100842CE012200A684.3552100942CE012200A663.9852续表101242CE010200A1392.492101342CE006200A671.9252101442CE012200A884.0952101542CE012200A684.3552101642CE012200A663.9852101742CE012200A884.0952101842CE012200A684.3552101942CE012200A884.0952102042CE006200A671.92523气流组织计算新风进入室内的地方应该装设合适的风阀。面积应该达到新风量随各个季节的不同的最大风量要求。以1001商铺为例,空调房间30.24m2,净高3.6m,单个房间的送风量为0.256m3/s。散流器类型选用方形散流器,每一个散流器的送风范围为9m2(3m×3m),该房间内安放2个。首先选择散流器,计算散流器出口风速。散流器的尺寸为300mm×300mm,出口风速按不大于5m/s选择:v实际上散流器的出口面积大约是原尺寸的90%,所以出口的实际风速为vs=3×0.9=2.7m/s。2.因为工作区风速应≤0.3m/s,所以计算当某处风速为0.3m/s时该点与风口的距离。x=3.可按以下公式计算出房间内风速的平均值:v符合室内风速要求。设计结果:不影响人们对室内环境的观感,本设计中各个房间送风口设计见表4-3:表4-3各个房间送风口设计房间号室内面积(m2)送风口室内平均风速(m/s)送风口尺寸㎡送风口面积㎡颈部风速m/s散流器实际出风口面积㎡散流器实际出风口风速m/s射流末端速度为0.5m/s的射程m100130.24300×3000.093.0000.0812.72.0820.169100230.24250×2500.06253.5000.056253.152.0220.164100333.6250×2500.06253.5000.056253.152.0220.164100451.84400×4000.163.0000.1442.72.7990.237100551.84400×4000.163.0000.1442.72.7990.237100651.84400×4000.163.0000.1442.72.7990.237100751.84400×4000.163.0000.1442.72.7990.237100851.84400×4000.163.0000.1442.72.7990.237100951.84400×4000.163.0000.1442.72.7990.237101033.6250×2500.06253.5000.056253.152.0220.164101130.24250×2500.06253.5000.056253.152.0220.164101230.24300×3000.093.0000.0812.72.0820.169101351.84360×3600.12963.0000.116642.72.5120.213101451.84400×4000.164.0000.1443.63.7550.318101551.84400×4000.163.0000.1442.72.7990.237101651.84400×4000.163.0000.1442.72.7990.237101751.84400×4000.164.0000.144
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 2024年生物制药研发生产许可使用合同
- 2024年电子商务平台技术开发及运营转让合同
- 定期动产赠与合同范例
- 水果生鲜加盟合同范例
- 活动板房购买合同范例
- 混泥土道路施工方案
- 汕头大学《创意立体剪裁》2023-2024学年第一学期期末试卷
- 2024至2030年返捻机项目投资价值分析报告
- 残联合同范例
- 2024至2030年氯碳化硅项目投资价值分析报告
- IATF16949-过程审核检查表-(含审核记录)-
- 《万疆》歌词全篇
- 电大劳动与社会保障法期末考试(已排版)
- JJF(纺织)074-2018羽绒蓬松度仪校准规范
- GB/T 709-2019热轧钢板和钢带的尺寸、外形、重量及允许偏差
- GB/T 23935-2009圆柱螺旋弹簧设计计算
- 癫痫发作急救及应急预案考核试题及答案
- 【课件】读后续写 suspended coffee
- GB/T 14048.15-2006低压开关设备和控制设备第5-6部分:控制电路电器和开关元件接近传感器和开关放大器的DC接口(NAMUR)
- 2023年上海各区中考物理一模卷及答案
- powerpoint 演示文稿 - 链表的基本概念
评论
0/150
提交评论