![[广东]10万平办公楼电气全套施工图含负荷计算书139张(2016知名设计所)_第1页](http://file4.renrendoc.com/view/157127ace6a013eafccce077ff3a9731/157127ace6a013eafccce077ff3a97311.gif)
![[广东]10万平办公楼电气全套施工图含负荷计算书139张(2016知名设计所)_第2页](http://file4.renrendoc.com/view/157127ace6a013eafccce077ff3a9731/157127ace6a013eafccce077ff3a97312.gif)
![[广东]10万平办公楼电气全套施工图含负荷计算书139张(2016知名设计所)_第3页](http://file4.renrendoc.com/view/157127ace6a013eafccce077ff3a9731/157127ace6a013eafccce077ff3a97313.gif)
![[广东]10万平办公楼电气全套施工图含负荷计算书139张(2016知名设计所)_第4页](http://file4.renrendoc.com/view/157127ace6a013eafccce077ff3a9731/157127ace6a013eafccce077ff3a97314.gif)
![[广东]10万平办公楼电气全套施工图含负荷计算书139张(2016知名设计所)_第5页](http://file4.renrendoc.com/view/157127ace6a013eafccce077ff3a9731/157127ace6a013eafccce077ff3a97315.gif)
版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、表格内容,A-TM1 变压器负荷计算表,阶段,施工图,箱系统,用电设备名称,安装容量,安装容量,需要系数,功率因数,正切值,有功功率,无功功率,视在功率,计算电流,备注,系统备注,配电箱编号,需要系数,有功率率,功率因数,计算电流,整定值,1.2Ij,1.5Ij,电缆,电缆,Ps(kW)-火灾,Ps(kW),(kx),Cos,tg,Pjs(kW),Qjs(kVar),Sjs(kVA),Ijs(A),主/备,负荷等级,(kx),Pjs(kW),Cos,Ijs(A),(A),型号,外径A塔办公811层办公用电,416.0 ,0.70 ,0.80 ,0.75,291.2 ,218.4 ,364.0
2、,553.1,三级负荷,0.8,332.8,0.80 ,632 ,800.0 ,759 ,948 ,3*150,162.3A塔办公1215层办公用电,417.0 ,0.70 ,0.80 ,0.75,291.9 ,218.9 ,364.9 ,554.4,三级负荷,0.8,333.6,0.80 ,634 ,800.0 ,761 ,951 ,3*150,162.3,A塔815层公共区小动力,109.0 ,0.70 ,0.80 ,0.75,76.3 ,57.2 ,95.4 ,144.9,三级负荷,0.8,87.2,0.80 ,166 ,200.0 ,199 ,249 ,2*120,99.0 ,A塔12
3、,24弱电用电,32.0 ,0.70 ,0.80 ,0.75,22.4 ,16.8 ,28.0 ,42.5,主用,一级负荷,0.8,25.6,0.80 ,49 ,63.0 ,58 ,73 ,16.0 ,22.4 A塔低区客梯1,70.0 ,0.22 ,0.70 ,1.02,15.4 ,15.7 ,22.0 ,33.4,主用,一级负荷,0.85,59.5,0.70 ,129 ,160.0 ,155 ,194 ,150.0 ,54.1 A塔低区客梯2,70.0 ,0.22 ,0.70 ,1.02,15.4 ,15.7 ,22.0 ,33.4,主用,一级负荷,0.85,59.5,0.70 ,129
4、,160.0 ,155 ,194 ,150.0 ,54.1 A塔高区客梯1,140.0 ,0.22 ,0.70 ,1.02,30.8 ,31.4 ,44.0 ,66.9,主用,一级负荷,0.85,119,0.70 ,258 ,315.0 ,310 ,388 ,185.0 ,60.5 A塔高区客梯2,140.0 ,0.22 ,0.70 ,1.02,30.8 ,31.4 ,44.0 ,66.9,主用,一级负荷,0.85,119,0.70 ,258 ,315.0 ,310 ,388 ,185.0 ,60.5 ,A塔8屋顶应急照明,32.0 ,0.80 ,0.90 ,0.48,25.6 ,12.4 ,
5、28.4 ,43.2,主用,消防负荷,0.8,25.6,0.90 ,43 ,63.0 ,52 ,65 ,16.0 ,22.4 A塔屋顶消防电梯,70.0 ,0.22 ,0.70 ,1.02,15.4 ,15.7 ,22.0 ,33.4,主用,消防负荷,0.8,56,0.70 ,122 ,160.0 ,146 ,182 ,95.0 ,44.1 ,A塔屋顶消防动力,111.0 ,0.0 ,0.00 ,0.80 ,0.75,0.0 ,0.0 ,0.0 ,0.0,主用,消防负荷,1,111,0.80 ,211 ,250.0 ,253 ,316 ,35.0 ,28.8 ,桥架宽度,770.5 合计,11
6、1.0 ,1496.0 ,815.2 ,633.7 ,1032.6 ,1568.8,按供电局要求取变压器容量1/41/3为补充量,总补偿量(单位Kvar)300,1.3,1001.65同时系数 K,0.85 ,692.9 ,538.7 ,877.7 ,1333.5,1000电容补偿 Cos=0.92, ,0.92 ,0.43,692.9,295.2,753.2 ,无功功率补偿量,243.5,实际负荷(补偿后),0.95 ,0.34,692.9 ,238.7 ,732.9 ,1113.5 ,干式变压器容量(KVA),1000, ,变压器负荷率为,0.73, ,有功、无功损耗,7.3 ,36.6
7、,高压侧,0.93 ,700.2 ,275.3 ,752.4 ,表格内容,A-TM2 变压器负荷计算表,阶段,施工图,箱系统,用电设备名称,安装容量,安装容量,需要系数,功率因数,正切值,有功功率,无功功率,视在功率,计算电流,备注,系统备注,配电箱编号,需要系数,有功率率,功率因数,计算电流,整定值,1.2Ij,1.5Ij,电缆,电缆,Ps(kW)-火灾,Ps(kW),(kx),Cos,tg,Pjs(kW),Qjs(kVar),Sjs(kVA),Ijs(A),主/备,负荷等级,(kx),Pjs(kW),Cos,Ijs(A),(A),型号,外径A塔办公1619层办公用电,420.0 ,0.70
8、 ,0.80 ,0.75,294.0 ,220.5 ,367.5 ,558.4,三级负荷,0.8,336,0.80 ,638 ,800.0 ,766 ,958 ,3*150,162.3A塔办公2023层办公用电,422.0 ,0.70 ,0.80 ,0.75,295.4 ,221.6 ,369.3 ,561.0,三级负荷,0.8,337.6,0.80 ,641 ,800.0 ,770 ,962 ,3*150,162.3,A塔1623层公共区小动力,111.0 ,0.70 ,0.80 ,0.75,77.7 ,58.3 ,97.1 ,147.6,三级负荷,0.8,88.8,0.80 ,169 ,2
9、00.0 ,202 ,253 ,2*120,99.0 ,A塔815层走道照明,32,0.70 ,0.85 ,0.62,22.4 ,13.9 ,26.4 ,40.0,一级负荷,0.8,25.6,0.85 ,46 ,63.0 ,55 ,69 ,16,22.4A塔1623层走道照明,32,0.70 ,0.85 ,0.62,22.4 ,13.9 ,26.4 ,40.0,一级负荷,0.8,25.6,0.85 ,46 ,63.0 ,55 ,69 ,16,22.4,A塔屋顶擦窗机用电,50,0.60 ,0.80 ,0.75,30.0 ,22.5 ,37.5 ,57.0,三级负荷,0.8,40,0.80 ,7
10、6 ,100.0 ,91 ,114 ,35,28.8A塔泛光用电,50,0.30 ,0.80 ,0.75 ,15 ,11.3 ,19 ,28.5 ,三级负荷,0.8,40,0.80 ,76 ,100.0 ,91 ,114 ,35,28.8A塔普通动力用电,37,0.70 ,0.80 ,0.75 ,25.9 ,19.4 ,32.4 ,49.2 ,三级负荷,0.8,29.6,0.80 ,56 ,80.0 ,67 ,84 ,50,33.4,A塔预留航空障碍灯用电,15,0.70 ,0.90 ,0.48 ,11 ,5.1 ,12 ,17.7 ,重要负荷,0.8,12,0.90 ,20 ,32.0 ,2
11、4 ,30 ,25,26.2A塔预留办公用电,302,0.00 ,0.80 ,0.75 ,0.0 ,0.0 ,0.0 ,0.0 ,重要负荷,0.8,241.6,0.80 ,459 ,500.0 ,551 ,689 ,2*185,121,A塔低区客梯1,105.0 ,0.00 ,0.70 ,1.02,0.0 ,0.0 ,0.0 ,0.0,备用,一级负荷,0.85,89.25,0.70 ,194 ,250.0 ,233 ,291 ,150.0 ,54.1 A塔低区客梯2,105.0 ,0.00 ,0.70 ,1.02,0.0 ,0.0 ,0.0 ,0.0,备用,一级负荷,0.85,89.25,0.
12、70 ,194 ,250.0 ,233 ,291 ,150.0 ,54.1 A塔高区客梯1,135.0 ,0.00 ,0.70 ,1.02,0.0 ,0.0 ,0.0 ,0.0,备用,一级负荷,0.85,114.75,0.70 ,249 ,315.0 ,299 ,374 ,185.0 ,60.5 A塔高区客梯2,135.0 ,0.00 ,0.70 ,1.02,0.0 ,0.0 ,0.0 ,0.0,备用,一级负荷,0.85,114.75,0.70 ,249 ,315.0 ,299 ,374 ,185.0 ,60.5 A塔12,24弱电用电,32.0 ,0.00 ,0.80 ,0.75,0.0 ,
13、0.0 ,0.0 ,0.0,备用,一级负荷,0.8,25.6,0.80 ,49 ,63.0 ,58 ,73 ,16.0 ,22.4 ,A塔8屋顶应急照明,13.0 ,0.00 ,0.90 ,0.48,0.0 ,0.0 ,0.0 ,0.0,备用,消防负荷,0.8,10.4,0.90 ,18 ,63.0 ,21 ,26 ,16.0 ,22.4 A塔屋顶消防电梯,70.0 ,0.00 ,0.70 ,1.02,0.0 ,0.0 ,0.0 ,0.0,备用,消防负荷,1,70,0.70 ,152 ,200.0 ,182 ,228 ,95.0 ,44.1 ,A塔屋顶消防动力,111.0 ,0.0 ,0.00 ,0.80 ,0.75,0.0 ,0.0 ,0.0 ,0.0,备用,消防负荷,1,111,0.80 ,211 ,250.0 ,253 ,316 ,35.0 ,28.8 ,桥架宽度,1053.5 合计,0.0 ,2066.0 ,793.3 ,586.3 ,986.5 ,1498.8,按供电局要求取变压器容量1/41/3为补充量,总补偿量(单位Kvar)300,1.3,1369.55同时系数 K,0.85 ,674.3 ,498.
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 影视设备智能穿戴设备集成考核试卷
- 石墨在微波吸收材料的研究考核试卷
- 森林保护与青少年素质教育考核试卷
- 生活的苦与乐初三语文作文
- 朋友初三语文作文
- 河南省洛阳市老城区三校联考2023-2024学年八年级下学期7月期末考试数学试卷(含答案)
- 桥梁施工技术与质量控制考核试卷
- 纸质航空航天材料研发与性能评价考核试卷
- 玩具企业的产品线拓展与市场定位考核试卷
- 等离子体刻蚀设备的安全控制考核试卷
- 提升员工安全素质与技能
- 劳务派遣劳务外包服务方案(技术方案)
- 趣说中国史宋朝篇
- 委托持股协议
- 债权人自愿放弃债权承诺书
- 拔罐技术操作考核评分标准
- 工业机器人操作与运维实训(高级)-教学大纲、授课计划
- 蛤蟆先生去看心理医生
- 心脏康复护理专家共识PPT
- 外墙外保温抗裂砂浆抹面工程检验批质量验收记录表
- 买卖合同纠纷起诉状范本
评论
0/150
提交评论