文档简介
1、风机盘管技术要求一、 设备一览表表一:*国际大酒店四管制风机盘管设备技术参数一览表地下三层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台FCU2002.27/1235.6/27.92.4160/50-2.42804130220-1-501.6302卧式暗装FCU4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.6301卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.469
2、08730220-1-501.6305卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.6402卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6401卧式暗装地下二层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-5
3、01.6305卧式暗装FCU4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.6302卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.6304卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64015卧式暗装地下一层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装F
4、CU2002.27/1235.6/27.92.4160/50-2.42804130220-1-501.63033卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6305卧式暗装FCU4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.63017卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63016卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.640
5、39卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.64013卧式暗装FCU120010.87/1235.6/27.97.6760/50-2.4163021230220-1-501.6405卧式暗装一层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.63011卧式暗装FCU
6、4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.6301卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63014卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.6409卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6404卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.
7、6406卧式暗装FCU120010.87/1235.6/27.97.6760/50-2.4163021230220-1-501.6403卧式暗装二层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.6306卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.6401卧式暗装FCU1
8、0009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6402卧式暗装FCU120010.87/1235.6/27.97.6760/50-2.4163021230220-1-501.6406卧式暗装三层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6304卧式暗装FCU4004.047/12
9、35.6/27.93.8860/50-2.45507130220-1-501.6305卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.6302卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64016卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6402卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.64012卧式暗装四层
10、机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6302卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63030卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.6406卧式暗装FCU8007.627/1235.
11、6/27.96.1560/50-2.4110015030220-1-501.6406卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6402卧式暗装五、六层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6304卧式暗装FCU5004.967/1235.6/27.94.4
12、260/50-2.46908730220-1-501.63060卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64012卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.64012卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6404卧式暗装七九层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干
13、球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.63012卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63096卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64024卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.64012卧式暗装FCU10009.027/1235.6/27
14、.97.2460/50-2.4136017430220-1-501.6406卧式暗装十层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6305卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63026卧式暗装FCU6005.987/1235.6/27.95.260/50-2.
15、483010830220-1-501.64010卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6406卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6402卧式暗装十一层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530
16、220-1-501.6309卧式暗装FCU4004.047/1235.6/27.93.8860/50-2.45507130220-1-501.6303卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63021卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64011卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6408卧式暗装FCU10009.027/1235.6/27.97.2460/50-
17、2.4136017430220-1-501.6402卧式暗装十二层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6308卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63022卧式暗装FCU6005.987/1235.6/27.95.260/50-2.48301083022
18、0-1-501.64018卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6406卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6402卧式暗装十三层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6
19、305卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.6305卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.64029卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-501.6406卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6406卧式暗装FCU120010.87/1235.6/27.97.6760/50-2.4163021
20、230220-1-501.6402卧式暗装十四层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63029卧式暗装FCU6005.987/1235.6/27.95.260/50-2.483010830220-1-501.6404卧式暗装FCU8007.627/1235.6/27.96.1560/50-2.4110015030220-1-50
21、1.6406卧式暗装FCU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6402卧式暗装十五层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6302卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.63010卧式暗装F
22、CU10009.027/1235.6/27.97.2460/50-2.4136017430220-1-501.6406卧式暗装十六层机型冷水盘管热水盘管中档风量单台耗电量出口静压电源工作压力最大水压降台数备注中档制冷量(全热)进出水温进风干/湿球温度中档制热量进出水温进风干球温度KWKWm3/hWPaV-HzMPaKPa台卧式暗装FCU3003.17/1235.6/27.93.1660/50-2.44105530220-1-501.6302卧式暗装FCU5004.967/1235.6/27.94.4260/50-2.46908730220-1-501.6306卧式暗装FCU120010.87/
23、1235.6/27.97.6760/50-2.4163021230220-1-501.6406卧式暗装注:出口静压请投标单位将12Pa和50Pa全型号进行报价。表二:*国际大酒店四管制风机盘管设备台数一览表序号机型地下三层地下二层地下一层一层二层三层四层五、六层七至九层十层十一层十二层十三层十四层十五层十六层台数汇总备注1FCU200233352FCU300551142412598522743FCU40012171653354FCU50054161423060962621225291063465FCU600215399116612241011182941966FCU80011342261212
24、68666847FCU10006612246222626568FCU1200532616二、技术要求1.招标范围及与相关专业界面划分1.1招标范围为四管制风机盘管、液晶温控器的供应;1.2投标人负责生产、制造、运输、供应、指导安装和配合调试。1.3风机盘管、液晶温控器的安装由机电总包施工单位完成。2关于招标技术要求的说明2.1本技术要求提出的各项功能要求和技术指标是最基本的要求,并未对一切细节作出全面详细规定,也未充分引述有关标准和规范的条文,投标人所提供的设备产品技术性能均应符合招标时已颁布的最新中国国家和行业标准或相关国际标准的规定。2.2投标人必须完成风机盘管的供应,所提供的文件资料必须
25、符合本技术要求和国家相关标准。3. 风机盘管技术要求3.1 标准和规范。所有材料设备制造工艺必须符合以下最新的法定标准、条例、规范和工作准则:(1)电机基本技术GB755;(2)电工电子产品基本环境试验规程GB2423.3;(3)采暖通风与空气调节设备噪声声功率级的测定工程法GB9068;(4)冷暖通风设备型号编制方法JB/T4302;(5)房间风机盘管空气调节器安全要求ZBJ 72018;(6)盘管耐压试验与密封性检查JB/T 9064;(7)冷暖通风设备 包装通用技术条件JB/T 9065;(8)冷暖通风设备外观质量清洁度JB/T 7246;(9)民用建筑供暖通风与空气调节设计规范GB50
26、736;(10)电动机外壳防护分级GB4942.1;(11)通风与空气工程施工质量验收规范GB50243;(12)建筑给水排水及采暖工程施工质量验收规范GB50242;(13)风机盘管机组GB/T19232。3.2 倘若上述各技术要求之间互相出现矛盾或发生抵触时,必须以标准中较高者为准则。3.3 运行技术参数:(1)工作电压:AC220V;(2)工作频率:50HZ;(3)低压配电系统接地型式:TN S。3.4 风机盘管专用技术要求。3.4.1 风机盘管的参数、接管方式详见设计施工图及设计说明设备表;3.4.2 按照设备表内所标注的制冷/制热量、送风量、余压值、电机功率、水温升降量及容许的水压降
27、等技术要求参数选取及提供合适的风机盘管机型。上述技术参数偏差±2%以内。除特别注明外,有关功能要求是按照风机盘管在中速运行时所能提供的功能而定;3.4.3 有关设备无论在运送、储存及安装期间,应采取正确的保护措施,尤其是盘管的翅片和风机盘管的外壳,以确定设备在任何情况下不受损坏;3.4.4 风机盘管在中速正常运行操作时,所产生的噪音必须低于国家标准所订定的要求,整机噪音应低于35分贝;3.4.5 风机盘管需设有适当的接驳口供冷冻/采暖水管、冷凝水管、送/回风管、电源及控制线接驳。风机盘管本体与接线盒若未连接成一体,应用接地线与接线盒连接,并在接线盒内预留接地端子。所有风管和水管接驳口
28、在进行接驳前须妥善的覆盖,以避免污染物进入;3.4.6 所有风机盘管均配置保温后侧回风箱/保温下回风箱,并设可拆卸金属铝格网过滤器;3.4.7 投标人在投标文件中必须注明风机盘管各组成部件的材质、品牌、产地、供货周期,提交由原厂编印的安装、操作及维修手册,提交技术资料及产品样本,填写附件中的表格;3.4.8 提供的风机盘管设备表只针对标书发放日之前最新版的机电施工图。今后精装配合时,可能需要调整风机盘管的型号和数量,投标人应依据调整后的设备清单进行供货;3.4.9 除特别注明外,所有风机盘管均为卧式机组;卧式机组的机身厚度不应大于300mm;3.4.10 风机盘管冷冻水进出水温度参数需符合施工
29、图设计参数要求;3.4.11 风机盘管须为专门生产同类型产品的厂家;必须具有五年以上生产同类设备的经验;3.4.12 所采用的材料必须完全符合当地消防审查的防火要求;3.4.13 有关设备的功能和噪音须按照国际认可的机构/组织所制定的标准进行测试和鉴定;3.4.14每台风机盘管须附有原厂的标志牌,详细标明厂家名称、机种型号和系列编号;3.4.15 提交原厂提供的技术数据及测试报告,以显示有关机组在指定的工作条件下的基本参数,包括(并不限制):型号、风量(高中低)、冷量、热量、机外余压、电机功率、噪音、重量、盘管排数、工作压力、水量、水压降,外形尺寸。以上数据应采用中文。供应商需以表格形式填写设
30、备清单的各项参数。清单中没有列项的需要供应商额外列表明确,供应商需要填写附件中的表格;3.4.16 提交由原厂编印的安装、操作及维修手册,提供完整的设备配件表及由原厂所建议的后备配件表;3.4.17 须提供原厂装配的风机盘管包括风机、盘管、冷凝水盘、电动机及配件等装配在一保温的金属外壳内,包括排气。所有风机盘管不可含有任何石棉或石棉产品;3.4.18 风机:(1)风机的叶轮及外壳须为全金属制造;(2)风机的叶片为直驱式离心前弯式叶片设计;(3)风机须经静态及动态平衡,并能在三个不同的速度运作,为低噪音风机。3.4.19 电动机:(1)所提供的电动机须适用于单相的电力供应;(2)电动机须与风机联
31、接及固定在风机盘管的机壳上;(3)电动机须能以三个不同转速操作,并须具足够的功能保证在任何转速运作下不会产生过载;(4)须提供固定分相式单相电容及配有热过载保护的电动机,并须由原厂装配;(5)轴承需采用进口优质轴承,为无油润滑轴承。3.4.20 盘管:(1)盘管须采用脱氧无缝铜管,外配以铝制散热翅片组装在镀锌钢板制成的盘管框架内,铝翅片应有防腐亲水膜功能;(2)铝制散热翅片须以机械连接方法与盘管水管外壁相互连接;(3)盘管的总分水管应采用无缝铜管制造,除设有供/回水管接口外,仍需配置排水及排气的装置;(4)盘管水管的水流速度不能低于0.6 米/秒及不高于1.8米/秒,应能承受1.6MPa工作压
32、力。3.4.21 冷凝水盘:(1)冷凝水盘为一次冲压成型,底部保温采用一次垫压;(2)冷凝水盘应采用镀锌钢板/不锈钢板内外表面喷塑制成,水盘底部须设有适当保温材料。能防止保温表面结露。水盘保温的保温材料为一块完整保温板,不得有拼接现象发生;(3)冷凝水盘须配有一外接头,供接驳排水管, 水平安装时,其内表面应有不小于0.01 的坡度,坡向外接头处,以保证冷凝水畅通排放。3.4.22 除特别指定外,各有关的设备须于下列的室外环境下按其规格运行,设备的规格试验亦应按下列的条件进行:一 夏季温度 40一 冬季温度 -15一 相对湿度 99%3.4.23 盘管在冷、热态时对地绝缘电阻值不小于2M;3.4
33、.24 盘管电气强度在1500 电压(1min)下,无击穿或闪络;3.4.25 投标人的责任指导安装单位安装、配合系统调试及试运行。3.5 液晶温控器专用技术要求。3.5.1 应具有控制风机盘管三速开关以及四管制阀门开关的功能;3.5.2 为方便用户在夜间操作,液晶显示屏应具有蓝色背光功能;3.5.3 可清晰显示环境温度以及设定温度,方便用户查看;3.5.4 为满足用户的舒适度要求,液晶温控面板应具有定时开关机、时钟以及睡眠功能;3.5.5 控制方式制冷与供暖间可任意切换;3.5.6 工作电压:220VAC (±10%)、50 Hz;3.5.7 控制性能:控温精度±1;3.
34、5.8 温度显示范围:040;3.5.9 温度设置范围:535;3.5.10 操作寿命:继电器开关次数应大于100000 次;3.5.11 环境温度范围:045。4. 产品质量保证4.1 质量保证期为24 个月,自本工程正式验收之日起计算。4.2 投标人应在杭州市内设常驻维修机构,并在投标文件中提供地址、联系方式;委派专职的、具有三年以上服务维修经验的技术服务工程师。维修人员须在接到维修电话后2 小时内赶到现场。维修人员到现场24 小时内,修复开机或提交设备维修报告。提供不间断的服务直到结束。维修点需提供足够的备件以适应维修需求。4.3 在质保期内,投标人应提供正常保养服务,因产品制造质量不良而产生损坏或不能正常工作的,投标人应提供免费维修。4.4 在质保期内的工作应包括对所有系统常规检查、调整和润滑等。具体的操作程序和内容须在试运行时就提交招标人。4.5 在质保期满时,投标人工程师应对设备进行另一次测试,任何故障须由投标人自费解决并取得招标人的同意。4.6 保外服务:投标人应对提供有偿的终身维修服务,所需更换的部件均按成本价提供,
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 公司员工个人工作总结例文8篇
- 体育老师个人教学工作总结范文
- 初中英语教师工作计划大全
- 2024年度施工现场临时用电安全管理及施工人员安全培训协议3篇
- 爱心助学捐款倡议书9篇
- 2022年幼儿园支部工作计划
- 经典电影全城高考观后感
- 六上分数除法解决问题例7
- 怎样拯救我们的脑课件
- 2024届河南省息县高三下学期三校联考高考一模物理试卷
- 未打卡情况说明表
- 全国各省关氏辈分收集
- 中国水饺行业发展研究报告
- 我国各类型扣件技术说明
- 毕节市财政局国库科工作运行规程
- 一年级语文课堂中的教学游戏
- 东汽600MW机组润滑油系统说明书
- 承插型盘扣式支架施工技术总结
- 震雄注塑机Ai_01操作说明书(中文)
- 四年级上学期家长会PPT课件.ppt
- 电话机和对讲机装配实习报告
评论
0/150
提交评论