1、Cooling Load Estimation same as space cooling load if space temperature is kept constant without fluctuation.,3,Terms,Further illustration of difference between heat gain and cooling load:,4,Terms,Sensible heat: energy leading to change in space air temperature with no change in moisture content. La
2、tent heat: energy related to moisture change without change in dry bulb temperature. Cooling coil load: rate of energy removal at cooling coil including the space cooling load, ventilation load and any distribution system heat gain.,5,Terms,6,Total Cooling Load,Addition of individual space cooling l
3、oad components of a zone at a given time Load profile: variation of load with time Calculation needed for different hours of a day and for different months of a year to arrive at the peak value of a zone,7,Total Cooling Load,Peak load: used to determine supply air flow rate for a zone; summation of
4、peak loads of various zones used to ascertain the volume flow rate of a constant air volume system Block load: max. summation of cooling loads of zones occurring at the same time; used to determine supply air flow rate of a variable air volume system Block load of a building determines the max. tota
5、l cooling requirement,8,Heat Gain/Cooling Load Components,External, internal and infiltration loads.,Top floor of a multi-storey building,9,CLTD/SCL/CLF Method,Simplified version of transfer function method, manageable manual calculation. CLTD: cooling load temperature difference SCL: solar cooling
6、load CLF: cooling load factor Thermal storage effect taken into account by these 3 factors in calculation.,10,Important Design Parameters,Outdoor design conditions Summer Code of Practice for Energy Efficiency of Building Services Installation(BEC 2012, EMSD) Max. dry bulb temperature: 35oC Max. wet
7、 bulb temperature: 29oC ASD Projects Dry bulb temperature: 33oC Relative Humidity: 66% Winter CoP for Building Energy Code (BEC 2012, EMSD) Minimum dry bulb temperature: 7 oC ASD Projects Dry bulb temperature: 10oC Relative Humidity : 40%,11,Important Design Parameters,Indoor design conditions therm
8、al comfort or industrial process requirements taking also into account energy consumption factors affecting thermal comfort dry bulb temperature relative humidity air movement (velocity) clothing activity level various thermal comfort charts relating these factors together, e.g. ASHRAE,12,Important
9、Design Parameters,Indoor design conditions (contd) CoP for Building Energy Code (EMSD) for offices Summer( for office and classroom) Min. dry bulb temperature: 23 oC Min. relative humidity: 50 % Winter: ( for applications other than hotel) Max. dry bulb temperature: 22 oC Max. relative humidity: 50
10、% ASD Projects Summer( for general office ) Dry bulb temperature: 25.5 oC Relative humidity: 50-60 % Winter: ( for general office) Dry bulb temperature: 20 oC Relative humidity: 50 %,13,Cooling Load Component,Fenestration: glazed aperture in building envelope Cooling load: conduction heat gain due t
11、o temperature difference & solar heat gain due to solar radiation Cooling load due to solar heat gain affected by solar radiation intensity, type of glazing and shading thermal storage of building combined effect of solar heat gain and thermal storage given by Solar Cooling Load (SCL in W/m2),14,Coo
12、ling Load Component: Conduction Heat Gain through roofs, walls & glass,Cooling load due to conduction heat gain evaluated by qcond, g = U A (CLTD) (Unit:W) U: overall heat transfer coefficient of roof, wall or glass in W/m2 K (thermal property dependent) A: area of roof, wall or glass, m2 CLTD: cool
13、ing load temperature difference, roof, wall or glass,15,Cooling Load Component: Conduction Heat Gain through roofs, walls & glass,Cooling load due to conduction heat gain (contd) Examples of CLTD values for given indoor and outdoor temperatures for conduction through glass Corrected values be obtain
14、ed by CLTDc = CLTD + (25.5 - tr) + (tm - 29.4)oC tr = indoor temp., oC tm = mean outdoor temp., oC = max. outdoor temp. - (daily range)/2,16,Cooling Load Component: Conduction Heat Gain through roofs, walls & glass,Cooling load due to conduction be evaluated by qcond = U A (CLTDc) CLTD values depend
15、s on wall/roof / window no, orientation, latitude and time Examples for wall no. 4 at 40o North Latitude,17,Cooling Load Component: Internal Partition,Cooling load be estimated simply by considering the temperature difference between the adjacent space and the room qcond, p = U A (tb - tr),18,Coolin
16、g Load Component: Solar Heat Gain,Cooling load due to solar heat gain (contd) SCL values for double strength glass (a reference glass) available from design handbook conversion of SCL values for actual fenestration used by Shading Coefficient (SC) cooling load due to solar radiation obtained by qrad
17、, g = A (SC) (SCL) SC values available from handbook for various types of fenestration (glass and shading),19,Cooling Load Component: Solar Heat Gain,Cooling load due to solar heat gain (contd) SCL values depends on latitude, time, orientation and zone type (A, B, C and D) of the space Examples of S
18、CL: 40o North Latitude, Zone Type B at selected solar time 11 hour to 18 hour Examples of zone type,20,Cooling Load Component: Solar Heat Gain,Cooling load due to solar heat gain (contd) Examples of SC If fenestration partially shaded, solar heat gain through sunlit and shaded parts be evaluated and
19、 added,21,Cooling Load Component: Lighting,Cooling load be estimated using qel = W Ful Fal (CLFel), W where W = total light wattage (rating of lamps), W Ful = lighting use factor Fal = lighting allowance factor (1.18 to 1.3) CLFel = lighting cooling load factor Examples of CLF,22,Cooling Load Compon
20、ent: Lighting,CLF = 1 if air conditioning is off at night or where the lights are on continuously non-stop: thermal storage effect cannot be made use of for reduction of peak cooling requirement,23,Cooling Load Component: Equipment,Cooling load estimated by qe = P (Fl,e) (Fu,e) (CLFe) / P = Power ra
21、ting of equipment, W Fl,e = Load factor (fraction of rated load delivered) Fu,e = Use factor = Motor efficiency CLFe = Cooling load factor for equipment CLFs for equipment be obtained similar to those for lighting CLF = 1 when air conditioning is off or with 24-hour equipment operation,24,Cooling Lo
22、ad Component: Occupants,People generate sensible and latent heats depending on activities Examples of sensible and latent heat gains for offices(Based on 24 room dry-bulb temperature) Sensible cooling load be estimated using qo, s = N (SHGo) (CLFo), W N = no. of occupants SHGo = sensible heat gain p
23、er occupant, W CLFo = cooling load factor for occupant,25,Cooling Load Component: Occupants,Sensible cooling load (contd) CLF depends on zone type and pattern of occupation Examples of CLF for a space of zone type B CLF = 1 if air conditioning system is off at night or with 24-hour occupancy or with
24、 high occupant density,26,Cooling Load Component: Occupants,Latent cooling load be estimated by qo, l = N (LHGo), W LHGo is the latent heat gain per occupant, W no storage of moisture is assumed and CLF = 1,27,Cooling Load Component: Ventilation & Infiltration,Outdoor air must be introduced to venti
25、late conditioned spaces. ASHRAE Standard 622001 recommends minimum ventilation rates for most common applications.,28,Cooling Load Component: Ventilation & Infiltration,Infiltration of air through gaps in building due to wind pressure and temperature difference Infiltration rate Vif estimated by air
26、 change rate method: no. of air change per hour Vif (m3/s) = (no. of air change per hour) (room volume in m3) / 3600 Cooling load due to ventilation & infiltration includes sensible and latent heats,29,Cooling Load Component: Infiltration,Outdoor air to be cooled and dehumidified from outdoor condit
27、ion to room air condition Sensible cooling load (associated with temperature reduction) estimated by qif,s = 1.23 V (to - tr) Latent cooling load (associated with moisture removal) estimated by ql = 3010 V(wo - wr) Total cooling load qt = 1.20 V(ho-hi),30,Rules of Thumb (for HK),31,Rules of Thumb (contd),32,OTTV,Definition Building (Energy Efficiency) Regulat
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 金融行业员工加薪申请书参考
- 施工现场沥青混凝土运输流程
- 小学数学实践教学案例分享计划
- 25年新版车间安全培训考试试题答案全面
- 心理健康中心安全保障措施
- 25年公司三级安全培训考试试题附参考答案(精练)
- 25年公司、项目部、各个班组三级安全培训考试试题附答案【培优B卷】
- 学校周边环境除四害工作方案
- 早教中心家长健康教育计划
- 弱电系统升级改造质量保障措施
- 控制器参数确定方法
- 2023年陕西西安经开区管委会招聘160人(共500题含答案解析)笔试历年难、易错考点试题含答案附详解
- 2023届广东省普通高中数学学业水平考试试卷及答案
- 钓鱼中各种氨基酸诱食剂说明书及使用方法
- 幼升小上实机考题汇总
- 2023年考研考博-考博英语-西安电子科技大学考试历年真题摘选含答案解析
- 化工原理课程设计水吸收氨气填料塔设计
- Excel水力计算展示-棱柱体渠道水面线计算演示
- 2013年广东省中考语文试题及答案
- UPS蓄电池安装施工方案(完整版无需过多修改)
- 数学建模案例分析-线性代数建模案例(20例)65959
评论
0/150
提交评论