1、ENGINEERING STANDARDSSECTION 1 SUMMARY1)STANDARDS SUMMARY InterContinental Hotels Group Asia Pacific12005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARY1.1SUMMARY. 31.2COMMON OMISSIONS AND PROBLEMS . 91.2.1FIRE LIFE SAFETY . 91.2.2MECHANICAL, ELECTRICAL AND PLUMBING . 11 InterCon

2、tinental Hotels Group Asia Pacific22005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARY1.1SUMMARYInterContinental Hotels Group Engineering Standards for Inter-Continental Hotels Group SummarySection System RequirementsAIR CONDITIONINGGeneral Air changes & temperatureGuest roomsPub

3、lic areassSwimming Pool IndoorsAdministration,Telephone operator & Department head offices Service areassStaff cafeteriaComputer roomLift plant roomsEquipment Chillers- Scroll/Screw/Centrifugal / /All public areas fully air conditioned. Service areas ventilation except staff cafeteria, offices. HVAC

4、 in locations with average temp of 13oC 5hrs/yr. P13oC/5/As detailed in tablesModerate climate: 4-pipe overhead fan coil, tropical: 2- pipe. Temperature summer: 22oC; winter: 24oC. Thermostat setting 23oC +/- 3oC. s 4 qr 222oC24oCt s23oC +/- 3oCFresh primary air/ exhaust: 90/85cbm/room with thermal

5、wheel heat recovery. / 90/85cbm/rqqsMedium pressure multiple zone variable air volume systems. 23oC.23oC VAV with latent heat recovery. 28oC orq 28 CMinimum fresh air/exhaust + individual fan coils/ + Laundry 100% fresh air/exhaust. 28oC with spot cooling. o100%/ 28 C sr ()Kitchens Induction hood. 2

6、7oC with spot cooling. o 27 CHVAC. 23oC23oCIndependent self-contained unit. 23oC. o 23 CTropical locations: Self-contained unit, unless supplied by room exhausts qr Moderate climate 5 hours temp.13oC: 3 units 50%. Diversity: 80%. Refrigerants: R134a, o407C. HFC only. 5 13oC 350%80% R134a, 407C Inter

7、Continental Hotels Group Asia Pacific32005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARYCooling TowersCross-flow/ induced draft-2speed fans. Not requiredfor air-cooled chillers./ Boilers - Hot water qCold climate 5oC: 250%. of maximum demand. Diversity: 80%. 94% efficiency or he

8、at pump.o 4 C2 67%80% 94%qBoilers Steam2 units 100%. 3-pass water tubes boilers. 2 100%Section System RequirementsBuilding AutomationFansControlling entire HVAC incl. fan coils, major plumbing equipment. Specific electrical circuits, coldrooms & freezers, spec. life safety equipment. Sub-metering. I

9、nterface w. Fidelio. s ¥s Fidelio Non-overloading centrifugal fan type.Impellers should have backward curved blades exc. fan coils. PLUMBINGWater SupplyQuality as per WHO standards. Additional treatment tobe non corrosive & non-scale forming. Unreliable supply backed up by own well, desalination pla

10、nt & storage tanks. Capacity: 900 ltrs/room/day. W/o laundry: 750 ltrs/room/day. 900/750/DistributionMax. fixture pressure 5,5 bar per zone. 1,5+/-0,5 bar at top level. Separate pumps for each zone. Direct feed to lower floors if street pressure is adequate. Sub- metering all major departments. 5,5/

11、1,5+/-0,5 Hardness0 ppm for boilers, dishwashers. 50 ppm laundry.120ppm cooling towers & hot water.0 ppm50 ppm Water Treatmentq 120 ppmDedicated water treatment systems for cooling towers, boilers, closed circuits heating & cooling qKitchens&LaundryEffluent Grease traps for kitchen effluent. PH corr

12、ection for laundry-as required. PH InterContinental Hotels Group Asia Pacific42005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARYHot waterqDuplex storage type with circulation pumps. Shell/tubeheat exchangers. Where non-scale forming exterior plate/frame heat exchangers. General

13、supply: 60oC. Dishwasher booster to 80oC. Thermostatic anti-scald mixing valves in all public areas to limit to 40oC. 80 oC60 oC40 oCP PIrrigationStorm drainage MaterialsSub-surface automatic piping system Separate system discharging into storm sewer, combination sewer as per local situation. Domest

14、ic water: copper or Polypropylene. Pool, fountains, irrigation: PVC. Stand-pipe, sprinklers, heating, cooling: BS. Sewer: Cast iron or PVC(Insulated). PVC BSPVCrq stSewage Treatment PlantAs required and/or feasible for recycling. / BathroomsTub: 3.5 mm steel, white. Showerhead: adjustable angle, 13

15、ltrs/min. Thermostatic anti-scald mixer. Tap:6 ltrs/min. Toilet: 6/3 ltrs dual flush.3.5 mm 13/ 6/ 6/3Gas & FuelAs per local conditions-most feasible supply. P Swimming PoolDedicated water treatment. Indoor pool heated to 28oC.o 28 CSection System RequirementsELECTRICALSupplyEmergency PowerDistribut

16、ionGuest RoomsHV loop to air-cooled transformers rated at 2*100% or3*50% capacity. High or low voltage metering-as per local code & best tariff. Power factor correction. 2*100%3*50% PEmergency generator for all life safety systems, lifts, partial lighting, coldrooms, domestic & sump pumps & specific

17、 other equipment. Fuel, enough for 48 hours. UPS for all computer equipment. ¥ P 48 Sub-metering all major departments & equipment Distribution panel in each room with 5 circuits5 InterContinental Hotels Group Asia Pacific52005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARYLighti

18、ngAs per interior designer, IC room & other standards.Dimming for all public areas except corridors, rooms. PsPAudio-visualMATV & Sound systems for all rooms, specific public areas. Pocket paging system. PSecurityCCTV, Hold-up & burglar alarm, Exit door monitoring system., Communication&DataSee sepa

19、rate standards Systems ELEVATORSGuest ElevatorsAdequate number to answer all calls within 30 secondsfor 50%, 45 sec. for 95%, 60 sec. for 100% of waiting persons. 3050% 4595% 1 Service Elevators Minimum of two (2) units for hotels 400 rooms, but minimum of 50% of guest elevators.4002 Banquet 50%Larg

20、er elevator to accommodate all guests within 30minutes and transport exhibition goods (car etc). 30 PqFiremens lift As required by local code.Escalators As required by layout.LIFE SAFETYSuppressionFire Detection & Alarm Fully sprinklered building, concealed quick responsetype. 2.5 fire hoses in high

21、 rise; low rise at discretion ofIHG2.5 r Fire extinguishers throughouts Kitchen hood: Wet chemical ext. system Computer room: Pre-action dry sprinkler¥ Fully addressable throughout the building. Class Awiring. ADedicated supervised 3-channel voice alarm system for high-rise. Can be utilized as sound

22、 system. s 3- Section System RequirementsInterfaces with paging systems, BMS, smoke control systems, elevator recall, other ext. sub-systems, doorhold-open devices s BMS P InterContinental Hotels Group Asia Pacific62005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARY BMS q P Guest

23、 rooms: Addressable smoke detector with integralacoustic alarmCentral Control RoomAll high-rise Emergency PowerGenerator for all life safety systems, lifts, telephonesystem, lighting: 15% public area, 20% service areas,100% stairs, exit signs, GMs apartment, doctors office, engineering office, gener

24、ator & switchgear rooms. Vestibule in each guestroom. 15%20% 100% Non-life safety: sump pumps, domestic water pumps, refrigeration, computer systems Emergency Exit SignsSmoke ControlBattery back-upAtrium exhaustStair pressurization in high-rise.Guest rooms corridor smoke exhaust via ventilation syst

25、em- built to higher standard. Smoke Doors Can be omitted in fully sprinklered building-unless req. by local code. Fire DampersAll fire-rated walls. 2 hours and over.P 2 ENERGYMANAGEMENTGENERAL UTILITYCONSUMPTION ElectricityAnnual consumption shall not exceed per square meter net area the following i

26、n climate zones: Moderate: 145, Mediterranean: 155, Tropical: 200 KWh/sqm/year. 145 155 qr200 /Peakdemand:Moderate:2.5KW/room, Mediterranean: 2.7 KW, Tropical: 3.5 KW.2.5 /2.7 /qr3.5 /Energy (net calorific value& net energy available at boiler discharge)Annual consumption shall not exceed per square

27、 meter net area the following in climate zones: Moderate: 180, Mediterranean: 140, Tropical: 80 KWh/sqm/year. & 180 140 qr80 / InterContinental Hotels Group Asia Pacific72005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARYDistrict heating peak demand: Moderate climate:6KW/room.s6

28、/WaterModerate:560ltrs/guest,Mediterranean:600,Tropical: 900.560/ 600/qr900/Air ConditioningK-factors for wall construction: 0.35; windows: 1.3.K 0.35 1.3Least costly utility selection for chillers, boilers, heating etc. Section System RequirementsPLUMBINGCentr. & screw chillers shall have an effici

29、ency of0.55 KWh/ton, boilers: 91%.& 10,000 cbm/hr. Indoor pool with latent heat recovery to heat pool water.qq 10,000 cbm/hr qsSecondary heating & cooling water systems shall have variable speed drives.q District heating: air conditioning systems shall be designed for maximum temp. spread, e.g. 70/5

30、0oC, fan coils 60/40oC. Hot water heating shall have pre-heating via recovery from common return. P 70/50oC60/40oC q sBuilding Automation system with detailed energy control functions. Induced draft cooling towers with variable speed fans, controlled from chiller for max. efficiency. Steam boilers t

31、o have heat recovery from flash steam in return. Automatic pressure reduction when laundry off, e.g. 10/2 bar. q 10/2Cogeneration only where feasible & outside service guaranteed. Lower floors supplied w. direct street pressure. Domestic water pumps variable speed. Max. fixture pressure 5 bar. Inter

32、Continental Hotels Group Asia Pacific82005 Revision All Rights ReservedENGINEERING STANDARDSSECTION 1 SUMMARY 5All toilets 6/3 ltrs dual flush. 6/3All sink faucets in rooms, public areas, staff lockers 6ltrs/min. 6/All showerheads in staff lockers 9 ltrs/min, guestrooms 13 ltrs/min. 9/ 13/Sub-meteri

33、ng of all major departmentsAutomatic sub-surface irrigation with timers, humiditysensors.Water treatment to all open systems to prevent scale Water lost to drain from filter backwash shall be recovered for further treatment to reduce losses by90%. s 90%Laundry: Washing machines w. recovery or tunnel washers. rs Section System RequirementsELECTRICALCheapest electricity tariff. Power factor correction. Peak demand contro

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论