1、short-circuit current 1 terms and definitionsthe following terms and definitions correspond largely to those defined in iec 60 909. refer to this standard for all terms not used in this book.the terms short circuit and ground fault describe faults in the isolation of operational equipment which occu

2、r when live parts are shunted out as a result.l causes:1. overtemperatures due to excessively high overcurrents.2. disruptive discharges due to overvoltages.3. arcing due to moisture together with impure air, especially on insulators.l effects:1. interruption of power supply.2. destruction of system

3、 components.3. development of unacceptable mechanical and thermal stresses in electrical operational equipment.l short circuit:according to iec 60 909, a short circuit is the accidental or intentional conductive connection through a relatively low resistance or impedance between two or more points o

4、f a circuit which are normally at different potentials.l short circuit current:according to iec 60 909, a short circuit current results from a short circuit in an electrical network.it is necessary to differentiate here between the short circuit current at the position of the short circuit and the t

5、ransferred short circuit currents in the network branches.l initial symmetrical short circuit current:this is the effective value of the symmetrical short circuit current at the moment at which the short circuit arises, when the short circuit impedance has its value from the time zero.l initial symm

6、etrical short circuit apparent power:the short circuit power represents a fictitious parameter. during the planning of networks, the short circuit power is a suitable characteristic number.l peak short circuit current:the largest possible momentary value of the short circuit occurring.l steady state

7、 short circuit current:effective value of the initial symmetrical short circuit current remaining after the decay of all transient phenomena.l dc aperiodic component:average value of the upper and lower envelope curve of the short circuit current, which slowly decays to zero.l symmetrical breaking c

8、urrent:effective value of the short circuit current which flows through the contact switch at the time of the first contact separation.l equivalent voltage source:the voltage at the position of the short circuit, which is transferred to the positive-sequence system as the only effective voltage and

9、is used for the calculation of the short circuit currents.l superposition method:the superposition method considers the previous load of the network before the occurrence of the short circuit. it is necessary to know the load flow and the setting of the transformer step switch.l voltage factor:ratio

10、 between the equivalent voltage source and the network voltage un,divided by 3.l equivalent electrical circuit:model for the description of the network by an equivalent circuit.l far-from-generator short circuit:the value of the symmetrical ac periodic component remains essentiallyconstant.l near-to

11、-generator short circuit:the value of the symmetrical ac periodic component does not remain constant. the synchronous machine first delivers an initial symmetrical short circuit current which is larger than twice the rated current of the synchronous machine.l positive-sequence short circuit impedanc

12、e:the impedance of the positive-sequence system as seen from the position of the short circuit.l negative-sequence short circuit impedance:the impedance of the negative-sequence system as seen from the position of the short circuit.l zero-sequence short circuit impedancethe impedance of the zero-seq

13、uence system as seen from the position of the short circuit. three times the value of the neutral point to ground impedance occurs here.l short circuit impedance:impedance required for calculation of the short circuit currents at the position of the short circuipt.1.2 short circuit path in the posit

14、ive-sequence systemfor the same external conductor voltages, a three-pole short circuit allows three currents of the same magnitude to develop between the three conductors. it is therefor only necessary to consider one conductor in further calculations. depending on the distance from the position of

15、 the short circuit from the generator, here it is necessary to consider near-to-generator andfar-from-generator short circuits separately.for far-from-generator and near-to-generator short circuits, the short circuit path can be represented by a mesh diagram with ac voltage source, reactances x and

16、resistances r (figure 1.2). here, x and r replace all components such as cables,conductors, transformers, generators and motors.fig. 1.2: equivalent circuit of the short circuit current path inthe positive-sequence systemthe following differential equation can be used to describe the short circuit p

17、rocesswhere w is the phase angle at the point in time of the short circuit. this assume that the current before s closes (short circuit) is zero. the inhomogeneous first order differential equation can be solved by determining the homogeneous solution ik and a particular solution ik.the homogeneous

18、solution, with the time constant g = l/r, solution yields:for the particular solution, we obtain: the total short circuit current is composed of both components:the phase angle of the short circuit current (short circuit angle) is then, in accordance with the above equation, for the far-from-generat

19、or short circuit, the short circuit current is therefore made up of a constant ac periodic component and the decaying dc aperiodic component. from the simplified calculations, we can now reach the following conclusions: l the short circuit current always has a decaying dc aperiodic component in addi

20、tion to the stationary ac periodic component.l the magnitude of the short circuit current depends on the operating angle of the current. it reaches a maximum at c = 90 (purely inductive load). this case serves as the basis for further calculations.l .the short circuit current is always inductive.1.4

21、 methods of short circuit calculationthe equivalent voltage source will be introduced here as the only effective voltage of the generators or network inputs for the calculation of short circuit currents. the internal voltages of generators or network inputs are short circuited, and at the position o

22、f the short circuit (fault position) the value ( is used as the only effective voltage (figure 1.4).l the voltage factor c 5 considers (table 1.1):l the different voltage values, depending on time and positionl the step changes of the transformer switchl that the loads and capacitances in the calcul

23、ation of the equivalent voltage source can be neglectedl the subtransient behavior of generators and motorsl this method assumes the following conditions:l the passive loads and conductor capacitances can be neglectedl the step setting of the transformers do not have to be consideredl the excitation

24、 of the generators do not have to be consideredl the time and position dependence of the previous load (loading state) of the network does not have to be considered fig. 1.4: network circuit with equivalent voltage sourcea) three-phase network, b) equivalent circuit in positive sequence system1.4.2

25、superposition methodthe superposition method is an exact method for the calculation of the short circuit currents. the method consists of three steps. the voltage ratios and the loading condition of the network must be known before the occurrence of the short circuit. in the first step the currents,

26、 voltages and the internal voltages for steady-state operation before onset of the short circuit are calculated (figure 1.5b). the calculation considers the impedances, power supply feeders and node loads of the active elements. in the second step the voltage applied to the fault location before the

27、 occurrence of the short circuit and the current distribution at the fault location are determined with a negative sign (figure 1.5c). this voltage source is the only voltage source in the network. the internal voltages are short-circuited. in the third step both conditions are superimposed. we then

28、 obtain zero voltage at the fault location. the superposition of the currents also leads to the value zero. the disadvantage of this method is that the steady-state condition must be specified. the data for the network (effective and reactive power, node voltages and the step settings of the transfo

29、rmers) are often difficult to determine. the question also arises, which operating state leads to the greatest short circuit current. figure 1.5 illustrates the procedure for the superposition method.fig. 1.5: principle of the superposition methoda) undisturbed operation, b) operating voltage at the

30、 fault location, c) superposition of a) and b)1.4.3 transient calculationwith the transient method the individual operating equipment and, as a result, the entire network are represented by a system of differential equations. the calculation is very tedious. the method with the equivalent voltage so

31、urce is a simplification relative to the other methods. since 1988, it has been standardized internationally in iec 60 909. the calculation is independent of a current operational state. in thisbook, we will therefore deal with and discuss the method with the equivalent voltage source.1.5 calculatin

32、g with reference variablesthere are several methods for performing short circuit calculations with absolute and reference impedance values. a few are summarized here and examples are calculated for comparison. to define the relative values, there are two possible reference variables.for the characte

33、rization of electrotechnical relationships we require the four parameters:l voltage u in vl current i in al impedance z in wl apparent power s in va.three methods can be used to calculate the short circuit current:1. the ohm system: units: kv, ka, v, mva2.the pu system:this method is used predominan

34、tly for electrical machines; all four parameters u, i, z and s are given as per unit (unit = 1). the reference value is 100 mva. the two reference variables for this system are ub and sb.example: the reactances of a synchronous machine xd, xd, xd are given in pu or in % pu, multiplied by 100 %.3.the

35、 %/mva system:this system is especially well suited for the fast determination of short circuit impedances. as formal unit only the % symbol is add.短路电流1 术语和定义以下术语和定义对应iec 标准60 909。 未出现在本书中的术语可以在该标准中查询。短路和接地故障主要是操作设备的带电部分被分流而导致绝缘损坏的结果。l 原因1. 温度过高导致强烈的过电流;2. 火花放电导致过电压3. 由于水分和污秽空气混杂导致的电弧作用,特别是在绝缘体上。l

36、后果:1. 供电中断2. 系统部件瘫痪3. 在电气操作设备中产生不可接受的机械力和热应力。l 短路:根据iec 60 909,短路是经历一段相对低电阻或在两个或更多不同电位之间的电阻间意外或故意的导电连接。l 短路电流:根据iec 60 909,短路电流是在电力网络中短路的结果。在这里有必要区分在短路过程中产生的短路电流和在网络分支中的转移电流。l 初始对称短路电流:这是在短路出现瞬间,短路阻抗从零开始变化时的对称短路电流的有效值。l 初始对称短路视在功率:短路功率代表了一个虚构的参数。在网络规划中,短路功率是一个合适的典型参数。l 最大短路电流:短路时可能的最大电流瞬时值。l 稳态短路电流:

37、初始对称短路电流在暂态过程中衰减完毕之后的电流有效值。l 短路电流非周期分量:慢慢衰减的短路电流上下包络曲线的平均值。l 对称断路电流:联络开关第一次接触分离时流过短路电流的有效值。l 等效电压源:被转移到正序系统作为唯一有效的短路位置的电压,并且主要用于短路电流的计算。l 叠加方法:叠加法考虑到在发生短路前网络的负荷情况。因此很必要知道负荷留了和变压器开关的设定。l 电压因素:等效电压源和网络电压之间除以三的比例。l 等效电路:网络描述的模型采用等效电路。l 远离发电机短路:对称交流周期分量维持原本不变的量的短路形式。l 靠近发电机短路:对称交流周期分量不保持不变的值的短路。同步机首先会产生

38、一个大于两倍额定电流的初始对称短路电流。l 正序短路阻抗:短路位置正序系统的短路阻抗。l 负序短路阻抗:短路位置负序系统的短路阻抗。l 零序短路阻抗:短路位置零序系统的短路阻抗。就是中性点到短路位置阻抗的三倍。l 短路阻抗:计算短路位置的短路电流所需要的阻抗。1.2 正序系统的短路路径:对于相同的外部导体电压,三相短路允许同一数量级的三相电流在三相导体中发展。所以在进一步计算中只需要考虑一相导体的情况。根据短路位置到发电机的距离,这里有必要将远离发电机短路和靠近发电机短路这两种情况分开考虑。对于远离和靠近发电机短路的情况,短路路径可以用一个有交流电压源,电抗x,电阻r构成的网络图表示。(图1.

39、2)这里x和r替代所有的原件,如电缆,导体,变压器,发电机和电机。图1.2 短路电流路径在正序系统中的等效电路下面的微分方程可以用来描述短路过程 ikrk+lkdikdt =usin(t+), (1.1)是短路点的相位角。这是假设电流在s关闭(短路)之前是零。非线性一阶微分方程可以通过决定齐次解ik和特解ik求解。 ik=ik+ik- (1.2)齐次解有一个时间常量=lr,方程式为:ik=-u(r2+x2)etgsin(-k) (1.3)对于特解,我们得出:ik=-u(r2+x2)sin(t+-k) (1.4)总短路电流由两部分构成:ik =-u(r2+x2)sin(t+-k)- etgsin(-k) (1.5)根据以上方程,单相短路电流的短路角为:k=-v=tan-1xr (1.6)对于远离发电机形式的短路,短路电流是由一个不变的交流周期分量和一个衰减的直流非周期分量构成。从简化计算,我们可以得出以下结论:l 短路电流总是由一个固定的交流周期分量和一个衰减的直流非周期分量构成;l 短路电流的大小取决于电流的工作角,最大值为90(纯电感负载)。这种情况作为进一步计算的基础。l 短路电流都是感应的。1.4 短路电流计算方法:三相系统中的短路电流有三种计算方法:1.在故障位置计算等效电压源;2.叠加法确定负载流量情况;3.瞬态计算。1.4.1

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论