版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、福建工程学院环境与设备工程系毕业设计说明书北京市某饭店通风空调设计摘要 本设计为北京某十层饭店空调工程设。该楼的工程概况为:总建筑面积约13132m,高37.4m, 地上十层,地下一层。空调设计中,一至三层的大空间(大堂、西餐厅、宴会厅等)采用全空气一次回风的空气处理方案。空气处理机组采用超薄吊顶式空气处理系统。其余空调房间(中餐厅、客房、贵宾房等)采用风机盘管加新风系统。新风由设置在走廊内的吊顶新风机组处理后送入各房间。在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。空调用制冷机房设在地下室,选用
2、两台螺杆式冷水机组。夏天使用冷水机组提供的7/12的冷水。水管路采用两管制。关键词:空调设计,全空气系统,风机盘管系统,冷水机组Design of Ventilating and Air Conditioning for restaurant in Beijing Abstract The air conditioning engineering of one Hotel with ten layers in Beijing was designed. The engineering general situation of the residences floor is:Total buil
3、ding area roughly 13132 m, high 37.4 m, on the ground 10 layer, underground 1 layer In air conditioning design, 1F and 3F big spaces ( great hall, western-style restaurant, banquet hall and so on) use concentrated all-air system. The air processing unit is microtome-ceil air system. Other air condit
4、ioned rooms (example Chinese dinner service, guest room, VIP Room and so on) use CFU and all-fresh air system, the outside air processes by new atmosphere unit which establishes in ceiling, and then sends in to various rooms. The main-machine and fan coilschoice were based on the calculation of cold
5、-load. And through the numeration of blast volume and water flux,the standard of air duct and water pipe was determined. The most disadvantage resistance and pressure of the loop-road were checked up to ensure the machine of fresh-air and water pump.The Air conditioning refrigeration engine room is
6、located in the basement, Selecting two screw rods types cold water unit, it uses 7/12 cold water which the cold water unit provides in summer. The water supply uses two pipelines.Key word: Air conditioning design, entire air system, air blower plate tube system, cold water unit. 设计说明书1 工程概况1.1.设计依据1
7、.1.1设计原始资料设计对象所在地:北京市某饭店土建资料:本大楼是一个具备餐饮、客房等功能的建筑,总建筑面积为13132平方米,建筑高度为37.4米,地下室深4m。该饭店地下室主要为设备机房,储藏间,给排水专业设备间,配电间等;地面一层为大厅及管理用房,层高3.8米;二层主要为办西餐厅,层高4.2米;三层为宴会厅,层高4.2米;四层为中餐厅及贵宾房,层高4.2米;五层为客房及管道转换层,层高3.6米;六至十层为标准客房,层高3.6米。外墙:砖墙;白灰粉刷;厚度370 mm ,型墙外窗:单层窗,透明玻璃(6mm),金属窗框,80%玻璃,白色帘,窗高2m。内墙:两面抹灰一砖内墙内门:木门 高2.0
8、米屋面:从上到下为:预制细石混凝土板25mm;表面喷白色水泥浆;通风量200mm;卷材防水层;水泥砂浆找平层20mm;保温层,沥青膨胀珍珠岩125mm;隔汽层;现浇钢筋混凝土板70mm;内粉刷1.2.设计范围本设计的范围为10层饭店大楼空调及整栋建筑的冷源设计。 1.3. 设计原则空调系统划分和分区要考虑节能要求和运行管理方法,设计施工要满足国家及行业有关规范规定的要求,充分利用国内外先进的空调技术及设备,创建健康舒适的室内空气品质及环境。2 空调系统方案的确定2.1 选择负荷计算方法采用目前广为使用的空调负荷实用计算方法空调冷负荷系数法计算冷负荷。即采用冷负荷温差CLTD和冷负荷系数CLF来
9、分别计算墙体、屋顶、窗户的传热冷负荷及窗户的日射冷负荷、内部热源引起的冷负荷。2.2 初步选择空调方式本设计一至三层采用全空气系统的集中式空调系统(一层无吊顶处,风机盘管侧送为半集中系统):四至十层均采用风机盘管加新风系统(新风独立处理)的半集中式空调系统。2.3 水力计算方式 风管和水管的水力计算采用假定流速法,即按技术经济要求选定风管的流速,再根据风管和水管的风量和水量确定风管的断面尺寸和阻力。2.4 初步设计水系统考虑到闭式循环有管道与设备不易腐蚀,不需为提升高度的静水压力,循环水泵压力低,从而水泵功率小,且投资省、系统简单的优点,采用闭式循环系统,两管制。同时由于系统采用风机盘管,本设
10、计采用异程式,各分路的供回水干管上设调节阀,调节各分路水系统平衡。膨胀水箱、冷却塔位于大楼顶层。根据一泵对一机的原则和阻力计算的结果,考虑一定的安全系数,并选择备用水泵。冷冻水泵采用变频调速技术以实现节能,根据负荷的变化和冷冻机的运行情况,调节水泵运行台数和转速,既可适应负荷变化也可维持冷冻机出水量和温差恒定。3 空调房间冷负荷计算3.1空调设计参数3.1.1 围护结构参数见下表围护结构参数表结构类型类型传热系数W/(K)外墙砖墙,白灰粉刷,厚度370 mm ,型墙1.50外窗双层窗(6mm),金属窗框,80%玻璃2.878屋面预制细石混凝土板25mm,表面喷白色水泥浆,通风量200mm,卷材
11、防水层,保温层、现浇钢筋混凝土板,内粉刷,0.48内门木门 高2.0米2.90外窗的有效面积系数为Ca=0.85 ,遮挡系数为Cs=0.89 ,遮阳系数Ci=0.5 ,日射得热因数最大值Dj,max=114W/m2 .玻璃门的有效面积系数为1.0 ,遮挡系数为Cs=0.893.1.2室外计算参数(北京市)北京市空调设计室外空气计算参数1.位置: 北纬3948, 东经119 28, 海拔31.2m2 大气压力: 夏季大气压力 99.86Kpa 冬季大气压力102.04Kpa3. 室外空气参数,见下表室外空气参数表序号空气参数数值空气参数数值1夏季空调室外计算干球温度tw33.2夏季空调室外计算湿
12、球温度ts26.42夏季空调室外日平均温度twp28.6夏季室外平均风速1.9m/s3.1.3 围护结构外表面的放热系数(夏季)围护结构的类型w(W/K)w(W/K)外墙18.614.4屋顶18.614.43.1.4 本建筑的室内设计参数如下表 室内空气设计参数表 室内温度/相对湿度/新风量/m3/(h人)夏冬夏冬中餐厅2621826555504025西餐厅2621826555504025大厅2621626550504018宴会厅2621626550504025客房2622026550504050贵宾房26216265505040303.1.5.其它冷负荷相关参数见表(三)其它冷负荷相关参数表
13、(三)房间名称人员照明设备散热W/m2劳动强度群集系数类型功率W/m2大厅极轻0.96明装荧光灯,灯罩无孔20无西餐厅极轻0.93明装荧光灯,灯罩无孔17无宴会厅极轻0.93明装荧光灯,灯罩无孔30无中餐厅极轻0.96明装荧光灯,灯罩无孔20无客房极轻0.93明装荧光灯,灯罩无孔20无走廊极轻0.93明装荧光灯,灯罩无孔15无注: 1.弱电机房、数据处理中心,设备按实际发热量估算。2.室内保持正压,不考虑空气渗透引起的冷负荷。 3.本设计由于内部房间的温差较小,不考虑内围护结构的传热。3.2空调设计冷负荷计算3.2.1选择冷负荷计算方法目前在我国暖通空调工程中,比较常用的是谐波反应法和冷负荷系
14、数法计算空调冷负荷,冷负荷计算法是建立在传递函数法的基础上,是便于在工程上进行手算的一种简化方法。本设计中采用采用目前广为使用的建筑空调负荷实用计算方法空调冷负荷系数法计算空调冷负荷,通过冷负荷温度与冷负荷系数直接从各种扰量值求得各分项逐时冷负荷。从而取得计算墙体、屋顶、窗户的传热冷负荷及窗户的日射冷负荷、内部热源引起的冷负荷。3.2.2 外墙和屋面瞬变传热引起的冷负荷Qc()=AK(tc +td)kk-tR (5-1)式中: Qc() - 外墙和屋面瞬变传热引起的逐时冷负荷,W;A - 外墙和屋面的面积,m2;K - 外墙和屋面的传热系数,W/(m2 ) ;由暖通空调附录2-2和附录2-3查
15、取; tR - 室内计算温度,;tc - 外墙和屋面冷负荷计算温度的逐时值,;由暖通空调附录2-4和附录2-5查取; td - 地点修正值,由暖通空调附录2-6查取; k - 吸收系数修正值;由暖通空调表2-8查取 k - 外表面换热系数修正值;由暖通空调表2-9查取3.2.3、内墙、地面引起的冷负荷 Qc()=AiKi(to.m+t- tR) (5-2) 式中: ki - 内围护结构传热系数,W/(m2 );ki=2.05 W/(m2 ) Ai - 内围护结构的面积,m2;to.m - 夏季空调室外计算日平均温度,;t- 附加温升。由暖通空调表2-10查取3.2.4、外玻璃窗瞬变传热引起的冷
16、负荷Qc() = cw Kw Aw ( tc() + td tR) (5-3)式中 : Qc() -外玻璃窗瞬变传热引起的冷负荷,W;Kw - 外玻璃窗传热系数,W/(m2 ),由暖通空调附录2-7和附录2-8查取; Aw - 窗口面积,m2; tc() - 外玻璃窗的冷负荷温度的逐时值,由暖通空调附录2-10查得; cw - 玻璃窗传热系数的修正值;由暖通空调附录2-9查得,双层金属窗框 cw=1.2 td - 地点修正值;3.2.5、透过玻璃窗的日射得热引起的冷负荷Qc() = C Aw Cs Ci Djmax CLQ (5-4)式中 :C- 有效面积系数,由暖通空调附录2-15查得;Aw
17、- 窗口面积,m2;Cs- 窗玻璃的遮阳系数,由暖通空调附录2-13查得;Ci- 窗内遮阳设施的遮阳系数,由暖通空调附录2-14查得;Djmax-日射得热因数,由暖通空调附录2-12查得30纬度带的日射得热因数;CLQ- 窗玻璃冷负荷系数,无因次;3.2.6、照明散热形成的冷负荷 荧光灯 Qc() =1000n1n2NCLQ (5-5) 式中 :Q -灯具散热形成的冷负荷,W;N-照明灯具所需功率,W; n1-镇流器消耗公率系数,明装荧光灯n1=1.2; n2-灯罩隔热系数;n2=1.0 CLQ-照明散热冷负荷系数,可有附录2-22查得;3.2.7、人体散热形成的冷负荷3.2.7.1、人体显热
18、散热形成的冷负荷Qc() =qs n CLQ (5-6-1)式中:qs - 不同室温和劳动性质成年男子显热散热量;n - 室内全部人数;- 群集系数,由暖通空调表2-12查得;CLQ - 人体显热散热冷负荷系数,由暖通空调附录2-23查得;3.2.7.2、人体潜热散热引起的冷负荷 Qc() = ql n (5-6-2)式中:ql -不同室温和劳动性质成年男子潜热散热量, W;n,-同式5-6-1;3.2.8、食物散热形成的冷负荷 本工程中西餐厅菜肴冷负荷以每人17W计算,即17200=3400W中餐厅菜肴冷负荷以每人30W计算,即30240=7200W3.3 、湿负荷的计算3.3.1、人体散湿
19、量可按下式计算:mw1=0.278ng10-6 g/s (57)式中: mw1 -人体散湿量, g/s;; g - 成年男子的小时散湿量,g/h; n - 室内全部人数; - 群集系数;3.4、新风负荷计算夏季空调新风冷负荷Qc.o=Mo(iwin) (58)式中: Qc.o-夏季新风冷负荷,KW; Mo-新风量,kg/s; iw-室外空气的焓值,kJ/kg in-室内空气的焓值,kJ/kg;3.5负荷计算实例以十层客房1001计算为例:(设计参数如前面表格所示)1).北外墙负荷:砖墙,白灰粉刷,厚度370 mm 型墙 K=1.5W/(m2 ) A=36.12 M2时间11:0012:0013
20、:0014:0015:0016:0017:0018:0019:0020:00tc()3131.431.331.231.231.331.431.631.832.1td0000000000k1.0261.0261.0261.0261.0261.0261.0261.0261.0261.026k0.940.940.940.940.940.940.940.940.940.94tc()29.930.2830.1930.0930.0930.1930.2830.4830.6730.96tR26262626262626262626t3.94.284.194.094.094.194.284.484.674.96K
21、1.51.51.51.51.51.51.51.51.51.5A12.1412.1412.1412.1412.1412.1412.1412.1412.1412.14Qc()70.9978.01476.2674.5074.5076.2678.0181.5385.0490.312).北外窗瞬时传热冷负荷:(规格: 单层窗(3mm),金属窗框,80%玻璃)根据ai=8.7 W/(K)和ao=14.4 W/(K),有附录2-8查得Kw=2.878W/(K)金属单层钢窗应乘以1.0的修正系数。则Kw=2.878W/(m2K)时间11:0012:0013:0014:0015:0016:0017:0018:0
22、019:0020:00tc()29.930.831.531.932.232.23231.630.829.9td000000000029.930.831.531.932.232.23231.630.829.9tR26262626262626262626t3.94.85.55.96.26.265.64.83.9Kw5.6245.6245.6245.6245.6245.6245.6245.6245.6245.624Aw4.064.0584.0584.0584.0584.0584.0584.0584.0584.058Qc()89.01109.55125.53134.66141.5141.5136.91
23、27.8109.689.013).北外窗透入日射得热引起的冷负荷:根据规范查双层钢窗有效面积系数Ca =0.85采用内遮阳系数c,s=0.890.5=0.43查得北纬39,南向日射得热因数最大值Dj,max=599W/m2福州地区北纬3948,属于北区,查得南区有内遮阳的玻璃窗冷负荷系数逐时值LQ=0.81时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00CLQ0.810.830.830.790.710.60.610.680.170.16Dj,max599599599599599599599599599599Cc,s0.4450.4450.
24、4450.4450.4450.4450.4450.4450.4450.445Aw3.453.453.453.453.453.453.453.453.453.45Qc()744.9763.3763.3726.5652.9551.8561625.3156.3147.24) .人员散热引起的冷负荷:休息室属于极轻劳动。当室温为26,每人散发的显热和潜热量为60.5W和73.3W。查得群集系数n2=0.93。查得人体显热散热冷负荷系数逐时值。休息室人数为3人。时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00CLQ 0.280.240.20.180
25、.160.620.70.750.790.82qs60.560.560.560.560.560.560.560.560.560.5n33333333330.930.930.930.930.930.930.930.930.930.93Qc()47.2640.5133.7630.3827.01104.7118.2126.6133.35138.4ql73.373.373.373.373.373.373.373.373.373.3Qc204.5204.5204.5204.5204.5204.5204.5204.5204.5204.5合计251.77245.02238.3234.9231.5309.163
26、22.66331.1337.86342.95).照明散热形成的冷负荷:则房间的照明总功率为1000W荧光灯明装,镇流器设在顶棚内,n1=1.2。灯罩的隔热系数n2=0.8。时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00CLQ0.10.090.080.070.060.370.670.710.740.76n11.21.21.21.21.21.21.21.21.21.2n20.80.80.80.80.80.80.80.80.80.8N1000100010001000100010001000100010001000Qc()9686.476.86
27、7.257.6355.2643.2681.6710.4729.66)西外墙冷负荷:砖墙,白灰粉刷,厚度370 mm 型墙 K=1.5 W/(m2 ) 时间11:0012:0013:0014:0015:0016:0017:0018:0019:00tc()36.335.935.535.234.934.834.834.935.3td000000000k1.0261.0261.0261.0261.0261.0261.0261.0261.026k0.940.940.940.940.940.940.940.940.94tc()35.0134.6234.2433.9533.6633.5633.5633.66
28、34.045tR262626262626262626t9.018.628.247.957.667.567.567.668.045K1.51.51.51.51.51.51.51.51.5A49.849.849.849.849.849.849.849.849.8Qc()672.99644.17615.35593.74572.1564.92564.92572.124600.97)北外窗瞬时传热冷负荷:(规格: 单层窗(3mm),金属窗框,80%玻璃)根据ai=8.7 W/(K)和ao=14.4 W/(K),有附录2-8查得Kw=2.878W/(K)金属单层钢窗应乘以1.0的修正系数。则Kw=3.04
29、*1.2= 3.648W/(m2K)时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00tc()29.930.831.531.932.232.23231.630.829.9td000000000029.930.831.531.932.232.23231.630.829.9tR26262626262626262626t3.94.85.55.96.26.265.64.83.9Kw5.6245.6245.6245.6245.6245.6245.6245.6245.6245.624Aw4.24.24.24.24.24.24.24.24.24.2Qc(
30、)92.12113.38129.91139.36146.45146.45141.72132.285113.3892.128)北外窗透入日射得热引起的冷负荷:根据规范查双层钢窗有效面积系数Ca =0.85采用内遮阳系数c,s=0.89*0.5=0.43查得北纬39,南向日射得热因数最大值Dj,max=599W/m2福州地区北纬3948,属于北区,查得南区有内遮阳的玻璃窗冷负荷系数逐时值LQ=0.81时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00CLQ0.190.20.340.560.720.830.770.530.110.1Dj,max5
31、99599599599599599599599599599Cc,s0.4450.4450.4450.4450.4450.4450.4450.4450.4450.445Aw3.573.573.573.573.573.573.573.573.573.57Qc()180.8190.32323.54532.9685.15789.83732.7504.35104.6895.169)屋顶冷负荷:屋面:从上到下为:预制细石混凝土板25mm;表面喷白色水泥浆;通风量200mm;卷材防水层;水泥砂浆找平层20mm;保温层,沥青膨胀珍珠岩125mm;隔汽层;现浇钢筋混凝土板70mm;内粉刷;属型,传热系数K=0.
32、48W/(K)时间11:0012:0013:0014:0015:0016:0017:0018:0019:0020:00tc()35.635.6363738.440.141.943.745.446.7td0000000000k1.0261.0261.0261.0261.0261.0261.0261.0261.0261.026k0.940.940.940.940.940.940.940.940.940.94tc()34.3334.3334.7235.6837.0338.6740.442.1543.7945.04tR26262626262626262626K0.480.480.480.480.480
33、.480.480.480.480.48A72727272727272727272Qc()288.03288.03301.36334.69381.35438.02498.01558.01614.6765810)将1001室内各部分的逐时冷负荷的计算结果列于下表:时间屋顶负荷北外墙东外墙西外墙北窗传热北窗日射东窗传热东窗日射西窗传热西窗日射人员负荷灯光负荷总计11:00288.0370.9944.90672.9989.01744.8924.1394.7192.12180.8251.77962650.3312:00288.0378.0144.90644.17109.55763.2829.6959.8
34、1113.38190.3245.0386.42652.5713:00301.3676.2646.02615.35125.52763.2834.0359.81129.91323.5238.2776.82790.1514:00334.6974.5048.25593.74134.65726.5036.5057.32139.36532.9234.8967.22980.5015:00381.3574.5051.05572.12141.50652.9338.3652.34146.45685.2231.5157.63084.8616:00438.0276.2653.84564.92141.50551.773
35、8.3644.86146.45789.8309.16355.23510.1517:00498.0178.0156.63564.92136.93560.9737.1237.38141.72732.7322.66643.23810.3018:00558.0181.5358.86572.12127.80625.3434.6427.42132.28504.3331.10681.63735.0519:00614.6785.0461.10600.94109.55156.3329.6919.94113.38104.7337.86710.42943.5720:00658.0090.3162.77636.968
36、9.01147.1424.1317.4592.1295.16342.93729.62985.5621:00684.6795.5863.89687.3970.75137.9419.1817.4573.2285.64347.98758.43042.0922:00694.6699.0964.45745.0354.77128.7514.8514.9556.6985.64351.36777.63087.8523:00691.33104.3665.01795.4641.0811.9511.1414.9542.5276.13353.05796.83003.780:00674.67107.8764.45831
37、.4827.39110.357.4214.9528.3576.13356.42806.43105.88由上表可知, 1001室下午18:00出现最大冷负荷3810.3W.3.6 各层冷负荷汇总3.6.1 十层其他房间负荷计算如下:时刻11:0012:0013:0014:0015:0016:0017:0018:0019:0020:0010012650.32652.62790.22980.53084.93510. 23810.33735.12943.62985.610021666.41666.71681.51670.31630.81951.22305.22452.72043.52074.51003
38、1638.31638.41652.21637.91594.21909.42257.92399.91985.52012.410041619.11619.21632.01615.61568.81880.22224.72362.71944.51968.610051346.41381.31391.91371.41320.11540.51822.01954.51514.81533.510061420.314251441.21425.71379.11540. 81756.21864.51442.81452.010071395.91400.61415.81397.81347.81505.31716.3182
39、0.31394.41400.410081104.11133.51226.41374.61505.81912.32180.02147.32002.32039.51009938.7947.91084.21306.91478.31845.12001.71832.01481.21505.91010324.3315.9313.0320.6333.6527.7676.4722.0761.2790.01011324.32315.9313.0320.6333.6527.7676.4722.0761.2790.01012324.3315.9313.0320.6333.6527.7676.4722.0761.27
40、90.01013324.3315.9313.0320.6333.6527.7676.4722.0761.2790.010141317.91437.31408.41258.31128.01275.51421.51413.41405.91428.110151283.71403.81374.91223.11089.81233.41374.91362.01349.91368.110161283.71403.81374.91223.11089.81233.41374.91362.01349.91368.110171283.71403.81374.91223.11089.81233.41374.91362
41、.01349.91368.110181283.71403.81374.91223.11089.81233.41374.91362.01349.91368.1合计21529221812247522213217312591429701303182660227033由上表可知, 下午18:00出现最大冷负荷30318W.3.6.2六至九层房间冷负荷由下表可知,下午17:00出现最大冷负荷24263W.时刻11:0012:0013:0014:0015:0016:0017:0018:0019:0020:0069012362.32364.52488.82645.82703.53072.13312.3317
42、7.02328.92327.669021416.41416.71419.91379.81299.81570.91872.91968.31509.91503.369031414.31414.41417.71377.61297.61568.71870. 61965.91507.41500.669041414.31414.41417.71377.61297.61568.71870. 61965.91507.41500.669051175.61210.51213.11172.91093.91280.811526.71623.51150.21143.269061260.31265.01273.81239.7116731297.41479.51554.51101.31086.469071255.91260.61269.41235.11162.521292.41474.21549.01095.61080.
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 无证房屋交易合同范本
- 合同转让合同的签订技巧
- 广告媒体设计合同
- 广告委托协议-合同范本
- 六年级语文上册第六单元口语交际 意见不同怎么办 公开课一等奖创新教学设计
- 《痴呆震颤麻痹》课件
- 狂犬病辩证论治方案
- 手术区铺无菌手术单
- 胫骨远端骨折术后护理
- 年产xx男帽项目建议书
- 市政污水管网深基坑拉森钢板桩支护专项施工方案
- (2.1.1)-投影法及三视图
- 2023年医师病历书写规范培训课件PPT(医务人员学习资料)
- GB/T 32661-2016球形二氧化硅微粉
- GB/T 1550-2018非本征半导体材料导电类型测试方法
- 某生物科技有限公司每日4万沼气提纯制天然气项目技术方案
- 千年菩提路解说词
- 灭火器日常检查记录表格
- 测绘地理信息从业人员保密知识培训课件
- 软件开发-项目-监理细则
- 静脉血栓防治解读(实用课件)
评论
0/150
提交评论