接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表_第1页
接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表_第2页
接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表_第3页
全文预览已结束

下载本文档

版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领

文档简介

接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表,,,,,,,,,,,,,,,,,,

工程名称:中建梅溪湖中心,,,,,,检查人:,,,,,,,,时间:,,,,

序号,电器名称,接地电阻,,,绝缘电阻,,,,,,,,,,,,漏电保护器漏电动作参数,

,,组别及电器设备名称,规范要求电阻值,实测电阻值,试验内容,,相间,,,相对零,,,相对地,,,零对地,动作,动作

,,,,,,,,,,,,,,,,,电流,时间

,,,,,,,,,,,,,,,,,(ma),(s)

1,总配电箱,总配电箱,≤4Ω,3.2,名称、编号,总配电箱,A-B,B-C,C-A,A-N,B-N,C-N,A-PE,B-PE,C-PE,PE-N,30,0.18

,,,,,,,300,250,250,250,300,350,300,250,350,150,,

,,,,,,塔吊1号动力分箱,250,315,60,295,190,170,195,260,175,195,30,0.18

,,,,,,钢筋加工区2号动力分箱,105,105,120,265,215,85,95,95,260,185,30,0.18

,,,,,,木工加工棚3号动力分箱,155,85,145,85,230,80,70,245,210,300,30,0.18

,,,,,,施工现场5号移动动力分箱,245,325,70,205,300,190,140,275,295,305,30,0.18

,,,,,,施工现场7号照明分箱,,,,160,,,95,,,130,30,0.18

,,,,,,生活区8号照明分箱,,,,,245,,,85,,275,30,0.18

,,,,,,食堂区9号照明分箱,,,,,,220,,,150,310,30,0.18

2,塔吊1号动力分箱,塔吊1号动力分箱,≤4Ω,3.1,名称,塔吊1号动力分箱,155,225,110,270,250,85,175,255,115,215,30,0.18

,,,,,,塔式起重机开关箱,210,180,100,150,245,210,230,135,135,135,30,0.18

3,钢筋加工区2号动力分箱,钢筋加工区2号动力分箱,≤4Ω,3.5,名称、编号,钢筋加工区2号动力分箱,140,235,290,120,315,210,290,195,225,190,30,0.18

,,,,,,钢筋调直机开关箱,120,100,225,290,100,260,205,280,325,90,30,0.18

,,,,,,钢筋切断机开关箱,85,260,125,65,135,110,120,305,70,310,30,0.18

,,,,,,钢筋弯曲机开关箱,100,190,105,195,315,105,210,250,235,285,30,0.18

,,,,,,交流电焊机开关箱,115,130,170,75,280,180,190,145,145,315,30,0.18

,,,,,,直流电焊机开关箱,225,115,310,295,135,220,230,285,305,325,30,0.18

接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表,,,,,,,,,,,,,,,,,2012年5月25日,

序号,电器名称,接地电阻,,,绝缘电阻,,,,,,,,,,,,漏电保护器漏电动作参数,

,,组别及电器设备名称,规范要求电阻值,实测电阻值,试验内容,,相间,,,相对零,,,相对地,,,零对地,动作,动作

,,,,,,,,,,,,,,,,,电流,时间

,,,,,,,,,,,,,,,,,(ma),(s)

4,木工加工棚3号动力分箱,木工加工棚3号动力分箱,≤4Ω,3.5,名称、编号,木工加工棚3号动力分箱,170,185,90,60,60,235,145,155,130,115,30,0.18

,,,,,,木工圆锯开关箱,220,105,220,195,305,125,325,80,65,305,30,0.18

,,,,,,木工圆锯开关箱,165,115,295,205,305,265,65,275,305,130,30,0.18

,,,,,,双面木工压刨机开关箱,120,250,275,280,85,170,190,280,255,65,30,0.18

5,施工现场7号照明分箱,施工现场7号照明分箱,≤4Ω,3.7,名称,施工现场7号照明分箱,,,,205,,,185,,,145,30,0.08

,,,,,,高压汞灯(3台)开关箱,,,,320,,,150,,,150,30,0.08

6,生活区8号照明分箱,生活区8号照明分箱,≤4Ω,3.2,名称、编号,生活区8号照明分箱,,,,,190,,,290,,120,30,0.08

,,,,,,荧光灯开关箱,,,,,270,,,130,,185,30,0.08

,,,,,,空调开关箱,,,,,190,,,100,,155,30,0.08

,,,,,,电热水器开关箱,,,,,90,,,220,,75,30,0.08

,,,,,,电视机(4台)开关箱,,,,,70,,,65,,315,30,0.08

接地电阻、绝缘电阻和漏电保护器漏电动作参数测定记录表,,,,,,,,,,,,,,,,,2012年5月25日,

序号,电器名称,接地电阻,,,绝缘电阻,,,,,,,,,,,,漏电保护器漏电动作参数,

,,组别及电器设备名称,规范要求电阻值,实测电阻值,试验内容,,相间,,,相对零,,,相对地,,,零对地,动作,动作

,,,,,,,,,,,,,,,,,电流,时间

,,,,,,,,,,,,,,,,,(ma),(s)

7,食堂9号照明分箱,食堂9号照明分箱,≤4Ω,3.1,名称、编号,食堂9号照明分箱,,,,,,290,,,325,190,30,0.08

,,,,,,荧光灯开关箱,,,,,,95,,,215,315,30,0.08

,,,,,,紫外线灭蚊灯开关箱,,,,,,210,,,245,195,30,0.08

,,,,,,冰柜开关箱,,,,,,250,,,220,70,30,0.08

,,,,,,抽排油烟机开关箱,,,,,,135,,,210,120,30,0.08

,,,,,,蒸汽柜开关箱,,,,,,275,,,140,115,30,0.08

,,,,,,消毒柜开关箱,,,,,,310,,,320,205,30,0.08

,,,,,,,,,,,,,,,,,

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。