版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
校区建筑单体B3负荷计算书,,,,,,,,,,,,,,
工程信息,,,,,,,,,,,,,,
基本参数,工程名字,工程编号,建设单位,计算人,审定人,校对人,日期,冷负荷单位,热负荷单位,湿负荷单位,冷负荷修正系数,热负荷修正系数,湿负荷修正系数,
,,,,,,,2014/5/7,瓦特(W),瓦特(W),千克每小时(kg/h),1,1,1,
,,,,,,,,,,,,,,,
气象参数,,,,,,,,,,,,,,
基本参数,国家,省份,城市,经度(°E),纬度(°N),,,,,,,,,
,中国,广东省,深圳,114.06,22.33,,,,,,,,,
夏季参数,夏季大气压(Pa),夏季室外空调计算日平均温度(℃),夏季室外空调计算干球温度(℃),夏季室外空调计算湿球温度(℃),夏季室外平均风速(m/s),大气透明度等级,,,,,,,,
,100240,30.5,33.7,27.5,2.2,5,,,,,,,,
,,,,,,,,,,,,,,,
工程负荷统计,,,,,,,,,,,,,,
夏季负荷统计,面积(㎡),夏季总冷负荷最大时刻(含新风/全热)(h),夏季室内冷负荷最大时刻(全热)(h),夏季总冷负荷(含新风/全热)(W),夏季室内冷负荷(全热)(W),夏季总湿负荷(含新风)(kg/h),夏季室内湿负荷(kg/h),夏季新风量(m^3),夏季新风冷负荷(W),夏季新风机组冷负荷(全热)(W),夏季新风机组冷负荷(显热)(W),夏季新风机组冷负荷(潜热)(W),,
,3962.7,16:00,16:00,585373,318834,454.328,46.124,32964.3,375539,375539,82999,292540,,
,,,,,,,,,,,,,,,
建筑物信息,,,,,,,,,,,,,,
参数,,建筑物名称,底层起始标高(m),起始楼层,终止楼层,跳过楼层号,建筑物体积(m^3),夏季围护结构外表面换热系数(W/(㎡·K)),冬季围护结构外表面换热系数(W/(㎡·K)),围护结构内表面换热系数(W/(㎡·K)),,,,
基本参数,学术交流中心,学术交流中心,0,1,4,,0,18.6,23,8.7,,,,
,,,,,,,,,,,,,,,
围护结构信息,,,,,,,,,,,,,,
学术交流中心围护结构基本信息,,,,,,,,,,,,,,
参数,,围护结构夏季传热系数(W/(㎡·K)),围护结构冬季传热系数(W/(㎡·K)),,,,,,,,,,,
外墙,混凝土加气混凝土280(087001),1.25,1.27,,,,,,,,,,,
外窗,断热铝合金普通中空玻璃窗,3.5,3.63,,,,,,,,,,,
外门,节能外门,3.02,3.12,,,,,,,,,,,
内门,木(塑料)框单层实体门,3.35,3.35,,,,,,,,,,,
屋面,预制01-1-35-1,0.76,0.77,,,,,,,,,,,
天窗,断热铝合金普通中空玻璃窗,3.5,3.63,,,,,,,,,,,
楼板,楼面-2,0.65,0.65,,,,,,,,,,,
内墙,砖墙(003003),2.38,2.38,,,,,,,,,,,
内窗,双层5mm外窗,2.58,2.58,,,,,,,,,,,
,,,,,,,,,,,,,,,
建筑物负荷统计,,,,,,,,,,,,,,
夏季负荷统计,,,,,,,,,,,,,,
参数,面积(㎡),夏季总冷负荷最大时刻(含新风/全热)(h),夏季室内冷负荷最大时刻(全热)(h),夏季总冷负荷(含新风/全热)(W),夏季室内冷负荷(全热)(W),夏季总湿负荷(含新风)(kg/h),夏季室内湿负荷(kg/h),夏季新风量(m^3),夏季新风冷负荷(W),夏季新风机组冷负荷(全热)(W),夏季新风机组冷负荷(显热)(W),夏季新风机组冷负荷(潜热)(W),,
学术交流中心,3962.7,16:00,16:00,694373,318834,454.328,46.124,32964.3,375539,375539,82999,292540,,
,,,,,,,,,,,,,,,
楼层信息,,,,,,,,,,,,,,
学术交流中心所有楼层信息,,,,,,,,,,,,,,
参数,,楼层号,层高(m),窗高(m),标高(m),属性,描述,,,,,,,
基本参数,1楼层,1,5.4,1.8,0,普通楼层,,,,,,,,
,2楼层,2,3.4,1.8,5.4,普通楼层,,,,,,,,
,3楼层,3,3.4,1.8,8.8,普通楼层,,,,,,,,
,4楼层,4,3.4,1.8,12.2,普通楼层,,,,,,,,
,,,,,,,,,,,,,,,
楼层负荷统计,,,,,,,,,,,,,,
学术交流中心所有楼层负荷统计,,,,,,,,,,,,,,
夏季负荷统计,,,,,,,,,,,,,,
参数,面积(㎡),夏季总冷负荷最大时刻(含新风/全热)(h),夏季室内冷负荷最大时刻(全热)(h),夏季总冷负荷(含新风/全热)(W),夏季室内冷负荷(全热)(W),夏季总湿负荷(含新风)(kg/h),夏季室内湿负荷(kg/h),夏季新风量(m^3),夏季新风冷负荷(W),夏季新风机组冷负荷(全热)(W),夏季新风机组冷负荷(显热)(W),夏季新风机组冷负荷(潜热)(W),,
1楼层,1174.3,16:00,16:00,338920,96663,287.309,19.42,20037.9,242256,242256,50452,191804,,
2楼层,1125.2,16:00,16:00,197711,93077,128.672,19.574,10431.6,104634,104634,26265,78369,,
3楼层,1056,16:00,16:00,86190,68001,24.333,4.513,1584,18189,18189,3988,14201,,
4楼层,607.2,17:00,17:00,72292,61833,14.014,2.617,910.8,10459,10459,2293,8166,,
,,,,,,,,,,,,,,,
房间负荷统计,,,,,,,,,,,,,,
学术交流中心所有房间负荷统计,,,,,,,,,,,,,,
夏季负荷统计,,,,,,,,,,,,,,
参数,面积(㎡),夏季总冷负荷最大时刻(含新风/全热)(h),夏季室内冷负荷最大时刻(全热)(h),夏季总冷负荷(含新风/全热)(W),夏季室内冷负荷(全热)(W),夏季总湿负荷(含新风)(kg/h),夏季室内湿负荷(kg/h),夏季新风量(m^3),夏季新风冷负荷(W),夏季新风机组冷负荷(全热)(W),夏季新风机组冷负荷(显热)(W),夏季新风机组冷负荷(潜热)(W),,
1001[办公室],33.5,17:00,17:00,4601,3447,1.469,0.212,100.5,1154,1154,253,901,,
"1002[办公室,4]",33.5,17:00,17:00,4318,3164,1.469,0.212,100.5,1154,1154,253,901,,
1003[安防、楼控合用分控室],80,17:00,17:00,7805,5049,3.454,0.452,240,2756,2756,604,2152,,
"1004[包间,3]",29,14:00,14:00,11059,3567,8.918,0.594,609,7492,7492,1533,5959,,
1005[包间],29,15:00,15:00,11400,3907,8.918,0.594,609,7492,7492,1533,5959,,
1006[会议室],48.2,15:00,15:00,19986,5762,16.067,1.34,1446,14224,14224,3641,10583,,
1007[主任办公室],33.4,15:00,15:00,4795,3644,1.465,0.211,100.2,1151,1151,252,898,,
1008[餐厅],729.2,8:00,8:00,248754,60367,228.846,19.526,15313.2,188387,188387,38556,149831,,
,,,,,,,,,,,,,,,
2001[小会议室],32.8,17:00,17:00,14087,4408,11.745,1.724,984,9679,9679,2478,7202,,
"2002[中会议室,2]",67.5,17:00,17:00,29599,9680,24.168,3.545,2025,19919,19919,5099,14821,,
2003[大会议室],139,17:00,17:00,60427,19407,49.702,7.233,4170,41019,41019,10499,30520,,
2004[客房],26.4,14:00,14:00,1980,1525,0.609,0.114,39.6,455,455,100,355,,
"2005[客房,9]",26.4,14:00,14:00,1822,1368,0.609,0.114,39.6,455,455,100,355,,
2006[客房],26.4,15:00,15:00,2039,1584,0.609,0.114,39.6,455,455,100,355,,
2007[客房],26.4,16:00,16:00,2679,2224,0.609,0.114,39.6,455,455,100,355,,
"2008[客房,8]",26.4,16:00,16:00,2516,2061,0.609,0.114,39.6,455,455,100,355,,
2009[客房],26.4,16:00,16:00,2711,2256,0.609,0.114,39.6,455,455,100,355,,
2010[客房],26.4,9:00,9:00,2783,2328,0.609,0.114,39.6,455,455,100,355,,
"2011[客房,8]",26.4,9:00,9:00,2594,2139,0.609,0.114,39.6,455,455,100,355,,
2012[客房],26.4,9:00,9:00,2751,2296,0.609,0.114,39.6,455,455,100,355,,
,,,,,,,,,,,,,,,
"3001[客房,2]",26.4,17:00,17:00,2049,1594,0.609,0.114,39.6,455,455,100,355,,
"3002[客房,5]",26.4,17:00,17:00,1871,1416,0.609,0.114,39.6,455,455,100,355,,
3003[客房],26.4,17:00,17:00,6251,5796,0.57,0.075,39.6,455,455,100,355,,
3004[客房],26.4,17:00,17:00,2117,1663,0.609,0.114,39.6,455,455,100,355,,
3005[客房],26.4,14:00,14:00,1980,1525,0.609,0.114,39.6,455,455,100,355,,
"3006[客房,9]",26.4,14:00,14:00,1822,1368,0.609,0.114,39.6,455,455,100,355,,
3007[客房],26.4,15:00,15:00,2039,1584,0.609,0.114,39.6,455,455,100,355,,
3008[客房],26.4,16:00,16:00,2679,2224,0.609,0.114,39.6,455,455,100,355,,
"3009[客房,8]",26.4,16:00,16:00,2516,2061,0.609,0.114,39.6,455,455,100,355,,
3010[客房],26.4,16:00,16:00,2711,2256,0.609,0.114,39.6,455,455,100,355,,
3011[客房],26.4,9:00,9:00,2783,2328,0.609,0.114,39.6,455,455,100,355,,
"3012[客房,8]",26.4,9:00,9:00,2594,2139,0.609,0.114,39.6,455,455,100,355,,
3013[客房],26.4,9:00,9:00,2751,2296,0.609,0.114,39.6,455,455,100,355,,
,,,,,,,,,,,,,,,
4001[客房],26.4,17:00,17:00,3318,2864,0.609,0.114,39.6,455,455,100,355,,
"4002[客房,11]",26.4,17:00,17:00,3141,2686,0.609,0.114,39.6,455,455,100,355,,
4003[客房],26.4,17:00,17:00,3387,2932,0.609,0.114,39.6,455,455,100,355,,
4004[客房],26.4,16:00,16:00,3238,2783,0.609,0.114,39.6,455,455,100,355,,
"4005[客房,8]",26.4,16:00,16:00,3074,2620,0.609,0.114,39.6,455,455,100,355,,
4006[客房],26.4,17:00,17:00,3273,2819,0.609,0.114,39.6,455,455,100,355,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
房间详细计算,,,,,,,,,,,,,,
学术交流中心所有房间详细计算,,,,,,,,,,,,,,
1001[办公室],,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,办公室,33.5,25,55,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,3.35,静坐,0.89,人员_办公建筑_工作日,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,100.5,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,0.44,人员_办公建筑_工作日,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,368.5,人员_办公建筑_工作日,,,,,,,,,,,
外墙[西],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[西],西,混凝土加气混凝土280(087001),8.4,5.4,45.36,45.36,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),4.2,5.4,22.68,4.68,,,,,,,
外窗[北],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[北],北,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),4.2,5.4,22.68,20.88,,,,,,,
外门[南],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[南],南,节能外门,0.9,2,1.8,,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),118,234,259,268,242,241,275,284,288,290,152,125,54
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),57,118,143,152,144,143,159,168,171,174,116,89,54
,潜热负荷(W),61,116,116,116,98,98,116,116,116,116,37,37,0
,湿负荷(kg/h),0.091,0.173,0.173,0.173,0.145,0.145,0.173,0.173,0.173,0.173,0.055,0.055,0
新风[冷],总冷负荷(W),1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154
,显热负荷(W),253,253,253,253,253,253,253,253,253,253,253,253,253
,潜热负荷(W),901,901,901,901,901,901,901,901,901,901,901,901,901
,湿负荷(kg/h),1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),253,253,253,253,253,253,253,253,253,253,253,253,253
,新风机组潜热负荷(W),901,901,901,901,901,901,901,901,901,901,901,901,901
,新风机组负荷(W),1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154
,新风机组湿负荷(kg/h),1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257
设备,总冷负荷(W),88,171,183,187,165,165,191,195,197,198,92,79,27
灯光,总冷负荷(W),87,190,249,271,266,261,285,305,313,319,239,174,119
外墙[西],总冷负荷(W),341,321,302,286,274,267,263,264,270,283,303,331,364
,辐射照度(W),114,147,166,178,179,374,536,638,626,515,221,0,0
,负荷温差(℃),10.6,10,9.4,8.9,8.6,8.3,8.2,8.3,8.4,8.8,9.5,10.3,11.4
外墙[北],总冷负荷(W),26,25,24,23,23,23,24,24,25,27,28,29,31
,辐射照度(W),201,193,168,178,179,178,168,193,201,188,95,0,0
,负荷温差(℃),7.8,7.4,7.1,6.9,6.9,7,7.1,7.4,7.7,8.1,8.5,8.9,9.4
外窗[北],总冷负荷(W),1279,1432,1581,1651,1825,1956,2074,2089,2094,2125,1941,1186,1001
,负荷温差(℃),4,4.6,5.1,5.7,6.2,6.7,7,7.1,7,7,6.7,6.2,5.7
,直射面积(㎡),18,18,18,0,0,0,18,18,18,18,18,0,0
,散射面积(㎡),18,18,18,18,18,18,18,18,18,18,18,18,18
,直射辐射照度(W),28,7,0,0,0,0,0,7,28,54,41,0,0
,散射辐射照度(W),94,121,136,146,148,146,136,121,94,65,24,0,0
,直射负荷强度(W/㎡),72.2,80.5,88.6,98.6,106.7,112.9,115.3,115.8,116.5,118.9,107.3,75.6,56.3
,散射负荷强度(W/㎡),45.2,62.5,78,91.3,101.1,108.3,111.5,110.7,104,92.7,75.2,56.9,46.1
,直射负荷(W),1040,1159,1276,0,0,0,1660,1667,1678,1712,1546,0,0
,散射负荷(W),0,0,0,1314,1456,1560,0,0,0,0,0,819,664
,总辐射负荷(W),1040,1159,1276,1314,1456,1560,1660,1667,1678,1712,1546,819,664
,温差传热负荷(W),239,273,304,337,369,396,414,422,416,413,395,367,338
外墙[南],总冷负荷(W),106,100,96,92,90,90,92,95,101,107,114,121,127
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外门[南],总冷负荷(W),68,77,84,92,100,105,106,105,102,98,92,83,77
,辐射照度(W/㎡),114.3,147.1,165.6,205.9,217.8,205.9,165.6,147.1,114.3,78.7,29,0,0
,负荷温差(℃),6,7.5,8.9,10.3,11.8,12.7,12.9,12.6,12.2,11.4,10.3,8.7,7.6
"1002[办公室,4]",,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,办公室,33.5,25,55,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,3.35,静坐,0.89,人员_办公建筑_工作日,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,100.5,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,0.44,人员_办公建筑_工作日,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,368.5,人员_办公建筑_工作日,,,,,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),4.2,5.4,22.68,4.68,,,,,,,
外窗[北],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[北],北,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),4.2,5.4,22.68,20.88,,,,,,,
外门[南],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[南],南,节能外门,0.9,2,1.8,,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),118,234,259,268,242,241,275,284,288,290,152,125,54
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),57,118,143,152,144,143,159,168,171,174,116,89,54
,潜热负荷(W),61,116,116,116,98,98,116,116,116,116,37,37,0
,湿负荷(kg/h),0.091,0.173,0.173,0.173,0.145,0.145,0.173,0.173,0.173,0.173,0.055,0.055,0
新风[冷],总冷负荷(W),1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154
,显热负荷(W),253,253,253,253,253,253,253,253,253,253,253,253,253
,潜热负荷(W),901,901,901,901,901,901,901,901,901,901,901,901,901
,湿负荷(kg/h),1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),253,253,253,253,253,253,253,253,253,253,253,253,253
,新风机组潜热负荷(W),901,901,901,901,901,901,901,901,901,901,901,901,901
,新风机组负荷(W),1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154,1154
,新风机组湿负荷(kg/h),1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257,1.257
设备,总冷负荷(W),88,171,183,187,165,165,191,195,197,198,92,79,27
灯光,总冷负荷(W),87,190,249,271,266,261,285,305,313,319,239,174,119
外墙[北],总冷负荷(W),26,25,24,23,23,23,24,24,25,27,28,29,31
,辐射照度(W),201,193,168,178,179,178,168,193,201,188,95,0,0
,负荷温差(℃),7.8,7.4,7.1,6.9,6.9,7,7.1,7.4,7.7,8.1,8.5,8.9,9.4
外窗[北],总冷负荷(W),1279,1432,1581,1651,1825,1956,2074,2089,2094,2125,1941,1186,1001
,负荷温差(℃),4,4.6,5.1,5.7,6.2,6.7,7,7.1,7,7,6.7,6.2,5.7
,直射面积(㎡),18,18,18,0,0,0,18,18,18,18,18,0,0
,散射面积(㎡),18,18,18,18,18,18,18,18,18,18,18,18,18
,直射辐射照度(W),28,7,0,0,0,0,0,7,28,54,41,0,0
,散射辐射照度(W),94,121,136,146,148,146,136,121,94,65,24,0,0
,直射负荷强度(W/㎡),72.2,80.5,88.6,98.6,106.7,112.9,115.3,115.8,116.5,118.9,107.3,75.6,56.3
,散射负荷强度(W/㎡),45.2,62.5,78,91.3,101.1,108.3,111.5,110.7,104,92.7,75.2,56.9,46.1
,直射负荷(W),1040,1159,1276,0,0,0,1660,1667,1678,1712,1546,0,0
,散射负荷(W),0,0,0,1314,1456,1560,0,0,0,0,0,819,664
,总辐射负荷(W),1040,1159,1276,1314,1456,1560,1660,1667,1678,1712,1546,819,664
,温差传热负荷(W),239,273,304,337,369,396,414,422,416,413,395,367,338
外墙[南],总冷负荷(W),106,100,96,92,90,90,92,95,101,107,114,121,127
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外门[南],总冷负荷(W),68,77,84,92,100,105,106,105,102,98,92,83,77
,辐射照度(W/㎡),114.3,147.1,165.6,205.9,217.8,205.9,165.6,147.1,114.3,78.7,29,0,0
,负荷温差(℃),6,7.5,8.9,10.3,11.8,12.7,12.9,12.6,12.2,11.4,10.3,8.7,7.6
1003[安防、楼控合用分控室],,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,安防、楼控合用分控室,80,25,55,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,8,静坐,0.89,人员_办公建筑_工作日,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,240,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,1.04,人员_办公建筑_工作日,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,880,人员_办公建筑_工作日,,,,,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),9.8,5.4,52.92,31.92,,,,,,,
外窗[北],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[北],北,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外门[北],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[北],北,节能外门,1.5,2,3,,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),9.5,5.4,51.3,51.3,,,,,,,
外墙[东],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[东],东,混凝土加气混凝土280(087001),8.4,5.4,45.36,45.36,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),283,558,618,640,578,575,657,678,687,693,363,300,129
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),137,281,341,363,345,341,380,400,409,416,276,212,129
,潜热负荷(W),146,277,277,277,234,234,277,277,277,277,88,88,0
,湿负荷(kg/h),0.217,0.413,0.413,0.413,0.347,0.347,0.413,0.413,0.413,0.413,0.13,0.13,0
新风[冷],总冷负荷(W),2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756
,显热负荷(W),604,604,604,604,604,604,604,604,604,604,604,604,604
,潜热负荷(W),2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152
,湿负荷(kg/h),3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),604,604,604,604,604,604,604,604,604,604,604,604,604
,新风机组潜热负荷(W),2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152,2152
,新风机组负荷(W),2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756,2756
,新风机组湿负荷(kg/h),3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003,3.003
设备,总冷负荷(W),211,409,437,447,395,393,455,465,469,473,219,189,64
灯光,总冷负荷(W),208,453,596,647,635,623,680,728,748,762,571,417,285
外墙[北],总冷负荷(W),177,168,161,156,155,157,161,166,174,182,191,201,211
,辐射照度(W),201,193,168,178,179,178,168,193,201,188,95,0,0
,负荷温差(℃),7.8,7.4,7.1,6.9,6.9,7,7.1,7.4,7.7,8.1,8.5,8.9,9.4
外窗[北],总冷负荷(W),1279,1432,1581,1651,1825,1956,2074,2089,2094,2125,1941,1186,1001
,负荷温差(℃),4,4.6,5.1,5.7,6.2,6.7,7,7.1,7,7,6.7,6.2,5.7
,直射面积(㎡),18,18,18,0,0,0,18,18,18,18,18,0,0
,散射面积(㎡),18,18,18,18,18,18,18,18,18,18,18,18,18
,直射辐射照度(W),28,7,0,0,0,0,0,7,28,54,41,0,0
,散射辐射照度(W),94,121,136,146,148,146,136,121,94,65,24,0,0
,直射负荷强度(W/㎡),72.2,80.5,88.6,98.6,106.7,112.9,115.3,115.8,116.5,118.9,107.3,75.6,56.3
,散射负荷强度(W/㎡),45.2,62.5,78,91.3,101.1,108.3,111.5,110.7,104,92.7,75.2,56.9,46.1
,直射负荷(W),1040,1159,1276,0,0,0,1660,1667,1678,1712,1546,0,0
,散射负荷(W),0,0,0,1314,1456,1560,0,0,0,0,0,819,664
,总辐射负荷(W),1040,1159,1276,1314,1456,1560,1660,1667,1678,1712,1546,819,664
,温差传热负荷(W),239,273,304,337,369,396,414,422,416,413,395,367,338
外门[北],总冷负荷(W),113,124,128,134,141,147,150,154,159,160,152,129,112
,辐射照度(W/㎡),201.5,192.6,167.6,177.9,179.4,177.9,167.6,192.6,201.5,188.4,95.1,0,0
,负荷温差(℃),8.5,9.7,10.2,10.8,11.6,12.3,12.6,13.1,13.6,13.7,12.9,10.3,8.4
外墙[南],总冷负荷(W),259,247,236,227,222,222,226,234,247,263,279,296,312
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外墙[东],总冷负荷(W),285,270,260,260,271,292,318,345,370,391,407,420,427
,辐射照度(W),626,638,536,374,179,178,166,147,114,79,29,0,0
,负荷温差(℃),8.9,8.4,8.1,8.1,8.5,9.1,9.9,10.8,11.6,12.2,12.7,13.1,13.3
"1004[包间,3]",,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,包间,29,25,50,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,20.3,静坐,0.89,人员_宾馆建筑_全年,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,609,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,0,人员_宾馆建筑_全年,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,580,人员_宾馆建筑_全年,,,,,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),4.2,5.4,22.68,4.68,,,,,,,
外窗[南],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[南],南,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),4.2,5.4,22.68,20.88,,,,,,,
外门[北],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[北],北,节能外门,0.9,2,1.8,,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),1358,1097,1044,1030,1020,1013,1007,1002,998,995,992,1252,1303
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),839,727,674,659,650,642,637,632,628,625,622,733,785
,潜热负荷(W),519,370,370,370,370,370,370,370,370,370,370,519,519
,湿负荷(kg/h),0.771,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.771,0.771
新风[冷],总冷负荷(W),7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492
,显热负荷(W),1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533
,潜热负荷(W),5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959
,湿负荷(kg/h),8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533
,新风机组潜热负荷(W),5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959
,新风机组负荷(W),7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492
,新风机组湿负荷(kg/h),8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325
设备,总冷负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
灯光,总冷负荷(W),402,362,329,320,314,310,307,304,302,300,298,338,370
外墙[南],总冷负荷(W),24,23,21,21,20,20,21,21,23,24,25,27,28
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外窗[南],总冷负荷(W),889,1174,1427,1662,1825,1989,2020,2016,1913,1747,1477,1186,1001
,负荷温差(℃),4,4.6,5.1,5.7,6.2,6.7,7,7.1,7,7,6.7,6.2,5.7
,直射面积(㎡),0,0,0,18,0,18,0,0,0,0,0,0,0
,散射面积(㎡),18,18,18,18,18,18,18,18,18,18,18,18,18
,直射辐射照度(W),0,0,0,3,5,3,0,0,0,0,0,0,0
,散射辐射照度(W),94,121,136,146,148,146,136,121,94,65,24,0,0
,直射负荷强度(W/㎡),45.2,62.6,78,92,103.3,110.6,112.8,111.4,104.4,93,75.5,57.1,46.3
,散射负荷强度(W/㎡),45.2,62.5,78,91.3,101.1,108.3,111.5,110.7,104,92.7,75.2,56.9,46.1
,直射负荷(W),0,0,0,1325,0,1593,0,0,0,0,0,0,0
,散射负荷(W),650,900,1123,0,1456,0,1606,1594,1497,1334,1082,819,664
,总辐射负荷(W),650,900,1123,1325,1456,1593,1606,1594,1497,1334,1082,819,664
,温差传热负荷(W),239,273,304,337,369,396,414,422,416,413,395,367,338
外墙[北],总冷负荷(W),115,110,105,102,102,103,105,109,114,119,125,132,138
,辐射照度(W),201,193,168,178,179,178,168,193,201,188,95,0,0
,负荷温差(℃),7.8,7.4,7.1,6.9,6.9,7,7.1,7.4,7.7,8.1,8.5,8.9,9.4
外门[北],总冷负荷(W),85,91,94,97,101,105,107,109,112,113,108,94,84
,辐射照度(W/㎡),201.5,192.6,167.6,177.9,179.4,177.9,167.6,192.6,201.5,188.4,95.1,0,0
,负荷温差(℃),8.5,9.7,10.2,10.8,11.6,12.3,12.6,13.1,13.6,13.7,12.9,10.3,8.4
1005[包间],,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,包间,29,25,50,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,20.3,静坐,0.89,人员_宾馆建筑_全年,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,609,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,0,人员_宾馆建筑_全年,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,580,人员_宾馆建筑_全年,,,,,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),4.2,5.4,22.68,4.68,,,,,,,
外窗[南],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[南],南,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),4.2,5.4,22.68,20.88,,,,,,,
外门[北],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[北],北,节能外门,0.9,2,1.8,,,,,,,,
外墙[东],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[东],东,混凝土加气混凝土280(087001),8.4,5.4,45.36,45.36,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),1358,1097,1044,1030,1020,1013,1007,1002,998,995,992,1252,1303
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),839,727,674,659,650,642,637,632,628,625,622,733,785
,潜热负荷(W),519,370,370,370,370,370,370,370,370,370,370,519,519
,湿负荷(kg/h),0.771,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.551,0.771,0.771
新风[冷],总冷负荷(W),7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492
,显热负荷(W),1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533
,潜热负荷(W),5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959
,湿负荷(kg/h),8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533,1533
,新风机组潜热负荷(W),5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959,5959
,新风机组负荷(W),7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492,7492
,新风机组湿负荷(kg/h),8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325,8.325
设备,总冷负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
灯光,总冷负荷(W),402,362,329,320,314,310,307,304,302,300,298,338,370
外墙[南],总冷负荷(W),24,23,21,21,20,20,21,21,23,24,25,27,28
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外窗[南],总冷负荷(W),889,1174,1427,1662,1825,1989,2020,2016,1913,1747,1477,1186,1001
,负荷温差(℃),4,4.6,5.1,5.7,6.2,6.7,7,7.1,7,7,6.7,6.2,5.7
,直射面积(㎡),0,0,0,18,0,18,0,0,0,0,0,0,0
,散射面积(㎡),18,18,18,18,18,18,18,18,18,18,18,18,18
,直射辐射照度(W),0,0,0,3,5,3,0,0,0,0,0,0,0
,散射辐射照度(W),94,121,136,146,148,146,136,121,94,65,24,0,0
,直射负荷强度(W/㎡),45.2,62.6,78,92,103.3,110.6,112.8,111.4,104.4,93,75.5,57.1,46.3
,散射负荷强度(W/㎡),45.2,62.5,78,91.3,101.1,108.3,111.5,110.7,104,92.7,75.2,56.9,46.1
,直射负荷(W),0,0,0,1325,0,1593,0,0,0,0,0,0,0
,散射负荷(W),650,900,1123,0,1456,0,1606,1594,1497,1334,1082,819,664
,总辐射负荷(W),650,900,1123,1325,1456,1593,1606,1594,1497,1334,1082,819,664
,温差传热负荷(W),239,273,304,337,369,396,414,422,416,413,395,367,338
外墙[北],总冷负荷(W),115,110,105,102,102,103,105,109,114,119,125,132,138
,辐射照度(W),201,193,168,178,179,178,168,193,201,188,95,0,0
,负荷温差(℃),7.8,7.4,7.1,6.9,6.9,7,7.1,7.4,7.7,8.1,8.5,8.9,9.4
外门[北],总冷负荷(W),85,91,94,97,101,105,107,109,112,113,108,94,84
,辐射照度(W/㎡),201.5,192.6,167.6,177.9,179.4,177.9,167.6,192.6,201.5,188.4,95.1,0,0
,负荷温差(℃),8.5,9.7,10.2,10.8,11.6,12.3,12.6,13.1,13.6,13.7,12.9,10.3,8.4
外墙[东],总冷负荷(W),285,270,260,260,271,292,318,345,370,391,407,420,427
,辐射照度(W),626,638,536,374,179,178,166,147,114,79,29,0,0
,负荷温差(℃),8.9,8.4,8.1,8.1,8.5,9.1,9.9,10.8,11.6,12.2,12.7,13.1,13.3
1006[会议室],,,,,,,,,,,,,,
基本参数,房间名称,房间面积(㎡),夏季设计温度(℃),夏季相对湿度(%),,,,,,,,,,
,会议室,48.2,25,65,,,,,,,,,,
人体,人数,劳动强度,群集系数,时间指派,,,,,,,,,,
,48.2,静坐,0.89,人员_宾馆建筑_全年,,,,,,,,,,
新风[冷],新风量(m^3),新风负荷类型,计算方法,新风机组处理状态,热回收类型,时间指派,,,,,,,,
,1446,新风冷负荷,稳态计算,处理到室内点状态,不考虑热回收过程,默认时间,,,,,,,,
设备,设备类型,设备功率(KW),时间指派,,,,,,,,,,,
,电子设备,0.24,人员_宾馆建筑_全年,,,,,,,,,,,
灯光,灯光类型,安装功率(W),时间指派,,,,,,,,,,,
,白炽灯,964,人员_宾馆建筑_全年,,,,,,,,,,,
外墙[南],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[南],南,混凝土加气混凝土280(087001),8.4,5.4,45.36,27.36,,,,,,,
外窗[南],外窗名称,外窗朝向,外窗围护结构,外窗长度(m),外窗宽度(m),外窗面积(㎡),遮阳类型,,,,,,,
,外窗[南],南,断热铝合金普通中空玻璃窗,4,4.5,18,无遮阳设施,,,,,,,
外墙[北],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[北],北,混凝土加气混凝土280(087001),8.4,5.4,45.36,43.56,,,,,,,
外门[北],外门名称,外门朝向,外门围护结构,外门长度(m),外门宽度(m),外门面积(㎡),,,,,,,,
,外门[北],北,节能外门,0.9,2,1.8,,,,,,,,
外墙[东],外墙名称,外墙朝向,外墙围护结构,外墙长度(m),外墙宽度(m),外墙面积(㎡),外墙净面积(㎡),,,,,,,
,外墙[东],东,混凝土加气混凝土280(087001),8.4,5.4,45.36,45.36,,,,,,,
时间,,8:00,9:00,10:00,11:00,12:00,13:00,14:00,15:00,16:00,17:00,18:00,19:00,20:00
人体,总冷负荷(W),3224,2605,2480,2445,2422,2405,2391,2380,2370,2362,2356,2972,3094
,成人显热量(W),67,67,67,67,67,67,67,67,67,67,67,67,67
,成人潜热量(W),41,41,41,41,41,41,41,41,41,41,41,41,41
,成人散湿量(g/h),61,61,61,61,61,61,61,61,61,61,61,61,61
,显热负荷(W),1993,1725,1601,1566,1543,1525,1512,1500,1491,1483,1476,1741,1863
,潜热负荷(W),1231,879,879,879,879,879,879,879,879,879,879,1231,1231
,湿负荷(kg/h),1.832,1.308,1.308,1.308,1.308,1.308,1.308,1.308,1.308,1.308,1.308,1.832,1.832
新风[冷],总冷负荷(W),14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224
,显热负荷(W),3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641
,潜热负荷(W),10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583
,湿负荷(kg/h),14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727
,新风承担房间显热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间潜热负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间负荷(W),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风承担房间湿负荷(kg/h),0,0,0,0,0,0,0,0,0,0,0,0,0
,新风机组显热负荷(W),3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641,3641
,新风机组潜热负荷(W),10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583,10583
,新风机组负荷(W),14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224,14224
,新风机组湿负荷(kg/h),14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727,14.727
设备,总冷负荷(W),84,66,63,63,62,62,62,62,61,61,61,79,82
灯光,总冷负荷(W),668,601,546,532,522,515,510,505,501,498,496,562,616
外墙[南],总冷负荷(W),138,132,126,121,118,118,120,125,132,140,149,158,166
,辐射照度(W),114,147,166,206,218,206,166,147,114,79,29,0,0
,负荷温差(℃),7.2,6.8,6.5,6.3,6.1,6.1,6.2,6.5,6.8,7.3,7.7,8.2,8.6
外窗[南],总冷负荷(W),889,1174,1427,1662,1825,198
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 版企业培训合作合同
- 运动自行车品牌代理合同
- 新疆沙雅县市级名校2025届初三下学期英语试题分类汇编含答案
- 五金制品锯类购销协议
- 小型企业劳动合同模板
- 土地使用权买卖合同模板范本
- 商场店铺租赁合同范本
- 冀教版小学数学六年级下册小升初毕业会考模拟卷(三) (含答案)
- 2025年云南省曲靖市沾益区民族中学中考历史一模试卷(含答案)
- 智能设备服务合同
- 住院医师规范化培训教学查房课件
- 2022-2023学年天津市部分区八年级(下)期中物理试卷(含解析)
- 酒精计法测定酒精中酒精度
- 婴幼儿语言发育筛查量表
- 川教版生命生态安全一年级上册第12课 做一个受欢迎的人 教学设计
- 油气输送管道高后果区识别与评价释义
- 高价值专利挖掘布局
- 托业考试TOEIC词汇汇总
- DL-T 736-2021 农村电网剩余电流动作保护器安装运行规程
- SB/T 10439-2007酱腌菜
- FZ/T 62034-2016磁性软纱门
评论
0/150
提交评论