.@:建筑给排水工程毕业设计----江苏建委综合楼中文摘要本文主要为超高层办公楼给水排水设施和消防系统的设计。其中,给水系统为分区供水,高区采用水箱供水,为上行下给式,中区采用水泵直接加压供水,低区由市政管网直接供水;建筑内部生活污水采用合流制排出;室内消防设计按一类高层建筑设计,自喷采用面积作用法计算,按中危险级设计;屋面雨水采用外排水方式。关键词办公楼给排水消防系统设计毕业设计ABSTRACTThisarticlemainlyshowsdesignwatersupplyanddrainagedesigninaofficialoccupancybuilding.Inthiswatersupplysystemsupplieswatertohighregionandlowpart,thehighleveltanksupplysystemofhighregion,submittohigherauthoritallthehighregion,municipalwaterdistributionsystemdirectsupplylowpart;livedrainagedischargeadoptflowtogetherinabuilding;accordingtothehigh-riseⅠtypedesigningtheinteriorfirepreventionsystem;automaticwatersprinklersystemcalculateofarea,adoptmediumperilousⅡ;Therainfallpipesareprovidedtoallowrainwatertorunawayfromthehouse.KEYWORDS:Aofficialbuildingwatersupplyanddrainagefirefightsystemdesi第一章设计说明书第一节给排水系统总体规划设计及方案比较1.给水系统该建筑给水水源来自城市自来水,建筑外有市政给水干管。从该给水干管上引两条引入管,一条引向住宅地下层贮水池;另一条引向低区,引入管上均设置水表。2.消防系统消防贮水池设置在地下设备层,供给消火栓和自动喷水灭火系统的用水。由《高层民用建筑设计防火规范》规定,应确保消防用水量的技术措施,如在设计中采用屋顶消防水箱和楼中间消防水箱供给消防时前10分钟的用水量,10分钟后由消防水泵启动供水。3.排水系统(1)市政排水管网为雨水和污水分流制,所以建筑也采用分流制,雨水由雨水口收集后,有组织地排向城市雨水管网。(2)办公楼的污水立管不能直接通向底层,所以立管均在设备层和一层地下内汇集到几根立管内再通向一层地下排出室外。污水排出室外后,直接排入市政污水管。4.热水系统该建筑内设置集中供热设施,七层以上设有开水房为办公人员提供饮用水,在五层与二十二层设有淋浴间。5.设计方案比较5.1给水系统方案比较及确定5.1.1不同方案的列举方案一:由于城市的市政管网压力在该处的压力为28米水柱,地下二层至四层的给水系统可以由市政管网直接供水,作为给水系统的低区。五层至二十=2\*CHINESENUM3二层通过二十=2\*CHINESENUM3二层设备层的水箱,采用上行下引的方式供水,作为给水系统的中区,但由于在此高度下,第四层的静水压力超出了0.45Mpa,所以在第六层的楼顶设置减压阀,以减小下面几层的用水水压,作为给水系统的中区。二十三层至三十二层通过三十三层的设备层水箱,采用上行下给的方式供水,作为给水系统的高区。其给水的系统图见图1.1.1。方案二:地下二层~四层由城市市政管网直接供水,五层~十六层由变频泵供水,并采用上行下给的供水方式。在第八层设置减压阀,用来减小下面几层的用水压力,达到用水舒适的目的。十七层~三十二层由水箱供水,二十八层设置减压阀。其给水的系统图见图1.1.2。图.2。方案三:地下二层~四层由城市市政管网直接供水,作为系统的低区。五层~十一层由变频泵供水,十二层`十八层由变频泵供水,这两个区作为系统的中区,分为A,B两个小区。十九层~二十五层由二十六层的水箱供水,采用上行下给式。二十六层~三十二层由三十三层的水箱供水,采用上行下给式。该系统的给水系统见图1.1.3A,B,C图1.1.3A图1.1.3B图1.1.3C5.1.2方案的比较根据以上列举的各个方案进行技术上和经济上的比较,选出一个相对比较优化的方案作为该综合楼给水系统的设计方案。6.方案确定综合上述三种方案在技术上和经济上的优点和缺点及本地区的实际情况,现确定方案三为该综合楼的给水系统的设计方案。表2.1.1给水系统方案比较比较方案优点缺点方案一1一~四层由市政管网直接供水,节能;;2建设费用和维修费用较小。四至二十一层和二十二层至三十二层由泵一次提升,减压阀减压供水,比较浪费电能,但水质不好。方案二1采用水箱供水和水泵供水;2设备与管材较少,布置集中,不占用水箱间的面积;3投资建设费用小。1通过变频泵提升的水经减压阀减压,浪费能源;2泵的启动比较频繁。方案三1高中区均采用水箱供水,水压稳定;2在短时间断电的情况下,不会发生缺水现象。由于是超高层应保证水量。3供水可靠性强、安全;1全楼的供水均经过泵的提升,浪费能源。2在设备层内设置水箱,对该层的结构提出了一定的要求。第二节消火栓系统方案比较及确定该综合楼的总高度为128m,其中三十三层楼顶的高度为123m。按照规范的要求,消防系统中的最大静水压力为0.8MPa。因此,该楼的消火栓给水系统要分区。连接系统中立管的横管可分别在地下一层,二十二层和三十三层的楼内。屋顶和二十二层设备层内设置一个消防水箱,储存前十分钟的用水量。该消防的系统图见图1.3.1。图1.3.11系统分为两个区,有高区和低区。高区和低区都采用水箱,上行下给式。如图1.3.1,高区和低区大致相同。高区:19层~33层;低区:地下二层~18层。由于离水箱近的消火栓压力不够,所以在水箱出水管上设置水泵和气压罐,保证出水压力。供水方法:地下二层设有消防泵组,供给二十二层的消防水箱。在二十二层设置另一组消防泵,从二十二层水箱取水,供给三十三层的消防水箱。这样串联供水方式,比较节能,由于消防泵只在产生火灾时启用,所以一般生活时间不会产生噪音。消火栓内应设置远距离启动消火栓的按钮,以便在使用消火栓灭火的同时启动消火栓。2自喷系统方案比较及确定在自喷系统中,一个报警阀控制的最高和最低的喷头的静水压力为0.5Ma。而且,一个湿式报警阀控制的喷头数为800个,干式为500个。按照上述的要求,可以将其分成若干个区分别进行控制,而且要满足以上要求。屋顶的消防水箱同时满足消火栓和自喷前十分钟的用水量。十分钟后,其用水量由系统的消防泵供给。所以共分7个区,每个分区一个报警阀,低层六个区和高层一个区分别设置一个消防喷淋泵,保证高区喷淋出水安全。底区消防喷淋泵设置在地下二层消防泵房内,高区消防喷淋泵设置在二十二层设备层上。第三节排水系统方案比较及确定一层的污水先收集到集水坑中,然后用污水泵将其抽至室外排水管网中。每一层的公共卫生间的排水采用两根立管排放,为增加排水的安全性,群楼和高层的排水单独排放。为使排水顺畅,设置通气立管。各层的排水先汇合到地下一层的排水横管中,最后单独排放至室外的排水管网中。第四节各系统具体说明4.1给水系统说明该建筑主体33层,建筑高度129.8m,属一类建筑。由于建筑设计中,已有设置高位水箱的设备层,所以由水箱供水和水泵直接供水都予以考虑。其生活给水系统应分区,因为当建筑物高度很高时,如果给水系统只采用一个区供水,则下层的给水压力过大,会带来许多不利之处:1)龙头开启,水成射流喷溅,影响使用;2)必须采用耐高压管材、零件及配水器材,否则容易破裂;3)由于压力过高,龙头、阀门、浮球阀等器材磨损迅速,寿命缩短,漏水增加,检修频繁,增大工作量;4)下层龙头的流出水头过大,如果不采取减压措施,其流出量比设计流量大得多,使管道内流速增加,以至产生流水噪音,并使顶层龙头产生负压抽吸现象,形成回流污染;5)由于压力过大,容易产生水锤及水锤噪音;6)维修管理费用和水泵运转电费增高。综合以上因素,结合本建筑的实际情况,采取竖向分区,采用方案三。具体形式如下:D、E区采用水泵-水箱联合供水方式,通过减压阀垂直串联分区供水;B、C区采用变频水泵(气压罐辅助)供水;地下区A采用市政管网直接供水。

高区E区,三十三层设备间设置水箱,=26\*CHINESENUM3二十六层至三十=2\*CHINESENUM3二层高差25.6米,区域最高压力点处的压力0.32MPa,静水压力小于35米。。

高区D区,二十六层备用间内设置水箱,二十五层至十九层高差25.2米,区域最高压力点处的压力0.32MPa,静水压力小于35米。

中区C区,十二层至十八层高差25.2米,区域最高压力点处的压力0.35MPa。

中区B区,五层至十一层高差25.6米,区域最高压力点处的压力0.40MPa。

低区,地下负二层至地上四层,市政管网供水28m,采用市政管网直接供水。分区特点:1)水质保证:城市管网供水水质符合饮用水标准,由屋顶和设备层的水箱供水,设计水在水箱内停留时间不超过24小时,故可以满足水质要求;采用水泵输送,也可以满足要求。2)水压保证:水泵水箱联合供水可以保证水压及用户用水的舒适度,由于高差不大,所以水泵直接供水也可保证水压。3)可靠性:楼内的给水系统相互独立,如果某一个分区出现故障不会影响其他分区的用水,可靠性较高。4)技术经济:运行维护方便,节省运营费用及电费。4.2消防给水系统说明根据《高层民用建筑设计防火规范》规定:消火栓处的静水压不应大于80米水柱,如超过80米水柱时,应采取分区给水或在消火栓处设减压设施。本建筑消火栓处的静水压力超过80米,为安全起见采取分区给水形式,具体如下:高区:19层至33层,由地下消防贮水池――消防水泵――消防水箱联合供水,消防水泵启动前由屋顶水箱供水低区:地下二层到18层,由二十二层的设备层内的水箱供水,但由于高差较大,所以在十层以下采用减压后供给。供水方式是上行下给,消防水泵串联供水,如图4.2.1。自动喷淋分区根据喷头数量。设置地下二层为一区,由于地下为人防和车库,是火灾的重要发生地点,所以地下二层为一区。地下一层与二层为一区;三层至五层为一区;六层至十二层为一区;十三区至十八层为一区;十九层至二十四层为一区;以上六区用一个消防自喷泵,设置在地下二层的消防泵房。二十四层至三十三层为一区,这个区用一个自喷泵,辅泵设置在二十二层一个,主泵设置在地下二层。由于二十四层以上比较高,一般室内外消防设施要求很高,在外界灭火困难时,楼内自救很重要,所以为了保证自喷水量和水压的充足,我单独设高区一个自喷系统。和消火栓系统一样水泵串联供水。4.3排水系统说明4.3.1污水系统由于该建筑地处江苏省,污水管网较为完善,故污水可方便的排入市政污水干管。办公楼内的卫生间原则上是分别设置一根排水立管,但是在20-21层个别办公室内的套间里的卫生间,可以只由横贯管引到公共卫生间的立管排除即可,具体见办公楼卫生间给排水详图。楼内的排水立管向上伸出屋面作伸顶通气,由于屋顶上要上人,故伸顶通气管比屋面高2米。住宅的污水立管不能直接通向底层,所以立管均在一层地下由横干管汇集到几根立管内再通向地下一层排出室外,高区的排水立管需要设置专用伸顶通气。。地下室内的污水汇集至集水坑内(其中消防电梯下和水泵间的集水坑设计流量较大),然后由潜污泵提升后排入排水干管内,再汇入城市污水管网内图.2雨水系统屋面雨水排水系统采用重力流普通外排水。楼屋面的雨水通过雨水斗收集后由雨水立管在地下一层吊顶内汇集到几根排出管内从一层排至室外散水。顶层屋顶和裙楼屋顶的雨水分别设置几个雨水斗及雨水立管排除。图热水系统说明该建筑没有设置集中供热设施,故住宅用热水由住户设热水器或壁挂锅炉自行解决。设计中预留出热水器位置,以及热水管道,详见卫生间及开水间详图。第二章设计计算书第一节给水系统计算书2.1给水系统设计计算2.1.1总用水量的计算依建筑物的性质和室内卫生设备的完善程度,确定办公楼类型为=1\*ROMANI类,每6平方米按1人计。因办公楼内的户型较小,用水定额取50L/人·d,时变化系数’=1.2。用水时间:T’=8h。由于1层-4层没有固定的办公室,所以采用办公室占总面积的60%,总人数=452+545+623+566+410.4+184+140+184人。按照建筑给水排水设计规范(GB50015-2003)进行计算各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班31048.01.20155.2023.2819.40总计如下未预见水量百分比:20%最大日用水量:186.24(立方米)最大时用水量:27.94(立方米)平均时用水量:23.28(立方米)2.1.2各分区最高日最大时用水量计算最高日用水量高区A(32~26层):各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班4528.01.2022.603.392.83总计如下未预见水量百分比:20%最大日用水量:27.12(立方米)最大时用水量:4.07(立方米)平均时用水量:3.39(立方米)高区B(25~19层)各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班5458.01.2027.254.093.41总计如下未预见水量百分比:20%最大日用水量:32.70(立方米)最大时用水量:4.90(立方米)平均时用水量:4.09(立方米)中区B(12~18层)各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班6238.01.2031.154.673.89总计如下未预见水量百分比:20%最大日用水量:37.38(立方米)最大时用水量:5.61(立方米)平均时用水量:4.67(立方米)中区A(11~5层)各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班5668.01.2028.304.253.54总计如下未预见水量百分比:20%最大日用水量:33.96(立方米)最大时用水量:5.09(立方米)平均时用水量:4.25(立方米)低区(1~4层)各用水部位统计结果如下用水部位用水标准单位数量用水时间变化系数最大日最大时平均时办公楼50.00L/人·班9188.01.2045.906.885.74总计如下未预见水量百分比:20%最大日用水量:55.08(立方米)最大时用水量:8.26(立方米)平均时用水量:6.88(立方米)2.1.3各分区给水管网水力计算1、低区水力计算:地区(地下2层-4层)由于地下2层没有卫生间,无用水。由《技术措施》查得,设计秒流量公式为式中:——计算管段的给水设计秒流量,L/s;——根据建筑用途而定的系数,查得商场系数为1.5;——计算管段的卫生器具给水当量总数。低区计算草图如下:一层;采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α式中:Q-计算管段的给水设计秒流量(L/s)Ng-计算管段的卫生器具给水当量总数α-根据建筑物用途而定的系数:1.5建筑类型:办公楼、商场计算结果:管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.100.800.50200.0300.540.02PP-R2-30.200.461.00250.0350.680.04PP-R3-40.201.891.00250.0350.680.11PP-R4-50.202.981.00250.0350.680.21PP-R5-60.202.751.00250.0350.680.31PP-R6-70.200.381.00250.0350.680.32PP-R7-81.400.391.50500.0441.180.34PP-R8-91.401.601.50500.0441.180.41PP-R9-101.400.161.50500.0441.180.42PP-R10-111.400.601.50500.0441.180.44PP-R11-121.500.322.00500.0501.270.46PP-R12-131.500.162.00500.0501.270.47PP-R13-141.501.552.00500.0501.270.54PP-R14-151.501.002.00500.0501.270.59PP-R15-161.570.522.50500.0551.330.62PP-R16-171.572.702.50500.0551.330.77PP-R17-181.570.392.50500.0551.330.79PP-R18-191.702.604.00500.0631.440.95PP-R19-201.742.754.50500.0661.471.14PP-R20-211.740.894.50500.0661.471.19PP-R21-221.770.605.00500.0681.501.23PP-R22-231.771.605.00500.0681.501.34PP-R23-241.770.085.00500.0681.501.35PP-R24-251.770.395.00500.0681.501.37PP-R25-261.800.345.50630.0230.961.38PP-R26-271.801.155.50630.0230.961.41PP-R27-281.860.086.50630.0241.001.41PP-R28-291.862.706.50630.0241.001.48PP-R29-301.860.796.50630.0241.001.50PP-R30-311.890.817.00630.0251.011.52PP-R31-321.892.707.00630.0251.011.58PP-R32-331.890.147.00630.0251.011.59PP-R33-341.890.507.00630.0251.011.60PP-R34-351.893.007.00630.0251.011.68PP-R36-371.200.380.50500.0331.010.01PP-R37-381.201.600.50500.0331.010.05PP-R38-391.200.080.50500.0331.010.00PP-R39-401.200.610.50500.0331.010.02PP-R40-411.301.001.00500.0381.100.04PP-R41-421.400.841.50500.0441.180.04PP-R42-181.401.151.50500.0441.180.05PP-R43-440.100.400.50200.0300.540.01PP-R44-450.102.700.50200.0300.540.08PP-R45-190.101.690.50200.0300.540.05PP-R46-260.001.550.0000.0000.000.00PP-R47-480.100.800.50200.0300.540.02PP-R二层:采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α计算结果:管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.100.800.50200.0300.540.02PP-R2-30.200.501.00250.0350.680.04PP-R3-40.301.891.50250.0741.010.18PP-R4-50.302.711.50250.0741.010.38PP-R5-60.470.502.50320.0530.980.41PP-R6-71.700.504.00500.0631.440.44PP-R7-81.703.004.00500.0631.440.63PP-R9-30.100.300.50200.0300.540.01PP-R10-110.100.800.50200.0300.540.02PP-R11-120.200.561.00250.0350.680.02PP-R12-130.202.701.00250.0350.680.09PP-R13-0250.0350.680.00PP-R14-50.200.571.00250.0350.680.02PP-R15-161.200.900.50500.0331.010.03PP-R16-171.300.901.00500.0381.100.03PP-R17-181.400.321.50500.0441.180.01PP-R18-191.401.151.50500.0441.180.05PP-R19-61.400.411.50500.0441.180.02PP-R20-70.000.600.0000.0000.000.00PP-R三层:采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α式中:Q-计算管段的给水设计秒流量(L/s)Ng-计算管段的卫生器具给水当量总数α-根据建筑物用途而定的系数:1.5建筑类型:办公楼、商场计算结果:管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.100.800.50200.0300.540.02PP-R2-30.200.501.00250.0350.680.04PP-R3-40.301.891.50250.0741.010.18PP-R4-50.302.711.50250.0741.010.38PP-R5-60.470.502.50320.0530.980.41PP-R6-71.700.504.00500.0631.440.44PP-R7-81.703.004.00500.0631.440.63PP-R9-30.100.300.50200.0300.540.01PP-R10-110.100.800.50200.0300.540.02PP-R11-120.200.561.00250.0350.680.02PP-R12-130.202.701.00250.0350.680.09PP-R13-0250.0350.680.00PP-R14-50.200.571.00250.0350.680.02PP-R15-161.200.900.50500.0331.010.03PP-R16-171.300.901.00500.0381.100.03PP-R17-181.400.321.50500.0441.180.01PP-R18-191.401.151.50500.0441.180.05PP-R19-61.400.411.50500.0441.180.02PP-R20-70.000.600.0000.0000.000.00PP-R四层:采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α计算结果:管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.100.800.50200.0300.540.02PP-R2-30.200.611.00250.0350.680.05PP-R3-40.202.701.00250.0350.680.14PP-R4-0250.0350.680.14PP-R5-60.200.471.00250.0350.680.16PP-R6-71.574.102.50500.0551.330.38PP-R7-81.660.473.50500.0601.410.41PP-R8-91.770.455.00500.0681.500.44PP-R9-101.950.538.00630.0271.040.46PP-R11-121.200.900.50500.0331.010.03PP-R12-131.300.901.00500.0381.100.03PP-R13-141.400.351.50500.0441.180.02PP-R14-151.401.151.50500.0441.180.05PP-R15-61.400.071.50500.0441.180.00PP-R16-171.200.900.50500.0331.010.03PP-R17-181.300.351.00500.0381.100.01PP-R18-71.301.151.00500.0381.100.04PP-R19-201.200.900.50500.0331.010.03PP-R20-211.300.901.00500.0381.100.03PP-R21-221.400.351.50500.0441.180.02PP-R22-81.401.151.50500.0441.180.05PP-R23-240.100.800.50200.0300.540.02PP-R24-250.200.801.00250.0350.680.03PP-R25-260.300.341.50250.0741.010.03PP-R26-270.401.892.00320.0380.830.07PP-R27-280.400.182.00320.0380.830.01PP-R28-290.400.202.00320.0380.830.01PP-R29-300.401.822.00320.0380.830.07PP-R30-90.520.603.00320.0621.080.04PP-R31-260.100.460.50200.0300.540.01PP-R32-330.100.800.50200.0300.540.02PP-R33-340.200.701.00250.0350.680.02PP-R34-350.202.701.00250.0350.680.09PP-R35-30250.0350.680.01PP-R36-300.200.391.00250.0350.680.01PP-R计算原则:(1)如果计算值小于该管段上最大的卫生器具额定流量时,按最大的一个卫生器具得额定流量作为设计秒流量;(2)如果计算值大于该管段上所有卫生器具额定流量总和时,按额定流量总和作为设计秒流量。说明:低区四层内用水的地方,全是公用卫生间,采用当量法计算。中区计算:中区(A:5层-11层;B:12层-18层)由《技术措施》查得,设计秒流量公式为式中:——计算管段的给水设计秒流量,L/s;——根据建筑用途而定的系数,查得商场系数为1.5;——计算管段的卫生器具给水当量总数。五层:采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.000.580.0000.0000.000.00PP-R2-30.101.000.50200.0300.540.03PP-R3-40.200.771.00250.0350.680.06PP-R4-0250.0350.680.13PP-R5-0250.0350.680.24PP-R6-70.201.891.00250.0350.680.31PP-R7-80.200.571.00250.0350.680.33PP-R8-90.300.801.50250.0741.010.39PP-R9-100.400.802.00320.0380.830.42PP-R10-110.470.292.50320.0530.980.44PP-R11-120.470.052.50320.0530.980.44PP-R12-130.470.822.50320.0530.980.48PP-R13-140.471.282.50320.0530.980.55PP-R14-150.521.053.00320.0621.080.61PP-R15-160.560.223.50320.0721.160.63PP-R16-170.562.703.50320.0721.160.82PP-R17-180.560.183.50320.0721.160.84PP-R18-190.562.773.50320.0721.161.04PP-R19-201.868.136.50630.0241.001.23PP-R20-211.865.046.50630.0241.001.36PP-R21-221.863.186.50630.0241.001.44PP-R22-232.240.5314.50630.0341.201.45PP-R24-250.100.700.50200.0300.540.02PP-R25-260.200.531.00250.0350.680.02PP-R26-270.201.551.00250.0350.680.05PP-R27-281.501.152.00500.0501.270.06PP-R28-291.502.392.00500.0501.270.12PP-R29-191.625.043.00500.0581.370.29PP-R30-310.100.800.50200.0300.540.02PP-R31-320.200.611.00250.0350.680.02PP-R32-330.202.701.00250.0350.680.09PP-R33-30250.0350.680.00PP-R34-350.200.471.00250.0350.680.02PP-R35-361.574.102.50500.0551.330.22PP-R36-371.660.473.50500.0601.410.03PP-R37-221.770.455.00500.0681.500.03PP-R38-390.100.800.50200.0300.540.02PP-R39-400.200.801.00250.0350.680.03PP-R40-410.300.341.50250.0741.010.03PP-R41-420.401.892.00320.0380.830.07PP-R42-430.400.182.00320.0380.830.01PP-R43-440.400.202.00320.0380.830.01PP-R44-450.401.822.00320.0380.830.07PP-R45-220.520.603.00320.0621.080.04PP-R46-471.201.000.50500.0331.010.03PP-R47-271.300.641.00500.0381.100.02PP-R48-490.101.000.50200.0300.540.03PP-R49-500.200.421.00250.0350.680.01PP-R50-50250.0350.680.07PP-R51-520.200.261.00250.0350.680.01PP-R52-50250.0350.680.01PP-R53-290.202.001.00250.0350.680.07PP-R54-551.200.900.50500.0331.010.03PP-R55-561.300.901.00500.0381.100.03PP-R56-571.400.351.50500.0441.180.02PP-R57-581.401.151.50500.0441.180.05PP-R58-351.400.071.50500.0441.180.00PP-R59-601.200.900.50500.0331.010.03PP-R60-611.300.351.00500.0381.100.01PP-R61-361.301.151.00500.0381.100.04PP-R62-631.200.900.50500.0331.010.03PP-R63-641.300.901.00500.0381.100.03PP-R64-651.400.351.50500.0441.180.02PP-R65-371.401.151.50500.0441.180.05PP-R66-410.100.460.50200.0300.540.01PP-R67-680.100.800.50200.0300.540.02PP-R68-690.200.701.00250.0350.680.02PP-R69-700.202.701.00250.0350.680.09PP-R70-70250.0350.680.01PP-R71-450.200.391.00250.0350.680.01PP-R六层:采用当量法计算计算原理参照《建筑给水排水设计规范GB50015-2003》,采用公共建筑采用当量法基本计算公式Q=0.2×SQRT(Ng)×α建筑类型:办公楼、商场计算结果:管段名称管道流量L/s管长m累计当量公称直径水力坡降mH2O/m流速m/s沿程损失mH2O管材1-20.100.680.50200.0300.540.02PP-R2-0200.0300.540.03PP-R3-40.100.080.50200.0300.540.03PP-R4-50.102.700.50200.0300.540.11PP-R5-60.102.880.50200.0300.540.20PP-R6-71.400.121.50500.0441.180.20PP-R7-81.570.382.50500.0551.330.22PP-R8-91.620.093.00500.0581.370.23PP-R9-101.660.403.50500.0601.410.25PP-R10-111.660.183.50500.0601.410.26PP-R11-121.662.103.50500.0601.410.39PP-R12-131.660.433.50500.0601.410.42PP-R13-141.701.004.00500.0631.440.48PP-R14-151.741.004.50500.0661.470.55PP-R16-50.000.200.0000.0000.000.00PP-R17-181.201.000.50500.0331.010.03PP-R18-191.300.371.00500.0381.100.01PP-R19-61.301.151.00500.0381.100.04PP-R20-210.001.000.0000.0000.000.00PP-R21-220.101.000.50200.0300.540.03PP-R22-230.200.421.00250.0350.680.01PP-R23-0250.0350.680.07PP-R24-0250.0350.680.01PP-R25-70.200.401.00250.0350.680.01PP-R26-270.001.150.0000.0000.000.00PP-R说明:中区和低区一样,都是公共卫生间。计算原则和低区一样。由于中区7层及7层以上卫生间基本相同,见草图。中区A,B两小区的用水主要部分是卫生间,由于用水不多,所以用泵直接供水便可满足。见下面的七层卫生间系统计算草图与中区系统供水计算草图。中区A,B计算系统草图7层卫生间计算草图高层计算:高层(B:19层-25层;A:26层-32层)说明;高区用水也主要是公共卫生间,但是在20-21层内有套间卫生间,再2层内有个公共淋浴间。供水计算和中,低区一样。其他楼层公共卫生间只有7层和29层卫生间两种类型的。29层卫生间计算草图20-21层套间卫生间系统图,根据当量法计算管径,横干管为DN50。20-21层套间卫生间与给水主立管相连,见给水系统图。22层公共淋浴间系统计算草图。高区系统计算草图2.1.4生活给水水池、水箱及水泵设计计算1地下水池容积计算由《技术措施》2.8.6“建筑物的生活用水贮水池的有效容积应按进水量变化曲线经计算确定,当资料不足时,宜按最高日用水量的20~25%确定。”则取25%为计算标准。V=×23%=186.24×25%=46.56取50,尺寸定为5m×4m×2.5m。2顶层屋顶水箱由《技术措施》2.8.8“建筑物的屋顶水箱的有效容积不宜小于最高日最大时用水量的一半”V=1/2×4.07=2.035,查《给排水标准图集》96S1,选用不锈钢水箱,公称容积为3,尺寸为2m×1.4m×1.4m。22层设备层水箱V=1/2×4.90=4.45,查《给排水标准图集》96S1,选用不锈钢水箱,公称容积为3,尺寸为2m×1.4m×1.4m。3高区A区生活泵水泵出水量按最大时用水量4.07(1.14)计算,由塑料管水力计算表查得:当水泵出水管流量为1.14时,水泵输水管径为32mm,流速V=1.13m/s,单阻i=0.044KPa/m;水泵吸水管管径为100mm,流速V=0.29m/s,单阻i=0.010KPa/m。计算草图如下:如图,可知输水管长165.4m,其沿程水头损失hy=0.044×165.4=0.73KPa,而吸水管的沿程水头损失hy=0.010×2=0.02KPa,故水泵管路总水头损失为(7.26+0.02)×1.3=9.45KPa。水箱最高水位与地下水池最低水位之差为:122.4―(―8)=120.4m由《设计手册第二册》得水泵扬程计算公式为:Hb=△H+Hl+Hξ+HfHb=9.45+(0.29×0.29/2/9.8)+120.4=130m所需扬程为:129m,流量4.07(1.13);选泵:40GDL6-12,扬程132M,流量1.67L/s;N=5.5KW设两台,一用一备。高区B区生活水泵水泵出水量按最大时用水量4.9(1.36)计算,由塑料管水力计算表查得:当水泵出水管流量为1.36时,水泵输水管径为32mm,流速V=1.38m/s,单阻i=0.062KPa/m;水泵吸水管管径为80mm,可知输水管长137.6m,其沿程水头损失hy=0.062×137.6=8.53KPa,而吸水管的沿程水头损失hy=0.062×2=0.12KPa,故水泵管路总水头损失为(8.53+0.12)×1.3=11.18KPa。水箱最高水位与地下水池最低水位之差为:95.6―(―8)=103.6m由《设计手册第二册》得水泵扬程计算公式为:Hb=△H+Hl+Hξ+HfHb103.4+(0.29×0.29/2/9.8)+11.18=115m所需扬程为:115m,流量4.9(1.36);选泵:40GDL6-12,扬程120M,流量1.36L/s;N=5.5KW设两台,一用一备。4中区生活水泵中区B区:采用给水变频泵组,自动控制。

水泵出水量按最大时用水量5.61(1.56)计算由塑料管水力计算表查得:当水泵出水管流量为1.56时,水泵输水管径为32mm,流速V=1.57m/s,单阻i=0.083KPa/m;水泵吸水管管径为100mm,流速V=0.29m/s,单阻i=0.010KPa/m。可知输水管长88.6m,其沿程水头损失hy=0.083×88.6=7.45KPa,而吸水管的沿程水头损失hy=0.083×2=0.16KPa,故水泵管路总水头损失为(7.45+0.16)×1.3=10.01KPa。最不利水龙头与地下水池最低水位之差为:66.8―(―8)=74.8m最不利水龙头压力5M。由《设计手册第二册》得水泵扬程计算公式为:Hb=△H+Hl+Hξ+HfHb74.8+(0.29×0.29/2/9.8)+10.01+5=90m所需扬程为:90,流量5.61(1.56);选泵:40MSL×10-5.5,扬程74-98M,流量1.5-3L/s;N=5.5KW设两台,一用一备。中区A区:采用给水变频泵组,自动控制。

水泵出水量按最大时用水量5.09(1.41)计算由塑料管水力计算表查得:当水泵出水管流量为1.41时,水泵输水管径为32mm,流速V=1.42m/s,单阻i=0.066KPa/m;水泵吸水管管径为100mm,流速V=0.29m/s,单阻i=0.010KPa/m。可知输水管长63.2m,其沿程水头损失hy=0.066×63.2=4.17KPa,而吸水管的沿程水头损失hy=0.066×2=0.16KPa,故水泵管路总水头损失为(4.17+0.13)×1.3=5.59KPa。最不利水龙头与地下水池最低水位之差为:43.2―(―8)=71.2m最不利水龙头压力5M。由《设计手册第二册》得水泵扬程计算公式为:Hb=△H+Hl+Hξ+HfHb71.2+(0.29×0.29/2/9.8)+4.17+5=81m所需扬程为:81,流量5.09(1.41);选泵:40MSL×9-5.5,扬程66.6-88.2M,流量1.5-3L/s;N=5.5KW设两台,一用一备。5、水池配水管的确定1)溢流管:管径比进水管大一级,且喇叭口下的垂直部分大于4倍的溢流管管径;2)进水管:从市政管网直接进水,管中的流速为1.0,流量为4.47,求得其管径为70mm;3)泄水管:按2h将水池内的水泄空进行计算,池子内的水量为V=50,流速为1.5,求得其直径为:50=1.5×0.25×××3600求得d=108mm,但管径一般不小于100mm,所以取125mm作为其管径,管内底和池底相平。4)通气管:管径采用100mm,用两根。人孔:人孔的尺寸为900mm×900mm的正方形人孔,设在进水的浮球阀处,人孔的一侧与池壁相平。孔口高出池顶100mm,孔盖密封并加锁。6、冷水水表的选择楼水表的选择说明:引入管水表只计生活用水量全楼设计秒流量=7.76L/s=27.94/h;查教材附录1-2,选LXL-50N螺翼式水表=30/h>27.94/h,符合要求;确定特性系数Kb,Kb=30×30/10=90;求水表的水头损失,=27.94×27.94/90=8.7;查教材表3-6,8.7<12,符合要求。因为楼内只有公共卫生间,所以整幢楼只用一个进楼的水表。第二节消防系统计算书2.2.1系统设置及参数的确定一、消火栓给水系统布置的地点1.每层都要设置,无可燃物的设备层可以不设置;2.消防电梯前要设置;3.高层屋顶要设,避难层要设;4.消火栓设置于明显的地方(比如在楼梯口附近或在走廊),离地面的高度为1.1m。二、消火栓给水系统用水量的确定该综合楼的总高度为33层,共129.8m,属于超高层民用建筑,其用水量查高层民用建筑室内外消火栓的用水量表可知,室外消防的用水量为30L/S,室内为40L/S,每根立管的最小流量为15L/S,每支水枪的最小流量为5L/S,同时使用的枪支数为8支。三、室内消火栓间距的确定1)高层民用建筑及其地下车库消火栓的间距为不超过30m。2)求充实水柱的长度查各类建筑要求水枪的充实水柱的长度表可知,该综合楼的充实水柱的长度不小于13m,计算公式如下:式中——水枪充实水柱的长度(m);——室内最高着火点离地面的高度(m);——水枪的喷嘴离地面的高度,一般取1(m);——水枪工作时的上倾角,一般取。所以,求出水枪的充实水柱的长度为:=5.86m由于每支水枪的最小流量为=5L/S,查《建筑给水排水设计手册》,水枪的口径应采用19mm,水带应采用衬胶水带,直径为65mm,长度为25m,水枪所需要的充实水柱长度为13m,为了使各层消火栓出水流量接近设计值,在拴口静压力超过0.5MPA的消火栓前设置减压孔板。3)消火栓的保护半径及立管中流量的分配R=Ld+式中Ld——消火栓水带的长度(m)。Ld=0.8×25=20mR=20+13=26.82m根据规范的要求,室内消火栓间距不应大于30m,所以最大间距取27m。该系统中,同时使用水枪的支数为8支,其高区流量的分配为:最不利管段为15L/S,此不利管段为15L/S,第三不利管段为10L/S。所以,在同一层上,需要有三只相邻的水枪同时到达室内的任何一个地方。在29层以下,最不利管段为13L/S,此不利管段为11L/S,第三不利管段为9L/S,第四不利管段为7L/S。所以,在同一层上,需要有四只相邻的水枪同时到达室内的任何一个地方。2.2.2一、消火栓口所需要的压力及其流量的确定消火栓口所需要的压力由下列公式计算=++式中——消火栓口所需要的水压(KPa);——水枪出水的水头损失(KPa);——水带的水头损失(KPa);——水枪口的压力(KPa)。式中——水带的比阻,口径为65mm的水带的比阻为0.0172;——水枪喷嘴射出的流量(L/S);式中B——水枪的水流特性系数。=0.004302510=26.87KPa=/0.158=155.33KPa=++=20+26.87+155.33=202.2KPa但考虑三股水柱作用时,消防立管实际流量16.5L/S,选DN125管,v=1.24m/s,1000i=23.50。考虑该建筑发生火灾时能保证同时供应8股水柱,消火栓用水量Q=85.5=44L/S。消火栓环状给水管采用DN150钢管,v=2.5m/s,1000i=81.00。二、消火栓管网的水力计算本消火栓系统分区,地下二层至十八层为一区,十九层至三十三层为一区,管网竖向成环。在三十三层和二十二层设有消防水箱。1)由消火栓的平面布置图和系统图可知,高区消火栓系统的最不利管段为:123abcdef。如下图所示:33层上消火栓口的压力及其流量分别为=0.19MPa=5L/S32层上消火栓口的压力及其流量为式中——32层消火栓口的压力(MPa);——楼层的高度(MPa)。=0.19+0.036=0.226MPa水枪的实际出流量为==5.52L/S4)31层上消火栓的压力及其流量=226+36=262KPa水枪的实际出流量为==5.97L/S5)计算管路的流量Q=5L/S=5+5.52=10.52L/S=10.52+5.97=16.49L/S==16.49L/S=2=216.49=32.98L/S=32.98+10=42.98L/S====42.98L/S6)消火栓系统的水力计算表见附表X-1系统中其它立管的管径为100mm,三十三层,十九层,十八层和地下二层的环状管网的管径均为150mm,f、g二点接出的管径取100mm,顶层的环状管网用150mm的管径。7)超压消火栓减压值的计算当系统中消火栓口的压力超过0.5MPa时,需要用减压孔板减压。减压孔板的选型及其减压数值见附表X2。注:表中个字母的含义如下:——第i层的的消火栓口距离十六层消火栓口的距离(m);——水流从第i层到十六层的总的水头损失(KPa);——十六层消火栓口的压力(KPa);——第i层消火栓口的压力(KPa);——消火栓的最小减压数值(KPa);——消火栓的最大减压数值(KPa);——减压孔板的减压值(KPa);——经减压孔板减压后的消火栓口的压力(KPa);——减压孔板的孔径(mm);=10++=-500=-H8)水泵的选择高区:最不利点消火栓到消防泵的高差为53.3m.水池最低水位至高区管网管道长度为52.2m,最不利消火栓立管到高区管网底环长度52.7m,沿程水头损失为:53.30.081+52.70.0235=5.5kpa1管路中总的水头损失为;=1.2=1.25.5=6.6m2水泵的扬程确定=53.3+6.6+20.22=80.1m3)水泵流量的确定=43L/S所以,水泵的型号及其参数见表4-1。表4-1水泵参数型号流量(L/S)扬程(m)轴功率(kw)IS125-100-25033.3-55.687.00-80.0075水泵电机型号Y280S-2(T)。低区:最不利点消火栓到消防泵的高差为99.4m.水池最低水位至低区管网管道长度为64.8m,最不利消火栓立管到低区管网底环长度75.9m,沿程水头损失为:64.80.081+75.90.0235=9.35kpa1)管路中总的水头损失为;=1.2=1.29.35=11.2m2)水泵的扬程确定=99.4+11.2+20.22=130.8m3)水泵流量的确定=43L/S所以,水泵的型号及其参数见表4-1。表4-1水泵参数型号流量(L/S)扬程(m)轴功率(kw)XBD14/50-DLX44140110水泵电机型号Y315S(T)。 9)水泵结合器的选择n=Q/q式中n——水泵结合器的个数(个);Q——室内消火栓的消防用水量(L/S);q——每个水泵结合器的出流量(L/S),取10L/S;n=40/10=4个水泵结合器的型号及其参数见表4-2。表4-2水泵结合器参数型号口径(mm)接口型号工作压力(MPa)重量(kg)SX150150KWS801.64032.3消防水箱及消防水池的设计一、消防水箱设计1)消防水箱容积的确定消防水箱应满足消防前10min钟的用水量的需求,计算公式为:V=10Qt/1000式中V——消防水箱的容积();Q——室内消防用水量(L/S);t——消防水箱的灭火时间,取10min。V=401060/1000=24>18因室内消防用水量为40L/S〉25L/S,根据《建筑设计防火规范》8.6.3.屋顶消防水箱计算容积超过18时可以取18。消防水箱的容积符合要求。2)消防水箱的设置高度及其校核高区消防水箱间的地面高度为119.2m,高区消防水箱距离地面的高度为0.3m,总高度为119.5m,可以求得水箱底部距离三十三层的消火栓口的距离为119.5-120.3=-0.8,低区水箱底部距离十八层消火栓口为9m,据规范的要求,建筑高度超过100m,最不利点的消火栓口的压力不应小于7m。以上条件不满足规范的要求,所以要设置增压设备。在水箱出水口处设置水泵和气压罐。见图2.3.1。3)局部增压设施采用水泵和气压罐增压,最不利消火栓实际流量为5.5L/S,消防立管流量16.5L/S,管径D=125mm,1000i=23.50,v=1.24m/s,高区L=0.8m低区L=9m,消防环管流量44L/S,管径D=150mm,1000i=81.00,v=2.5m/s,高区Ld=46m,低区Ld=33m.高位水箱到最不利点所需的压力:H=hd+Hg+il*(1.1)=20.2+1.1*(46*0.0081+0.0235*0.8)=20.6m低区水箱到最不利点所需的压力:H=hd+Hg+il*(1.1)=20.2+1.1*(33*0.0081+0.0235*9)=20.7m水箱队最不利点的消火栓作用压力为7m,不能满足最不利点的消火栓水压要求,应选择气压供水加压或设置稳压泵。高区气压罐低压:P1=20.6-7=13.6m,P2=P1+10=23.5m.低区气压罐低压:P1=20.7-7=13.7m,P2=P1+10=23.7m.根据《高层民用建筑设计防火规范》GB50045-95规定:气压给水设备的气压水罐其调节水量为2支水枪30的用水量和5个喷头30的用水量之和,即:气压罐的调节容积:V=2530+5130=0.45m3V0=1.10=1.65m3。其中:---容积附加系数,补气式立式水罐为1.10---安全系数,宜采用1.0-1.3,本式取1.1。选择:图2.3.1二、消防水池的设计1)消防水池容积的计算该综合楼属于一类高层民用建筑,消防水池的贮水量为3h的消防用水量。所以,水池的容积为:V=3.6Qt《技术措施》7.4.3式中V——消防水池的容积();Q——室内消防用水量(L/S);t——消火栓的灭火时间(h);V=3.6403=4322.4自动喷水灭火系统的设计2.4.1自喷灭火系统布置原则一、自动灭火系统是根据被保护场所的气象条件,对被保护对象的保护目的以及可燃物类别和火在燃烧特性、空间环境和喷头特性等因素综合来确定类型及选择。1、常用灭火系统1)湿式:湿式系统是一种装有自动喷水的闭式喷头,平时管内充满水,用时作为系统自动驱动媒介的系统。特点:反应比较迅速,控灭火能力强。缺点:易造成误喷;不适用于温度<40C和>700C;易漏水,损失装饰。2)干湿:平时报警阀后管道充满有压气体,着火时先喷气再冲充水喷水灭火。优点:平时管内无水,对装饰无损害,对环境温度无要求,适用于火灾危险性不高,温度特殊场所(如冷库)。缺点:灭火不及时。3)预作用:有火灾探测系统,装有自动喷水的闭式喷头,平时有压气体,着火后先报警排气,再充水,等温度升高时再喷水灭火。适用于现场要求较高,不造成误喷的场所。4)重复启闭预作用系统:一种在扑灭火灾能自动关闭阀门,复燃后能再次启闭阀门灭火的系统,是一种真正的自动灭火系统。适用于灭火后立即停水的场合。5)雨淋系统:装有开式喷头,油探测器、传动管或手动后来控制一组喷头。特点:反应快,灭火及时,能有效控制扑灭火灾,但耗水量大。适用于火势发展迅猛,易蔓延,空间净空高的场所。6)水幕系统:喷出水帘水幕。作用:隔绝、降温。适用于重要建筑的门窗下及舞台和观众席间。7)水喷雾系统,适用于与电有关或石油化工有关的灭火,如变压器或与石化有关的罐,大的传送带两头及上下部。特点:电绝缘性好,不会造成液体飞溅。8)自动喷水泡沫灭火联用系统(同时作用),闭式:一般湿式系统中传一个泡沫罐。开式:(飞机库)先喷水控火,再喷泡沫强化灭火效能;或先喷泡沫灭火,再喷水冷却,防止死灰复燃。特点:省水,对物品损失小。2、火灾危险等级我国火灾危险等级可分为:1)轻危险级,2)中危险级,3)严重危险级。我国轻危险级,一般指可燃物较少,可燃性低和火灾发热量较低,外部增援和疏散人员较容易的场所。如建筑高度为24m及以下的旅馆、办公楼仅在走道设置闭式系统的建筑。中危险级,一般可指内部燃烧数量为中等,可燃性也为中等,火灾初期不会引起剧烈燃烧的场所。大部分民用建筑和工业厂房划归中危险级。由于此类场所种类多,范围广,因此又划分为中Ⅰ级和中Ⅱ级。中Ⅰ级为高层民用建筑,一般公共建筑,木结构中的食品、家电、玻璃制品等工厂的备料与生产车间,冷藏库,钢屋架等构件。商场内物品密集、人员密集,发生火灾的频率较高,容易酿成大火造成群死群伤和高额财产损失的严重后果,因此将大规模商场列入中Ⅱ级,列入中Ⅱ级的民用建筑还有可燃物较多的书库、舞台(葡萄架除外),汽车停车场,以及难于疏散、难以扑救的总建筑面积1000m2及以上的地下商场。2.5自动喷水灭火系统的布置及管网的水力计算该大楼的危险等级查《自动喷水灭火系统设计规范》,该楼属于中危险等级级,汽车停车库为中危险级级,由于是超高层建筑,所以需要分区。自喷平面与系统布置见平面图和喷淋系统大样图。高区最不利点在三十二层上,低区最不利点在二十四层上。1.三十二层自喷系统的布置:1)设计参数三十二层为中危险极=1\*ROMANI级,喷头的喷水强度为q=6.0,作用面积为160,最不利点喷头的流量为1.33L/S,喷头的间距及其相邻的支管的间距小于或等于3.6m,喷头与墙的最大距离不超过1.7m,理论作用面积的长边为L=1.2m=15.17m,2)系统的布置喷头的布置形式采用长方形布置,三十二层的平面布置见下图:采用作用面积法计算K=80中危险级1级,计算原理参照《自动喷水灭火系统设计规范GB50084-2001》,采用作用面积法基本计算公式1. 喷头流量q=K*SQRT(10P)式中:q-喷头处节点流量,L/minP-喷头处水压,MPaK-喷头流量系数2. 流速V=(4*Q)/(π*Dj*Dj)式中:Q-管段流量L/sDj-管道的计算内径(m)3. 水力坡降i=0.00107*V*V/(pow(Dj,1.3),式中:i-每米管道的水头损失(mH20/m)V-管道内水的平均流速(m/s)Dj-管道的计算内径(m)4. 沿程水头损失h=i*L,式中:L-管段长度m5. 局部损失(采用当量长度法)h=i*L(当量),式中:L(当量)管段当量长度,单位m(《自动喷水灭火系统设计规范》附录C)6. 总损失h=h(局)+h(沿)7. 终点压力Hn=Hn-1+h管段名称起点压力mH2O管道流量L/s管长m当量长度管径mm水力坡降mH2O/m流速m/s损失mH2O终点压力mH2O1-210.001.331.592.00250.7702.502.7612.762-312.761.330.200.60250.7702.500.6213.383-413.381.331.400.60250.7702.501.5414.914-514.911.334.570.60250.7702.503.9818.895-618.891.334.410.50250.7702.503.7822.686-722.687.130.650.60500.5633.360.7123.387-823.3815.986.113.00650.7384.536.7330.119-1036.9325.981.723.00651.9517.379.2246.1510-1146.1525.980.403.00651.9517.376.6252.7811-1252.7825.980.900.00651.9517.371.7654.53计算结果:所选作用面积:168平方米总流量:25.98L/s平均喷水强度:8.65L/min.平方米入口压力:54.53米水柱3)作用面积的选择见上图,该作用面积的实际面积为F==168>160,符合要求。4)设计流量的计算a作用面积内的理论设计流量=1686/60=16.89L/Sb作用面积内的计算设计流量1.3318=23.94L/S5)校核a作用面积内的计算强度=6023.94/168=8.5>6b一直喷头的喷水强度=8.21>66)按控制标准确定管径,进行水力计算,见附表Z-1;报警阀的水头损失:0.0030216.82=0.85m为满足该层最不利的喷头的喷水强度要求,报警阀前的应有的压力为:H=4+19.341.2+10+0.85=38.06m2.二十四自喷系统的布置二十四层为中危险极=1\*ROMANI级,喷头的喷水强度为q=6.0,作用面积为160,最不利点喷头的流量为1.33L/S,喷头的间距及其相邻的支管的间距小于或等于3.6m,喷头与墙的最大距离不超过1.7m,理论作用面积的长边为L=1.2m=15.17m,2)系统的布置喷头的布置形式采用长方形布置,二十二层的平面布置见下图:3)作用面积的选择见上图,该作用面积的实际面积为F=7.22(8.1+3)=179.

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论