2发电机动态试验报告_第1页
2发电机动态试验报告_第2页
2发电机动态试验报告_第3页
2发电机动态试验报告_第4页
免费预览已结束,剩余1页可下载查看

下载本文档

版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领

文档简介

同步发电机动态试验报告工程名称: 试验日期:2023年12月18日设备编号:2#发电机 温 度:5℃ 湿 度:35%RH托付单位: 执行标准:GB50150-2023一、主设备技术参数:发电机: 型号:QFJ-60-2额定电压:10500V额定功率:60MW额定电流:4124A励磁电流:259.0励磁电流:796A功率因数:0.8编号:202301003制造厂:南京无励磁机,承受静止励磁。二、测量转子及轴承座绝缘和沟通阻抗绝缘电阻绝缘电阻ΜΩ0/分203000转/分28超速后3000转/分20轴承座3000转/分20沟通阻抗转速 电流A 电压V功率WV电流AW0441.9102.91009.356650043685.4707.73041200434.673.6707.962982400434.976.3708.14301.63000433.771.4708.13299.7三、自动励磁调整系统调试〔协作制造厂进展〕。四、机组启动试验:#2发电机短路特性试验:发电机升电流 400A,检查各屏柜的沟通电流回路电流值及相序,无开路,读数正常; 查#1发电机回路无特别;升#1发电机至额定电流4124A,二次额定电流4.12A。测量各CT在各屏柜的电流正常,向量正确,发电机差流接近为0。定子电流实测值IaIbIc发电机短路特性表格:上升 〔励磁定子电流实测值IaIbIc0400800120016002023240028003200360040004124(A)00.4010.8011.2021.6021.9942.412.813.223.584.024.11(A)00.4020.8031.2091.6012.012.422.823.233.604.044.13(A)00.4000.8041.2071.6092.012.422.823.233.604.044.13励磁电压〔V〕015.829.843.857.068.883.694.8108.7121.2136.3140.1励磁电流〔A〕052.2105156204253306357410459509523定子电流发电机短路试验定子电流发电机短路试验45004000350030002500电2023机上升下降1500100050000100200300400500600实测值4124400036003200280024002023160012008004000Ia(A)4.114.013.593.212.802.412.001.591.2010.8010.4080Ib(A)4.134.033.613.212.822.422.011.601.2060.8050.4110Ic(A)4.134.023.603.202.822.422.011.601.2030.8060.4100励磁电压〔V〕140.1136.1120.1108.194.782.168.256.142.829.315.40励磁电流〔A〕52350645540535330224920115110249.70发变组短路试验:升#14124A,二次额定电流4.12A电流1123A,二次3.75。测量各CT在各屏柜的电流正常,向量正确,发电机差流接近为0,发变组差流接近为0,主变差流接近为0。定子电流实测值IaIbIc—、发变组短路特性表格:上升 〔励磁定子电流实测值IaIbIc0400800120016002023240028003200360040004124(A)00.4030.8061.2041.6042.042.392.803.203.604.034.10(A)00.4020.8081.2021.6032.032.402.813.213.624.024.10(A)00.4020.8071.2001.6022.022.392.803.203.604.004.00励磁电压〔V〕023.536.950.363.477.190.8103.0115.9128.8138.4141.9励磁电流〔A〕067.3121173222269316374427475527541定子电流发变组短路特性表格:下降定子电流实测值4124400036003200280024002023160012008004000Ia(A)4.103.993.643.232.842.432.001.5981.2090.8060.4070Ib(A)4.104.013.633.222.832.422.011.6031.2070.8080.4050Ic(A)4.004.003.613.202.812.402.001.6001.2050.8070.4030励磁电压〔V〕141.9137.8128.1115.2102.290.176.162.749.236.222.90励磁电流〔A〕54152347141736530826121716511863.20发变组短路曲线发变组短路曲线4500400035003000流2500电磁2023励上升下降1500100050000100200300励磁电压400500600发变组空载特性特性试验:测录发电机开路特性。上升特性做至 11KV额定值。记录表式见表,上升曲线到1.05倍额定电压既11025V时作耐压试验。测量PT发变组空载特性表格:上升 〔励磁电流1500A/75mv 〕定子电压实测值01000202330004000500060007000800090001000011025Uab010.2220.0330.0340.150.160.170.180.190.3100.2120.2Ubc010.2120.0730.0240.250.260.270.280.390.4100.3120.3Uca010.2020.0930.0140.050.060.070.080.190.2100.2120.0励磁电压〔V〕06.71318.223.929.335.140.847.353.463.274.7励磁电流〔A〕018.744.167.190.7116138161186211240266发变组空载特性表格:下降定子电流实测值11025100009000800070006000500040003000202310000Uab120.2100.390.280.370.360.350.340.030.0420.0410.190Ubc120.3100.490.180.470.160.250.140.130.0320.0610.170Uca120.0100.190.180.370.160.050.040.030.0120.0310.150励磁电压〔V〕77.963.153.347.140.735.029.123.818.1136.60励磁电流〔A〕26623720818315813511288.965.542.117.50发变组空载曲线发变组空载曲线12023100008000压电端机6000上升下降400020230050100150200250300高厂变短路时,高厂变差流接近为 0,发变组差流接近为0。保持发电机周率和电压额定,用高内阻电压表测量发电机空载轴电压。发电机轴两端电压V应近似相等轴承电压V1 2发电机两端电

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论