1、ICS 29.240.30F 21Record No. J5222006Electric Power Industry Standard of the People's Republic of ChinaPDL / T 5340 2006Technical Code for Designing of Telecommunication Lines Against Danger Effects from DC Power Transmission LinesIssue Date: May 6, 2006ImpIementation Date: October 1, 2006Issued

2、by the NationaI DeveIopment and Reform Commission of the PeopIe's RepubIic of ChinaElectric Power Industry Standard of the People's Republic of ChinaPDL / T 5340 2006Technical Code for Designing of Telecommunication Lines Against Danger Effects from DC Power Transmission LinesTranslation spo

3、nsored by: China Electric Power Planning & Engineering Association Translated by: SUNTHER Consulting Co., Ltd.Reviewed by: Central Southern China Electric Power Design InstituteCHINA ELECTRIC POWER PRESS BEIJING, 2013图书在版编目(CIP)数据DL/T 53402006 直流输电线路对电信线路危险影响防护设计技术规定=Technical code for designing

4、 of telecommunication lines against danger Effects from DC power transmission lines: 英文 / 中华人民共和国国家发展和改革委员会发布. 北京:中国电力出版社,2013.5ISBN 978-7-5123-4080-0. D . 中 . 直流输电线路-影响-通信线路防护-设计规范-中国-英文 . TN913.3-65中国版本图书馆CIP 数据核字(2013)第 029582 号中国电力出版社出版(北京市东城区北京站西街 19 号 100005 ) 北京博图彩色印刷有限公司印刷*2013 年 5 月第一版2013

5、年 5 月北京第一次印刷850 毫米×1168 毫米 32 开本 1.125 印张 24 千字敬 告 读 者本书封底贴有防伪标签,刮开涂层可查询真伪本书如有印装质量问题,我社发行部负责退换版 权 专 有翻 印 必 究DL / T 5340 2006ContentsForeword1 Scope12 Terms and Definitions23 Fault Conditions of DC Transmission Lines and Operating Conditions of Telecommunication Line Circuits64 Permissible Value

6、 of Danger Effects75 Calculation of Danger Effects116 Protective Measures17Appendix A (Normative)Calculation of Mutual InductiveCoefficient of Infinite LongAdjacent Lines19Appendix B (Normative)Calculation of the Inductance to Groundof the Conductors of DC Transmission Lines23IDL / T 5340 2006Forewo

7、rdThis code is prepared in response to the arrangement made by the Notice on Issuing the Plan for Supplementing Electric Power Industry Standard 2003 Issued by the General Office of National Development and Reform Commission (FGBGY2003873).The large-scale construction of HVDC transmission lines and

8、the increasingly growing transmission voltages are bound to cause electromagnetic interference to the adjacent telecommunication lines. Unfortunately, no material and literature in China and foreign countries has systematically presented the harmful effects caused by DC transmission lines to the adj

9、acent telecommunication lines and the relevant protection measures, the relevant influencing mechanism and the calculation methods in this respect. Additionally, no unified calculation and design standard is available in China. In light of this, it makes great sense to establish this code to support

10、 the engineering design of DC transmission lines, address the actual problems of a project, improve the design quality of communication protections, make the project construction cycle less time consuming and reduce the investment costs of the project.This code places emphasis on describing the uniq

11、ue characteristics of the design of DC transmission lines that may cause adverse effects to the adjacent telecommunication lines. Since the design of DC transmission lines has much in common with that of AC transmission lines, DL/T 5033 2006 The Design Rules of Telecommunication Lines Against Danger

12、 and Interference Effects From Power Transmission Lines may be taken as a reference.IIDL / T 5340 2006Appendices A and B to this code are normative. This code is proposed by China Electricity Council.This code is solely managed and interpreted by Technical Committee on Electric Power Planning and En

13、gineering of Standardization Administration of Power Industry.This code is mainly drafted by Central Southern China Electric Power Design Institute.The organizations participating in drafting this code include China Power Engineering Consulting Group Corporation, Northeast China Electric Power Desig

14、n Institute, East China Electric Power Design Institute, Southwest Electric Power Design Institute, and Guangdong Electric Power Design and Research Institute.The leading authors of this code include Xiong Wanzhou, Wang Weihua, Zeng Liansheng, Xie Xing, Miao Guiliang, Zhao Shixiong, Yu Wenzhi, Han Y

15、anming, Wei Dejun, and Meng Xianbin.This code is translated by SUNTHER Translation & Solutionsunder the authority of China Electric Power Planning & Engineering Association.IIIDL / T 5340 20061ScopeThis code specifies the permissible value of danger effects on telecommunication lines from DC

16、 transmission lines, presents the calculation methods of danger effects, and provides necessary parameters and protective measures.This code applies to the design of the protections that protect telecommunication lines from danger effects caused by the adjacent DC transmission lines.In addition to t

17、his code, the design of the protections that protect telecommunication lines from danger effects caused by the adjacent DC transmission lines shall comply with the provisions of the national standards currently in force as well.1DL / T 5340 20062Terms and DefinitionsThe following terms and definitio

18、ns apply to this code.2. 0. 1Telecommunication linesCommunication lines in forms of overhead open wire, overhead or buried cable, overhead or buried telecommunication optical fiber cable, and railway signal electrical line, cable television (signal, feed and subscriber) line, and remote control and

19、signaling line.2. 0. 2Railway signal electrical linesCables and overhead open wires that transmit information for railway signal system, such as relay semi-automatic or automatic obturate way circuit, remote control line, remote signaling line, and railway circuit within the automatic obturate secti

20、on.2. 0. 3Danger effectsThe induced voltage and current on telecommunication lines caused by DC transmission lines can possibly endanger the safety of telecommunication operation and maintenance personnel, damage telecommunication lines or equipment, cause fire to buildings and structures, or cause

21、wrong operation of railway signaling equipment which will bring hazards to traffic safety.2. 0. 4AdjacencyThe relative position of telecommunication lines to DC transmission lines when the electromagnetic effects of DC2DL / T 5340 2006transmission lines may cause danger to the telecommunication line

22、s.Parallel adjacency describes a situation in which the variation of distance between two adjacent lines does not exceed 5% of the arithmetic mean of the distance. Oblique adjacency describes a situation in which the variation of distance between two adjacent lines exceeds 5% and increases or decrea

23、ses linearly (both DC transmission lines and telecommunication lines having no turning points).2. 0. 5Adjacent distanceThe distance obtained by perpendicularly drawing a line from any point on the center line of the telecommunication line to that of the DC transmission line.2. 0. 6Length of adjacent

24、 sectThe projected length of the adjacent section of the telecommunication lines on the DC transmission lines.2. 0. 7Cross-overThe situation in which DC transmission lines pass through telecommunication lines from overhead.2. 0. 8Inductive coupling effectEffects of current in DC transmission lines o

25、r from the ground on telecommunication lines through inductive coupling.2. 0. 9Capacitive coupling effectEffects of voltage of DC transmission lines on telecommunication lines through capacitive coupling.3DL / T 5340 20062. 0. 10Resistive coupling effectEffects on the grounding systems and the buria

26、l cables of telecommunication offices (stations) caused by ground resistive coupling when the short-circuit current flowing through the grounding system of DC power transmission line towers results in a potential difference between the direct grounding area and the remote ground area.2. 0. 11Magneti

27、c induction endlong electromotancePotential difference between any two points on a telecommunication line caused by the current in DC transmission line and the ground.2. 0. 12Magnetic induction ground voltageThe ground potential induced at any point on a telecommunication line by the current in the

28、DC transmission line and the ground.2. 0. 13Railway circuitA circuit in which the tracks of railway are used as conductors to check if there are trains on the railway, transmit the information about the presence of trains and form a communication circuit between the ground and the train.2. 0. 14Auto

29、matic obturate way circuitA circuit used to determine the traveling directions of trains when they are traveling bi-directionally on the same railway within the automatic obturate section (normally in the same route of the4DL / T 5340 2006communication lines of railways).2. 0. 15Broadcasting signal

30、linesSignal transmission lines of the wired broadcasting signal transmission system.2. 0. 16Broadcasting feedback linesFeedback transmission lines of the wired broadcasting power transmission system.2. 0. 17Broadcasting user's linesThe transmission lines correspond the output end of transformers

31、 to the input end of user's equipment used in the wired broadcasting power transmission system.5DL / T 5340 20063Fault Conditions of DC Transmission Lines and Operating Conditions of Telecommunication Line Circuits3.0.1 1 The fault conditions of a DC transmission line that may have danger effect

32、s on the adjacent telecommunication lines shall include the following situations:1 Grounding short-circuit of the pole conductors of mono-polar operated DC transmission lines;2 Grounding short-circuit of conductors of one pole of bipolar operated DC transmission lines.3.0.2 2 When calculating the da

33、nger effects on adjacent telecommunication lines caused by DC transmission lines, the following modes should be selected according to the operating conditions of the telecommunication lines.1 The telecommunication lines have one end grounded throughlow impedance and the other end grounded through hi

34、gh impedance (open circuit).2 The telecommunication lines have both ends grounded through low impedance.3 The telecommunication lines have both ends grounded through high impedance (open circuit).6DL / T 5340 20064 Permissible Value of Danger Effects4.0.1 1 In the event of grounding short-circuit fa

35、ult of the pole conductors of DC transmission lines, the endlong electromotance or the ground voltage induced on the telecommunication lines of the overhead open wires shall not exceed 3000 V (peak value).4.0.2 2 In the event of grounding short-circuit fault of DC transmission lines, the permissible

36、 value of endlong electromotance or the ground voltage induced on the core wires of the telecommunication cable lines shall comply with the following requirements.1 Where isolation transformers or lightning protectors areprovided at both ends of the core wires of the telecommunication cable lines:1)

37、 For telecommunication cable lines free of long-distance power supplyUs0.85UDt(4.0.2-1)Us1.2UAt(4.0.2-2)2) For telecommunication cable lines with long-distance power supply in "conductor-to-earth" modeUs0.85UDt-Urs(4.0.2-3)Us1.2UAt-Urs(4.0.2-4)3) For telecommunication cable lines with long

38、-distance power supply in "conductor-to-conductor" mode and grounded at the center pointUs0.85UDt- Urs2(4.0.2-5)7DL / T 5340 2006Where:Us1.2UAt- Urs2(4.0.2-6)UDt DC test voltage of cable core and grounding sheath, V;UAt AC test voltage (effective value) of cable core and grounding sheath,

39、V;Urs long-distance power supply voltage of the sections for which the effects are calculated;Us induced voltage (peak value) of the cable core in the event of faults of DC transmission lines, V.2 When the conditions in clause 1 of 4.0.2 are not satisfied, thevalues specified in 4.0.1 shall be used;

40、 in this case, the insulation electric strength of the telecommunication lines and equipment at both ends of them as well as the over-current capability of the protection unit shall be considered.4.0.3 3 In the event of grounding short-circuit fault of the pole conductor of DC transmission line, the

41、 magnetic induction voltages (including magnetic inductive endlong electromotance and magnetic inductive ground voltage) generated on the telecommunication optical fiber cables shall meet the following provisions:1 For telecommunication optical fiber cable lines which havemetal wire pairs and are fr

42、ee of long-distance power supply:Us0.85UDt(4.0.3-1)2 For telecommunication optical fiber cable lines which have metal wire pairs and long-distance power supply:1) Telecommunication optical fiber cable lines with long-distance power supply in "conductor-to-earth" mode:Us0.85UDt-Urs(4.0.3-2)

43、8DL / T 5340 20062) Telecommunication optical fiber cable lines with long-distance power supply in "conductor-to-conductor" mode and grounded at the center point:Us0.85UDt- Urs2(4.0.3-3)3 Telecommunication optical fiber cable lines with metal members but free of metal wire pairs:Us0.85UDt(

44、4.0.3-4)Where:UDt DC test voltage of outer insulating sheath of optical fiber cables, V;Urs long-distance power supply voltage of the sections for which the effects are calculated, V;Us induced voltage (peak value) of the metal members of the optical fiber cables in the event of faults of DC transmi

45、ssion lines, V.4 Danger effects may not be considered for optical fiber cablesfree of metal members and wire pairs.4.0.4 4 When grounding short-circuit fault occurs at one pole conductor of the DC transmission line, the permissible value of potential difference between the adjacent buried telecommun

46、ication cable cores, the metal wire pairs of the telecommunication optical fiber cable, the metal members and the ground, and the permissible value of potential rise on grounding devices disposed at telecommunication office (station) shall comply with the provisions of 4.0.2 and 4.0.3.4.0.5 5 Where

47、inductive coupling effect and resistive coupling effect are simultaneously caused by DC transmission lines to underground telecommunication cables or telecommunication optical fiber cables,9DL / T 5340 2006the resultant value shall comply with the provisions of 4.0.2 and 4.0.3.4.0.6 6 If the composi

48、te effects of magnetic induction endlong electromotance and the ground potential rise exceeds the permissible value, the ground voltage of the telecommunication line conductors must be further calculated according to the operating conditions of the telecommunication circuit described in 3.0.2.10DL /

49、 T 5340 20065 Calculation of Danger Effects5.1 1Provisions of Calculation5.1.1 1 When grounding short-circuit fault occurs at DC transmission lines, the magnetic danger effects on the telecommunication lines caused by the fault current originating from the rectifier station side shall be considered;

50、 when checking the ground voltage of the telecommunication lines, the magnetic danger effects on the telecommunication lines caused by the fault current originating from the inverter station side may be considered.5.1.2 2 The effects caused by DC transmission lines to the underground telecommunicati

51、on cable lines and the telecommunication optical fiber cable lines shall include resistive coupling effect which shall be calculated based on the short-circuit current flowing through the tower grounding device when one pole conductor of the DC transmission lines experiences grounding short-circuit

52、faults.5.1.3 3 Where DC transmission lines cause both inductive and resistive coupling effects to buried telecommunication cable lines and optical fiber cable lines, the resultant effect shall be calculated as the square root of the sum of squares of both effect values.5.1.4 4 For design of telecomm

53、unication lines with dischargers for protection at locations such as repeaters, junction cabinets and junction boxes, the ground voltage of telecommunication lines shall be considered when the dischargers operate.5.1.5 5 For DC transmission lines with ground wires, the magnetic11DL / T 5340 2006dang

54、er effects may be considered according to the return current effect in ground wires.5.2 2Calculation of Magnetic Danger Effects5.2.1 1 When one pole conductor of DC transmission lines experiences grounding short-circuit fault, the endlong electromotance induced by the short-circuit current on teleco

55、mmunication lines through inductive coupling shall be calculated using Formula 5.2.1.nWhere:E= SwMili Is sti =1(5.2.1)Emagnetic induction endlong electromotance on telecommunication lines, V;w apparent angular frequency affecting the current, rad/s,w =2 f, f=30 Hz;Mi mutual induction coefficient of

56、the ith adjacent section between the DC transmission line and the telecommunication line at 30 Hz, H/km;il length of the ith adjacent section between the DCtransmission line and the telecommunication line, km;ls sum of weighted values of the short-circuit current components at individual frequencies when one pole conduct

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论