1、工艺热力管线 岩棉管壳保温结构通用(适用T350,DN350mm)岩棉厚度选用表,保温材料用量表介质温度T150公称直径DN(mm)152025405080100150200250300350保温厚度 (mm)404040404050505050606060铝皮用量 (m2/m)0.390.410.440.480.520.740.800.991.201.471.671.85铁丝用量 (kg/m2)0.150.150.150.150.150.140.140.140.130.130.130.13保温层面积(m2/m)0.320.340.350.400.430.600.660.821.001.241

2、.401.56介质温度 150T250公称直径DN(mm)152025405080100150200250300350保温厚度 (mm)505050506070707070808080铝皮用量 (m2/m)0.460.470.510.550.670.880.951.131.351.621.801.99铁丝用量 (kg/m2)0.150.150.150.140.140.140.140.130.130.130.130.13保温层面积(m2/m)0.380.400.420.470.560.720.780.941.131.361.521.69介质温度 250T350公称直径DN(mm)15202540

3、5080100150200250300350保温厚度 (mm)606060707080809090100100100铝皮用量 (m2/m)0.540.540.580.700.760.951.021.271.491.761.942.14铁丝用量 (kg/m2)0.140.140.140.140.140.140.140.130.130.130.130.13保温层面积(m2/m)0.450.460.480.590.620.780.841.071.251.491.651.81光管表面积 表-4公称直径DN(mm)152025405080100150200250300350表面积 (m2/m)0.070

4、.090.100.150.180.280.340.500.690.861.021.19防腐层材料用量表名称单位用量备注红丹kg/m20.24光管表面积见表-4清油kg/m20.12汽油kg/m20.024保温材料用量表名称单位用量备注岩棉管壳m/m1.05岩棉弯头个/个1.05半圆头自攻螺钉Kg/100m0.9M4×16,GB841-66立管托板Kg/m立管0.54mm厚钢板沥青玻璃布m2/m22.40.1×250结构说明:1. 防腐层:管外壁除锈后刷红丹底漆两遍。2. 保温层:岩棉管壳。3. 捆扎镀锌铁丝:16。4. 防潮层:沥青玻璃布。5. 外保护层:合金铝皮0.6mm

5、厚。6. 半圆头自攻螺钉。其他说明1. 弯头保温选用岩棉弯头。2. 岩棉容重选用150kg/m3。3. 每段管壳用双重铁丝捆扎一道,间隔200-300mm。4. 沥青玻璃布以螺纹形式半重叠缠绕自低向高处施工,每隔3m用铁丝捆扎一道。5. 为防止保温层干滑,立管管线底部要设置托板,每隔5-10mm加一块。6. 水平管线保温时,切口宜置于侧下。7. 在用铝皮施工时,接管线坡向,自下向上施工,两板横向半圆凸缘重叠,纵向搭口应在管线水平中分线下30°-45°处,相邻铝皮搭接要紧密,以防止雨水渗入,8.当没有沥青玻璃布时,可用细格玻璃布(0.1×250)两面刷沥青代替。工艺

6、热力管线 保冷结构通用保冷厚度选用表,保冷材料用量表介质温度 -40 表-1公称直径DN(mm)152025405080100150200250300350400450500保冷厚度 (mm)505050506070707080808090909090铝皮用量 (m2/m)0.470.470.510.550.610.740.800.991.201.401.561.781.952.142.32保冷层面积(m2/m)0.390.400.420.470.560.720.780.941.191.361.521.751.902.072.23保冷层体积(m3/10m)0.120.120.130.160.2

7、20.350.400.520.750.891.021.321.461.611.75介质温度 -20公称直径DN(mm)152025405080100150200250300350400450500保冷厚度 (mm)404040505050606060707070707070铝皮用量 (m2/m)0.390.410.440.550.610.740.881.061.281.551.731.922.102.282.46保冷层面积(m2/m)0.320.340.360.470.490.600.720.881.071.301.461.631.781.952.11保冷层体积(m3/10m)0.080.09

8、0.100.160.170.220.320.420.530.760.870.981.091.211.32介质温度 0公称直径DN(mm)152025405080100150200250300350400450500保冷厚度 (mm)303030303040404040404040405050铝皮用量 (m2/m)0.320.340.360.410.450.660.740.921.121.331.511.701.872.142.32保冷层面积(m2/m)0.260.280.300.340.370.530.590.750.941.111.271.441.591.821.98保冷层体积(m3/10m

9、)0.050.060.060.080.080.160.190.250.330.400.460.530.590.830.91光管表面积 表-4公称直径 DN(mm)152025405080100150200250300350400450500表面积 (m2/m)0.070.090.100.150.180.280.340.500.690.861.021.191.341.511.67防腐层材料用量表名称单位用量备注红丹kg/m20.24光管表面积见表-4清油kg/m20.12汽油kg/m20.024保冷材料用量表名称单位用量备注泡沫玻璃管壳m/m1.05或复合泡沫玻璃塑料管壳泡沫玻璃弯头个/个1.0

10、5或复合泡沫玻璃塑料弯头半圆头自攻螺钉Kg/100m0.9M4×16,GB841-66立管托板Kg/m立管0.54mm厚钢板粗格玻璃布m2/m21.20.1×250沥青玛蹄脂Kg/m210粘结剂Kg/m325体积见表-1捆扎镀锌铁丝Kg/m20.3516#结构说明1. 防腐层:管外壁除锈后刷红丹底漆两遍。2. 保冷层:泡沫玻璃预制块或复合泡沫玻璃塑料预制块。3. 捆扎镀锌铁丝:16#4. 防潮层:(1)沥青玛蹄脂,(2)粗格玻璃布,(3)沥青玛蹄脂。5. 外保护层:合金铝皮 06mm。6. 半圆头自攻螺钉。其他说明1. 泡沫玻璃容重选用150-180kg/m3,弯头选用泡沫玻璃弯头或复合泡沫玻璃塑料弯头。2. 预制块管壳,弯头一般为1/2圆弧型,管壳长度为300-500mm。3. 施工时,预制块用粘结剂勾缝,接缝要错开,水平管线的纵缝要在

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论