1、gw23a-252 型 隔 离 开 关gw23a-252 disconnector安 装 维 修 使 用 说 明 书installation maintenance operation manual编号:0tk.466.5029no:0tk.466.5029山东泰开隔离开关有限公司shandong taikai disconnector co., ltd二一年七月july. 2010tk gw23a-252 disconnector catalogue、general. 2、working conditions. 2、characteristics. 3、classification and

2、technical parameter. 4、product structure and the operation principle. 5、packaging and delivery. 8、inspection and storage. 8、unloading and lifting. 9、installation and debugging. 9、acceptance and fine-tuning before installation on site 13、accompanying document 14、 ordering instructions 141tk gw23a-252

3、 disconnector 、 general1.1 product usagegw23a-252d(w) series is a three-phase, ac, hv disconnector of double post, horizontal break, single arm shrinkable clamp style.(briefed as “gw23a-252 disconnector”)is used in power supply system with rated frequency 50hz and rated voltage 252kv, providing hv l

4、ine to transition under no load conditions as well as disconnecting the repaired hv busbar、circuit breaker and other high voltage electric equipment and between live hv lines. at the same time, it also applied when mode of operation in power system need to change during reversing switch to carry out

5、 charging current for switching busbar 、voltage transformer and lightening arrester.1. the explanation of product specifications(examples) g w 23a - 252 d (w) / j 3150- 50rated short-time withstand currentrated current motor operation mechanismimproved design serial number anti-pollution typewith ea

6、rth switchrated voltagedesign serial number outdoordisconnector 1.2 standard u gb 1985-2004 hv ac disconnecting switch and earth switchu gb/t 11022-1999 common technical requirement for hv switchgear and control gearu dl/t 486-2000 order technical requirement for disconnector and earth switchu dl/t

7、593-2006 hv ac disconnecting switch and earth switch、working conditionsu ambient temperature: -50+50;u height above sea level no more than 2000m(2500m and more we can improve product adaptability according to the customers requirements);u wind presssure no more than 700pa(equal to wind speed no more

8、 than 34m/s);u seismic intensity no more than 9 degree;u ice coating thicknessno more than 20mm;u pollution classes or ;u the mounting place should be far from inflammable, explosive, corrosive danger and violent vibration。u special working conditions shall be solved by clients and manufacturer.、cha

9、racteristicsgw23a-252disconnector is a kind of perfected and improved disconnector (conforming to sgccs requirement) developed on the basis of gw23a-252. the moving contact system is of robotic manipulator structure, which provides beautiful outline, excellent electric and mechanical performances, g

10、ood ability in resisting corrosion and earthquake and reduces the longitudinal distance of the power station, saves occupying area、down leads and insulators comparing with other kind of disconnectors. it provides the following characteristics: a. the main circuit adopts top-grade anti-rust al-alloy

11、that provides excellent conducting capacity, light weight, high mechanical intensity; the driving part of the main blade, balance spring, clamping spring, reset spring are designed in the conduct pipe to be free from the outside environment influnence. b. the fixed contacting surface is tinplated; c

12、hange the structure of the static connector, enhance the contacting stress of the dynamic and static connectors; add insulating components to the upper conductive rod(avoid branching); measures are adopted to ensure the conductive circuit is not to hot, such as, sealing glum is daubed to the fixed c

13、onductive contacting surface to avoid the entering of the water and moisture.c. every part of the main blade all adopts fixed soft connecting through-flow, soft connection adopts pure aluminum material, silver plating on the conductive connecting surface, good conductive and flowing ability, anodic

14、oxidation processing is conducted to every layer of the soft connection to ensure the processing of the no corrosion of the soft connecting net. d. top pressure tripping device is improved to insure reliable making and keep good working state under the action of wind force and electric dynamic force

15、. modify the insulating roller into stainless roller to avoid aging and fragment.e. rotating link adopts no oil lubricated bearings and insulating no oil bearing, transmission link adopts joint bearings, all the shaft pins are using aluminum bronze or stainless steel material which have corrosion re

16、sistance capability, low rotating resistance, small cooperating gap, reliable transmission, by effectively avoiding the rusting of the rotating bearing, it ensures the flexible rotation. f. by adopting high quality raw materials or high anti-corroding surface treatment measures to improve the corros

17、ion resistance capability of overall product of corrosion of, such as all the surfaces of the steel components adopt galvanized treatment; all the shaft pins adopt aluminum bronze or stainless steel material; the non conductive contact surface of the conductive pipe adopts anodic oxidation treatment

18、 etc. g. the main earthing blade and vertical transmission rod connected to the noumenon are connected by the plywood and clamp, the main earthing blade is the third class level, the transmitting end adopts u-shaped bolts and clamp connecting style, and the other adopts double screw adjustable conne

19、ctor, the field welding and drilling can be canceled, and the field installation, debugging, disassembly and maintenance are very convenience to the consumers.h. the earthing blade adopts the single foot action structure with the counterweight of a heavy hammer, the hammer adopts adjustable structur

20、e to ensure the moments of the earthing blade balance, the opening and the closing operation smooth, and the operation easy and reliable during the process of opening and closing. i. the earthing blade can be incorporated by cjtka perfectly improved electric mechanism, or cs31 perfectly improved man

21、power mechanism, all of them adopt stainless steel or aluminum alloy case and have beautiful outlook, good anti-corroding, water-proof and dust-proof capability. secondary components which have the interlocking unit and can satisfy various interlocking functions introduce the high-qualified products

22、 produced by the domestic famous enterprises or joint ventures.j. high qualified strength post insulator which is stable is adopted, it requires that the sintering position of the porcelain bottle porcelain should naked and have waterproof structure, safety coefficient of mechanical load 2.5 times a

23、nd above should be met. porcelain bottle manufacturer and the test of porcelain bottles entering the company should be strictly examined to ensure its high quality and reliability. k. holistic supplying the product can be according to the above the ground part, provide steel galvanized infrastructur

24、es and vertical, horizontal transmission rod.、classification and technical parameterclassificationaccording to current class:2000a、3150a、5000a ;according to the quantity of the enclosed earth switches:single static contact:without earthing switch、with earth switch at moving contact side、with earth s

25、witch at static contact side、with double earth switches;double static contact:without earthing switch、with earth switch at moving contact side、with earth switch at static contact side、with double earth switches at moving contact side、with earth switch at moving contact side + at static contact side、

26、three earthing switches1. main technical parameter is shown in table 1table 1no.itemunittechnical parameter1rated voltagekv2522rated currenta20003152050003disconnectorrated peak withstand currentka125160rated short-duration withstand current and durationka50/363/34earth switch rated peak withstand c

27、urrentka125rated short-duration withstand current and durationka50/35rated 1 min power frequency withstand voltage(effective value)to earthkv460across open contacts460+1456rated lightening impulse withstand voltage(peak)to earthkv1050across open contacts1050+2007switch bus bar induction current capa

28、city(bus bar transfer voltage: 400v)a25008switch tiny capacitance currenta29switch tiny inductance currenta110radio interference levelv50011mechanical life次300012rated static mechanical load of the terminal horizontal longitudinaln1500horizontal transverse1000vertical12502. product structure charact

29、eristic is shown in table 2table 2no. technical requirementparameter1open contacts insulation distance(mm)25502to earth insulation distance(mm)20003main circuit resistance()1801501004three-pole closing asynchronism of the main blade (mm)205three-pole closing asynchronism of the earth blade (mm)206cl

30、osing and opening time of incorporated motor mechanism (s)1217motor operation output corner of main blade1358manual operation output corner of earth blade90、product structure and the operation principle1. structure of the disconnectorgw23a-252 disconnector(single-pole assembly sketch is shown in pic

31、 7, three-pole assembly sketch is shown in pic 8)mainly consists of pedestal、post insulator、rotating insulator、main blade、fixed contact、 operating mechanism,etc. earth switch could be incorporated. the pedestal is composed by the channel steel and steel sheet. the lower part is designed with install

32、ation hole to fix with the foundation, the upper part is mounted with insulation post, the side is able to be installed with earth switch; and it could also be installed with mechanical interlock plate etc. the insulator, dividing into the post insulator and the rotating insulator, is made by the to

33、p-grade porcelain. it establishes the insulation to earth for the live system and guarantees the mechanical stability for the disconnector under moving or fixed load. the main blade, with single cantilever and shrinkable structure, is composed by the upper-pipe equipment、lower-pipe equipment、pedesta

34、l etc. the moving contact is equipped on the top of upper-pipe equipment and the contacting pressure is produced and held by the press tripping device (inside the upper-pipe equipment). the fixed contact is composed by the fixed contact rod , steel cored aluminum stranded wire,cross-arm aluminum she

35、et and clamp.1 rotating insulator 2 pedestal at moving contact side 3 motor operation mechanism 4 manual operation mechanism 5 post insulator 6 main blade 7 fixed contact 8 pedestal at fixed contact sidepic 1 single pole schematic 2. interlock of disconnector and earth switch(pic 2) the earth switch

36、 should not be closed when the disconnetor is at closing position, vise versa.pic 2 mechanical interlock principle3. motor operation mechanism(figure1,sequnence 3)cjtka motor mechanism-outdoor dynamic mechanism is driven by three phase ac power and conveys torque to the outgoing axle through the gea

37、r、worm and worm wheel speed reduction device. the mechanism could be designed with auxiliary switch, hand device closed or opened by manpower, heater、lightening lamp、 manual lockout switch and other components. 4. manual operation mechanism(figure1,sequnence 3)cs31 manual mechanism conveys torque to

38、 the outgoing axle through the worm and worm wheel speed reduction device. the mechanism could be designed with auxiliary switch, keyhole and electromagnetic lock if required by user. 5.1 working principle cjtka motor mechanism pushes the rotating insulator to turn 135through the connector, vertical

39、 connecting rode and pedestal rotating axle; the four-connecting-rod composed by the bent arm、connecting rods changes the force direction, drives the lower conductive tube to rotate at vertical plane. the gear rack in the lower conductive tube meshes with the wheel gear in the gearbox, the wheel gea

40、r drives the connect fork through the turning axle to force the upper conductive tube to reciprocate following the lower conductive tube. when the disconnector is near to be closed, the inclined plane on top of gearbox contacts the roller and pushes the roller to move upward along the inclined plane

41、, which pushes the pull rod to move and forces the clamping spring to be compressed and the contact finger to clamp the conductive tube of the fixed contact, applicable pressure is hold and the closing motion ends.the opening operation is contrary to this, after being folded, put the upper and lower

42、 conductive rods beside the pedestal, form a clear transverse fracture with the static connector. through the transmission turning arm, connecting pole, the two secondary active poles are connected to the transmission turning arm of the primary active pole, so as to make the three phases work simult

43、aneously. 5.2 working principle of earth switchcs31 manual mechanism pushes the turning axle of to rotate 90through the connecting rod、four-connecting-rod, the earth knife rotates at vertical plane at first, then changes into linear motion after rotating about 90until inserting into the earth fixed

44、contact and meshes correctly, the closing operation ends; the opening operation is opposite to that. the opening operation is contrary to this, the earthing blade rotates 90at the vertical plane, take the earthing static connector back to the horizontal opening position, and form a clear vertical fr

45、acture with the upper earthing static connector. the active arm of the earthing blade has the small power operation, static action, reliable closing because of the principle of the moment balance of the two sides of the lever. through the transmission turning arm, connecting pole, the secondary acti

46、ve pole is connected to the transmission turning arm of the primary active pole, so as to make the three phases work simultaneously. 、package and deliveryn typical delivery unitu conductive part will be packed as per set unit.u post insulator will be packed as per 9 pieces unit.u pedestal will be pa

47、cked as per set unit.u mounting accessories will be packed as per set unit.u earth blade rod will be packed as contract u operation mechanism;u vertical and horizontal driving link will be packed as contract.n package type the conductive part, pedestal part and transmission connecting pole adopt ste

48、el frame naked packaging, easily damaged surface is protected by the air cushion film. all the case packed delivery units such as installing accessory, earthing knife pole and operating mechanism etc. adopt the crates packing box, corresponding careful loading and unloading must be according to the

49、symbols of the box side.the design of the transport packaging must ensure the perfect protection to the possible mechanical damage and the change of the weather during the transportation,loading and unloading process. all the quality characteristics of the tested working procedure will remain unchan

50、ged during the producing process.、inspection and storageinspectionthe product should be put at dry and ventilated place. check-up should be arranged as quickly as possible. the packing list should be signed and given back to the consigner by the transporting company.check the documents and spare par

51、ts according the packing listafter inspection, if the transfer or long-term storage of the product are needed, pack them to their original state.storageit should be blocked up 10 cm or higher and put in dry and ventilated place if wont be installed in a long time(in 3 months). if it is put outdoor,

52、drainage is good and guarantee the sunshine is good. but with wooden crates, at least from the ground mat 10cm.if the storage time is less than 3 months, the electric heater neednt electricity.long-term storage (3 months above), if the equipment is indoor stored, and the warehouse is dry, the operat

53、ing mechanism should be checked every 6 months to ensure that there is no moisture inside. if the equipment is outdoor stored or in wet warehouse, please refer to the method of keeping short-term storage, and make sure that there is electricity within the heater in the operating mechanism.u、unload a

54、nd liftingu when lifting and unloading package, dont damage to equipment。u do be carefull when lifting and unloading post insulator and rotating insulator.u please open the package at site before installation and put them in unit to prevent losting at site and ensure that the hoisting equipment can

55、be conveniently.u please package material and lifting it steady in a proper way like in pic 1.pic 3a the lifting scheme of insulator pic 3b the lifting scheme of pedestalpic 3c the lifting scheme of motor mechanism pic 3d the lifting scheme of main conductorpic 3 the lifting scheme of pedestalwarnin

56、g: uthe main blade should be lifted in the opening position, do not unfasten the strapping tape of the main blade when lifting, break it when it is fixed on the post insulator and ready for adjusting. together lifting of the assembled main blade, post insulator and rotating insulator is prohibited, the damage to the conductive part, the changing of the assembling relation under the impact of changing stress

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论