1、外文资料INDUCTION MOTOR STARTING METHODS AND ISSUESAbstract - Many methods can be used to start large AC induction motors. Choices such as full voltage, reduced voltage either by auto-transformer or Wyes - Delta, a soft starter, or usage of an adjustable speed drive can all have potential advantages and

2、 trade offs. Reduced voltage starting can lower the starting torque and help prevent damage to the load. Additionally, power factor correction capacitors can be used to reduce the current, but care must be taken to size them properly. Usage of the wrong capacitors can lead to significant damage. Cho

3、osing the proper starting method for a motor will include an analysis of the power system as well as the starting load to ensure that the motor is designed to deliver the needed performance while minimizing its cost. This paper will examine the most common starting methods and their recommended appl

4、ications.Index Terms: motor starting. Reduced voltage start auto transformer, wyes-delta, power factor correctionI. INTRODUCTIONThere are several general methods of starting induction motors: full voltage, reduced voltage, wyes-delta, and part winding types. The reduced voltage type can include soli

5、d state starters, adjustable frequency drives, and autotransformers. These, along with the full voltage, or across the line starting, give the purchaser a large variety of automotives when it comes to specifying the motor to be used in a given application. Each method has its own benefits, as well a

6、s performance trade offs. Proper selection will involve a thorough investigation of any power system constraints, the load to be accelerated and the overall cost of the equipment.In order for the load to be accelerated, the motor must generate greater torque than the load requirement. In general the

7、re are three points of interest on the motors speed-torque curve. The first is locked-rotor torque (LRT) which is the minimum torque which the motor will develop at rest for all angular positions of the rotor. The second is pull-up torque (PUT) which is defined as the minimum torque developed by the

8、 motor during the period of acceleration from rest to the speed at which breakdown torque occurs. The last is the breakdown torque (BDT) which is defined as the maximum torque which the motor will develop. If any of these points are below the required load curve, then the motor will not start. The t

9、ime it takes for the motor to accelerate the load is dependent on the inertia of the load and the margin between the torque of the motor and the load curve, sometimes called accelerating torque. In general, the longer the time it takes for the motor to accelerate the load, the more heat that will be

10、 generated in the rotor bars, shorting ring and the stator winding. This heat leads to additional stresses in these parts and can have an impaction motor life.II. FULL VOLTAGEThe full voltage starting method, also known as across the line starting, is the easiest method to employ, has the lowest equ

11、ipment costs, and is the most reliable. This method utilizes a control to close a contactor and apply full line voltage to the motor terminals. This method will allow the motor to generate its highest starting torque and provide the shortest acceleration times.This method also puts the highest strai

12、n on the power system due to the high starting currents that can be typically six to seven times the normal full load current of the motor. If the motor is on a weak power system, the sudden high power draw can cause a temporary voltage drop, not only at the motor terminals, but the entire power bus

13、 feeding the starting motor. This voltage drop will cause a drop in the starting torque of the motor, and a drop in the torque of any other motor running on the power bus. The torque developed by an induction motor varies roughly as the square of the applied voltage. Therefore, depending on the amou

14、nt of voltage drop, motors running on this weak power bus could stall. In addition, many control systems monitor under voltage conditions, a second potential problem that could take a running motor offline during a full voltage start. Besides electrical variation of the power bus, a potential physic

15、al disadvantage of an across the line starting is the sudden loading seen by the driven equipment.This shock loading due to transient torques which can exceed 600% of the locked rotor torque can increase the wear on the equipment, or even cause a catastrophic failure if the load can not handle the t

16、orques generated by the motor during staring.A. Capacitors and StartingInduction motors typically have very low power factor during starting and as a result have very large reactive power draw. See Fig. 2. This effect on the system can be reduced by adding capacitors to the motor during starting.The

17、 large reactive currents required by the motor lag the applied voltage by 90 electrical degrees. This reactive power doesnt create any measurable output, but is rather the energy required for the motor to function. The product of the applied system voltage and this reactive power component can be me

18、asured in VARS (volt-ampere reactive). The capacitors act to supply a current that leads the applied voltage by 90 electrical degrees. The leading currents supplied by the capacitors cancel the lagging current demanded by the motor, reducing the amount of reactive power required to be drawn from the

19、 power system.To avoid over voltage and motor damage, great care should be used to make sure that the capacitors are removed as the motor reaches rated speed, or in the event of a loss of power so that the motor will not go into a generator mode with the magnetizing currents provided from the capaci

20、tors. This will be expanded on in the next section and in the appendix.B. Power Factor CorrectionCapacitors can also be left permanently connected to raise the full load power factor. When used in this manner they are called power factor correction capacitors. The capacitors should never be sized la

21、rger than the magnetizing current of the motor unless they can be disconnected from the motor in the event of a power loss.The addition of capacitors will change the effective open circuit time constant of the motor. The time constant indicates the time required for remaining voltage in the motor to

22、 decay to 36.8% of rated voltage after the loss of power. This is typically one to three seconds without capacitors.With capacitors connected to the leads of the motor, the capacitors can continue to supply magnetizing current after the power to the motor has been disconnected. This is indicated by

23、a longer time constant for the system. If the motor is driving a high inertia load, the motor can change over to generator action with the magnetizingCurrent from the capacitors and the shaft driven by the load. This can result in the voltage at the motor terminals actually rising to nearly 50% of r

24、ated voltage in some cases. If the power is reconnected before this voltage decays severe transients can be created which can cause significant switching currents and torques that can severely damage the motor and the driven equipment. An example of this phenomenon is outlined in the appendix.Ill. R

25、EDUCED VOLTAGEEach of the reduced voltage methods are intended to reduce the impact of motor starting current on the power system by controlling the voltage that the motor sees at the terminals. It is very important to know the characteristics of the load to be started when considering any form of r

26、educed voltage starting. The motor manufacturer will need to have the speed torque curve and the inertia of the driven equipment when they validate their design. The curve can be built from an initial, or break away torque, as few as four other data points through the speed range, and the full speed

27、 torque for the starting condition. A centrifugal or square curve can be assumed in many cases, but there are some applications where this would be problematic. An example would be screw compressors which have a much higher torque requirement at lower speeds than the more common centrifugal or fan l

28、oad. See Fig. 3. By understanding the details of the load to be started the manufacturer can make sure that the motor will be able to generate sufficient torque to start the load, with the starting method that is chosen.A. AutotransformerThe motor leads are connected to the lower voltage side of the

29、 transformer. The most common taps that are used are 80%, 65%, and 50%. At 50% voltage the current on the primary is 25% of the full voltage locked rotor amps. The motor is started with this reduced voltage, and then after a pre-set condition is reached the connection is switched to line voltage. Th

30、is condition could be a preset time, current level, bus volts, or motor speed. The change over can be done in either a closed circuit transition, or an open circuit transition method. In the open circuit method the connection to the voltage is severed as it is changed from the reduced voltage to the

31、 line level. Care should be used to make sure that there will not be problems from transients due to the switching. This potential problem can be eliminated by using the closed circuit transition. With the closed circuit method there is a continuousVoltage applied to the motor. Another benefit with

32、the autotransformer starting is in possible lower vibration and noise levels during starting. Since the torque generated by the motor will vary as the square of the applied voltage, great care should be taken to make sure that there will be sufficient accelerating torque available from the motor. A

33、speed torque curve for the driven equipment along with the inertia should be used to verify the design of the motor. A good rule of thumb is to have a minimum of 10% of the rated full load torque of the motor as a margin at all points of the curve.Additionally, the acceleration time should be evalua

34、ted to make sure that the motor has sufficient thermal capacity to handle the heat generated due to the longer acceleration time.B. Solid State or Soft StartersThese devices utilize silicon controlled rectifiers or Scars. By controlling the firing angle of the SCR the voltage that the device produce

35、s can be controlled during the starting of the motor by limiting the flow of power for only part of the duration of the sine wave. The most widely used type of soft starter is the current limiting type. A current limit of 175% to 500% of full load current is programmed in to the device. It then will

36、 ramp up the voltage applied to the motor until it reaches the limit value, and will then hold that current as the motor accelerates.Tachometers can be used with solid state starters to control acceleration time. Voltage output is adjusted as required by the starter controller to provide a constant

37、rate of acceleration.The same precautions in regards to starting torque should be followed for the soft starters as with the other reduced voltage starting methods. Another problem due to the firing angle of the SCR is that the motor could experience harmonic oscillating torques. Depending on the dr

38、iven equipment, this could lead to exciting the natural frequency of the system.C. Adjustable Frequency DrivesThis type of device gives the greatest overall control and flexibility in starting induction motors giving the most torque for an amount of current. It is also the most costly.The drive vari

39、es not only the voltage level, but also the frequency, to allow the motor to operate on a constant volt per hertz level. This allows the motor to generate full load torque throughout a large speed range, up to 10:1. During starting, 150% of rated current is typical.This allows a significant reductio

40、n in the power required to start a load and reduces the heat generated in the motor, all of which add up to greater efficiency. Usage of the AFD also can allow a smaller motor to be applied due to the significant increase of torque available lower in the speed range. The motor should still be sized

41、larger than the required horsepower of the load to be driven. The AFD allows a great degree of control in the acceleration of the load that is not as readily available with the other types of reduced voltage starting methods.The greatest drawback of the AFD is in the cost relative to the other metho

42、ds. Drives are the most costly to employ and may also require specific motor designs to be used. Based on the output signal of the drive, filtered or unfiltered, the motor could require additional construction features. These construction features include insulated bearings, shaft grounding brushes,

43、 and insulated couplings due to potential shaft current from common mode voltage. Without these features, shaft currents, which circulate through the shaft to the bearing, through the motor frame and back, create arcing in the bearings that lead to premature bearing failure, this potential for arcin

44、g needs to be considered when applying a motor/drive package in a hazardous environment, Division2/Zone2.An additional construction feature of a motor used on an AFD may require is an upgraded insulation system on the motor windings. An unfiltered output signal from a drive can create harmonic volta

45、ge spikes in the motor, stressing the insulation of the motor windings.It is important to note that the features described pertain to motors which will be started and run on an AFD. If the drive is only used for starting the motor, these features may not be necessary. Consult with the motor manufact

46、urer for application specific requirements.D. Primary Resistor or Reactor StartingThis method uses either a series resistor or reactor bank to be placed in the circuit with the motor. Resistor starting is more frequently used for smaller motors.When the motor is started, the resistor bank limits the

47、 flow of inrush current and provides for a voltage drop at the motor terminals. The resistors can be selected to provide voltage reductions up to 50%. As the motor comes up to speed, it develops a counter EMF (electro-magnetic field) that opposes the voltage applied to the motor. This further limits

48、 the inrush currents. As the inrush current diminishes, so does te voltage drop across the resistor bank allowing the torque generated by the motor to increase. At a predetermined time a device will short across the resistors and open the starting contactor effectively removing the resistor bank fro

49、m the circuit. This provides for a closed transition and eliminates the concerns due to switching transients.Reactors will tend to oppose any sudden changes in current and therefore act to limit the current during starting. They will remain shorted after starting and provide a closed transition to l

50、ine voltage.IV. INCREMENT TYPEThe first starting types that we have discussed have deal with the way the energy is applied to the motor. The next type deals with different ways the motor can be physically changed to deal with starting issues.Part WindingWith this method the stator of the motor is de

51、signed in such a way that it is made up of two separate windings. The most common method is known as the half winding method. As the name suggests, the stator is made up of two identical balanced windings. A special starter is configured so that full voltage can be applied to one half of the winding

52、, and then after a short delay, to the second half. This method can reduce the starting current by 50 to 60%, but also the starting torque. One drawback to this method is that the motor heating on the first step of the operation is greater than that normally encountered on across-the-line start. The

53、refore the elapsed time on the first step of the part winding start should be minimized. This method also increases the magnetic noise of the motor during the first step.中文译文异步电动机起动的方法和问题摘要:大容量的交流异步电动机有多种启动方法。可选择的如全压启动、降压启动、自耦变压器启动、星三角转换启动、软启动、或者使用可调速驱动器,都有潜在优势和选择。降压启动可以减小启动转矩,可以防止损坏负载。此外,功率因数校正电容器可

54、以用来减小电流,但选择的型号必须合适,否则将会造成电容器的严重损坏 。为电动机选择一个合适的启动方法,需要分析电力系统和启动负载以确保电机达到所需性能且成本最少。本文将探讨最常见的几种启动方法以及它们的应用。检索词:电机启动 降压启动 自耦变压器 星三角 功率因数校正.引言异步电动机有多种启动方法:全压启动、降压启动、星三角转换启动和部分绕组等类型。降压启动包括固态启动器、变频启动和自耦变压器启动。这些连同全压或者直接启动,当电动机的应用场合被确定后可以给购买者大量类型的变化。每种方法都有它自己的好处,以及贸易业绩。合理的选择包括对电力系统透彻的研究,负载的加速以及设备的全部成本。为了使负载能

55、够很好的加速,电动机必须产生比负载需求更大的转矩。一般来说,在机械特性曲线上集中有三点。第一点是堵转转矩(LRT),使电机由静止到旋转的最小转矩。第二点是最小启动转矩,使电机由静止加速到出现制动转矩是的最小转矩。最后一点是临街转矩,就是电机能产生的最大转矩。如果任何一段虚线在负载曲线以下,则电机就不能启动。电机的加速时间是由负载的惯性以及电机的机械特性曲线和负载的特性曲线之间的差额决定的。总的来说,电机的加速时间越长,则电机转子铜条、端环、定子绕组产生的热量也就越多。这些热量会给这些部件带来额外的压力甚至还会影响到电机的使用寿命。.全电压全压文启动的方法也叫直接启动,是最早被使用的方法,且设备

56、成本最低工作最可靠。这种方法利用一个控制器闭合电流接触器给电动机输入全压。此方法允许电动机产生最大的启动转矩使加速时间最短。由于用此方法启动电机会使启动电流达到电机额定电流的六到七倍,因此方法也是给供电系统带来最大的压力的方法。如果供电系统比较薄弱,大功率电机的突然启动不仅会使电动机的电压瞬间下降,而且会使给电机供电的整个母线端电压下降。电压下降会使此电动机的启动转矩和工作在同一母线上的电动机的转矩下降。异步电动机的转矩大约和输入电压的平方成比例变化。因此,由于电压的大幅下降,工作在此供电系统的电动机可能停车。另外许多控制系统监控器工作在低电压下,第二个全压启动时电压问题会使正在运行的电机离线

57、。同时,母线电压变化,直接启动的另一个问题驱动设备突然被加载。由于瞬时转矩可以超过转子制动转矩的600%,这个冲击负荷会增加设备的磨损,如果负载不能承受由电机启动产生的力矩,甚至会造成灾难性故障。A电容器和启动异步电动机功率因数通常很低,因此在开始有很大的感性无功。 如图2所示。 在启动时通过给电机增加电容器可以降低对系统的这种影响。电机需要大量的无功电流滞后于输入电压90度。这个无功功率不产生任何输出,但是这是电机运行所必需的。输入电压产生无功功率和这个无功功率组成的可用无功功率功率表测量。电容器担任提供一个超前90度的电流。由电容器产生的超前电流取消了电机需要的滞后电流,降低了从供电系统输

58、入的感性无功功率。避免过电压和电机损坏 应小心谨慎确保电容器被切除当电机达到额定转速时,否则由于功率损失,电动机利用由电容器提供的磁化电流将不会进入发电模式. 这将在下一段和附录中详述。B功率因数校正电容器也可永久留下提高满载功率因数,当使用这种方式时被称为功率因数校正电容器。该电容器的容量不能大于电动机的励磁电流,除非当功率降低时他们可以和电机分离。附加的电容器将会改变电机的开环时间常数,时间常数表示电机断电后电压衰减到原来的36.8%所需要的时间。没有电容的典型值是两到三秒。由于电容器和电动机的前端相连,在电机断开电源之后电容可以继续提供励磁电流。这表明该系统的时间常数较大。如果电机驱动高

59、惯性负载,电动机会利用电容提供的励磁电流和负载的带动转变为发电状态。这可能导致电机端部的电压上升到额定电压的50%。如果在电压剧烈衰减之前再次通电会产生很大的开关电流和转矩,会造成电动机和驱动设备的严重损坏。这种现象的例子在附录中有概述。.降电压每一种降压方法都是通过控制电动机的输入电压来减小电动机起动电流对供电系统的冲击。在考虑具体的降压启动方法时,了解负载特性是非常重要的。当电机制造商要确定他们的设计时必须知道电机的机械特性和被驱动设备的转动惯量。可以通过初始状态或脱离转矩,以及不少于四个速度上升的数据点和全速时的转矩构成启动状态的曲线。在很多情况下可以被假设成一个离心曲线或直角曲线,但是在一些应用场合这还是有问题的。例如螺杆式压缩机在低速时比离心式鼓风机类负载需要更大的转矩。通过详细了解负载的特性,厂商可以确定选择的启动方法可以产生足够大的力矩启动负载。A自耦变压器电动机连接在变压器的低压侧。80%、65%和50%是最常用

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论