冷藏库设计速查表,,,,,,,,,,,,,,

库内温度:-15℃~-18℃、机组配置全封闭按美国谷轮(COPELAND)和法国美优乐(MANEUROP)配置;机组配置半封闭按德国比泽尔(BIZER)配置;风机按国产风机配设。,,,,,,,,,,,,,,

序号,冷库容积(m3),贮藏吨位(T),库体外型尺寸长*宽*高(m),机组配置(HP),,,蒸发器,冷库板数量(m2),制冷机组使用工况下的制冷量(KW),,,制冷机组使用工况下的耗电量(KW),,

,,,,全封闭,,半封闭,,,全封闭,,半封闭,全封闭,,半封闭

,,,,COPELAND,MANEUROP,BIZER,,,COPELAND,MANEUROP,BIZER,COPELAND,MANEUROP,BIZER

1,15,3.7,2.94*2.94*2.5,3,MGM-36,,DD-15,46.7,,,,2.15,2.15,

2,20,5,2.94*3.92*2.2,4,MGM-50,2,DD-22,57.4,,,,2.55,2.55,1.5

3,30,7.5,4.41*3.92*2.5,4.5,MGM-64,3,DD-30,76.2,,,,3.5,3.5,2.2

4,40,10,5.39*3.92*2.5,6,MGM-80,4,DD-40,88.8,,,,4.5,4.5,3

5,50,12.5,5.39*4.9*2.5,6.5,MGM-80,4,DD-40,104.3,,,,4.8,4.8,3

6,60,15,6.37*4.9*2.5,7,MGM-100,5,DD-60,118.8,,,,5.3,5.3,3.7

7,80,20,6.86*5.88*2.6,9,MGM-125,8,DD-80,146.8,,,,6.9,6.9,5.8

8,100,25,8.82*5.88*2.5,11,MGM-160,10,DD-100,177.2,,,,8.8,8.8,7.4

9,140,35,11.76*5.88*2.5,15,MGM-100*2,12,DD-60*2,226.5,,,,10.6,10.6,9

10,180,45,15.19*5.88*2.5,18,MGM-125*2,15,DD-80*2,284,,,,13.8,13.8,11

11,200,50,16.66*5.88*2.5,22,MGM-160*2,16,DD-100*2,308.6,,,,17.6,17.6,12

12,250,63,20.58*5.88*2.5,27,MGM-125*3,20,DD-80*3,374.3,,,,20.7,20.7,15

13,300,75,24.5*5.88*2.5,33,MGM-160*3,25,DD-100*3,440,,,,26.4,26.4,18

14,370,92,30.38*5.88*2.5,36,MGM-125*4,30,DD-80*4,538.6,,,,27.6,27.6,22

15,400,100,33.32*5.88*2.5,44,MGM-160*4,32,DD-100*4,587.8,,,,35.2,35.2,23.5

1、果蔬冷却加工入库温度+35℃、库房温度-2℃、拉温时间:20H、出库温度:+4℃、机械负荷:2320W/T;冷却设备负荷:2900W/T。冷藏耗冷按:70W/T估算。,,,,,,,,,,,,,,

2、冷冻加工入库温度+35℃、库房温度-23℃、拉温时间:20H、出库温度:-15℃、机械负荷:5810W/T;冷却设备负荷:7550W/T。冷藏耗冷按:70W/T估算。,,,,,,,,,,,,,,

3、室内小型低温冷库入库温度-10℃、库房温度-18℃、出库温度:-15℃、机械负荷:120-160W/T;冷却设备负荷:156-208W/T。,,,,,,,,,,,,,,

4、盐水制冰机械负荷:7000W/T;桶式快速制冰设备负荷:7800W/T;贮冰间设备负荷:25W/T;风冷冷凝器高温时1HP配10m2面积;低温时配8m2面积;,,,,,,,,,,,,,,

保鲜库设计速查表,,,,,,,,,,,,,,

库内温度:0℃~+5℃、机组配置全封闭按美国谷轮(COPELAND)和法国美优乐(MANEUROP)配置;机组配置半封闭按德国比泽尔(BIZER)配置;风机按国产风机配设。,,,,,,,,,,,,,,

序号,冷库容积(m3),贮藏吨位(T),库体外型尺寸长*宽*高(m),机组配置(HP),,,蒸发器,冷库板数量(m2),制冷机组使用工况下的制冷量(KW),,,制冷机组使用工况下的耗电量(KW),,

,,,,全封闭,,半封闭,,,全封闭,,半封闭,全封闭,,半封闭

,,,,COPELAND,MANEUROP,BIZER,,,COPELAND,MANEUROP,BIZER,COPELAND,MANEUROP,BIZER

1,10,1.7,1.96*2.94*2.2,2.5,MGH-28,,DL-20,33.1,,,,1.86,1.86,

2,20,3.4,2.94*3.92*2.2,3,MGH-32,,DL-25,53.3,,,,1.98,1.98,

3,30,5,4.9*3.43*2.2,4,MGH-36,2,DL-25,70.3,,,,2.15,2.15,2.35

4,40,6.7,5.88*3.92*2.2,4.5,MGH-40,3,DL-40,89.2,,,,2.28,2.28,2.5

5,50,8.4,6.86*3.92*2.3,5,MGH-50,4,DL-40,103.4,,,,2.5,2.5,2.9

6,60,10,7.84*3.92*2.3,5.5,MGH-64,4,DL-55,115.6,,,,2.7,2.7,3.08

7,75,13,7.84*4.9*2.3,6,MGH-64,5,DL-55,136,,,,2.95,2.95,3.4

8,100,17,9.8*5.39*2.3,7.5,MGH-80,6,DL-40*2,175.5,,,,3.4,3.4,3.98

9,120,20,10.78*5.88*2.3,8,MGH-80,6,DL-40*2,203.4,,,,3.5,3.5,3.98

10,150,25,12.74*5.88*2.3,8.5,MGH-100,8,DL-55*2,235,,,,4.3,4.3,4.9

11,170,29,14.21*5.88*2.4,10.5,MGH-125,9,DL-60*2,263.6,,,,4.8,4.8,5.73

12,190,32,14.7*5.88*2.5,11,MGH-125,10,DL-60*2,275.8,,,,4.86,4.86,5.8

13,240,40,18.62*5.88*2.5,13,MGH-160,12,DL-80*2,341.5,,,,5.8,5.8,7.2

14,300,50,23.52*5.88*2.5,17,MGH-100*2,15,DL-55*4,423.6,,,,7,7,7.6

15,380,64,29.4*5.88*2.5,21,MGH-125*2,18,DL-60*4,522,,,,8.3,8.3,9.8

1、果蔬冷却加工入库温度+35℃、库房温度-2℃、拉温时间:20H、出库温度:+4℃、机械负荷:2320W/T;冷却设备负荷:2900W/T。冷藏耗冷按:70W/T估算。,,,,,,,,,,,,,,

2、冷冻加工入库温度+35℃、库房温度-23℃、拉温时间:20H、出库温度:-15℃、机械负荷:5810W/T;冷却设备负荷:7550W/T。冷藏耗冷按:70W/T估算。,,,,,,,,,,,,,,

3、室内小型低温冷库入库温度-10℃、库房温度-18℃、出库温度:-15℃、机械负荷:120-160W/T;冷却设备负荷:156-208W/T。,,,,,,,,,,,,,,

4、盐水制冰机械负荷:7000W/T;桶式快速制冰设备负荷:7800W/T;贮冰间设备负荷:25W/T;风冷冷凝器高温时1HP配10m2面积;低温时配8m2面积;,,,,,,,,,,,,,,

冷冻库设计速查表,,,,,,,,,,,,,,

库内温度:-21℃--26℃、机组配置半封闭按德国比泽尔(BIZER)配置;风机按国产风机配设。,,,,,,,,,,,,,,

序号,冷库容积(m3),贮藏吨位(T),库体外型尺寸长*宽*高(m),机组配置(HP),,,蒸发器,冷库板数量(m2),制冷机组使用工况下的制冷量(KW),,,制冷机组使用工况下的耗电量(KW),,

,,,,,,半封闭,,,,,半封闭,,,半封闭

,,,,,,BIZER,,,,,BIZER,,,BIZER

1,8,,2.4*2.4*2.4,,,4,DJ-15,,,,,,,3-3.2

2,12,,3.6*2.4*2.4,,,4,DJ-15,,,,,,,3-3.2

3,16,,3.6*3.0*2.4,,,5~6,DJ-20,,,,,,,4.5-5

4,20,,3.6*3.6*2.4,,,6.5-7.5,DJ-20,,,,,,,5.5-6.5

5,24,,4.2*3.6*2.4,,,7.5-8.5,DJ-30,,,,,,,7-7.5

6,32,,4.8*3.6*2.65,,,8.5-10,DJ-40,,,,,,,8-8.5

7,40,,5.4*4.2*2.5,,,12.-14,DJ-60,,,,,,,9_10

1、果蔬冷却加工入库温度+35℃、库房温度-2℃、拉温时间:20H、出库温度:+4℃、机械负荷:2320W/T;冷却设备负荷:2900W/T。冷藏耗冷按:70W/T估算。,,,,,,,,,,,,,,

2、冷冻加工入库温度+35℃、库房温度-23℃、拉温时间:20H、出库温度:-15℃、机械负荷:5810W/T;冷却设备负荷:75

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论