《建筑防排烟系统技术标准》GB51251-2017防排烟计算表_第1页
《建筑防排烟系统技术标准》GB51251-2017防排烟计算表_第2页
《建筑防排烟系统技术标准》GB51251-2017防排烟计算表_第3页
《建筑防排烟系统技术标准》GB51251-2017防排烟计算表_第4页
《建筑防排烟系统技术标准》GB51251-2017防排烟计算表_第5页
已阅读5页,还剩14页未读 继续免费阅读

下载本文档

版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领

文档简介

防排烟前室、楼梯间加压送风量计算表,,,,,,,,,,,,,,,,,,,,"★取值说明:

●v-门洞断面风速;楼梯间、前室均送风0.7m/s;楼梯间送风,独立前室不送风1.0m/s;消防电梯前室送风1.0m/s;楼梯间自然通风,前室送风0.6(楼梯间门总面积/前室门总面积+1)m/s;

●△P-漏风门平均压差;0.7m/s时,6.0Pa;1.0m/s时,12Pa;1.2m/s时,17Pa;

●N1-疏散门开启数量;楼梯间:24m以下,2层内疏散门开启,取2;24m以上,3层内疏散门开启,取3;地下楼梯间,1层内疏散门开启,取1;前室,取3,<3层的按实际层数取;

●N2-漏风门数量;加压楼梯间总门数-N1;

●N3-漏风阀门数量;前室楼层数-3;

●A-单个门漏风面积;1.5m*2.0m,0.018m2;1.2m*2.0m,0.0168m2;1.2m*2.0m,0.012m2",,,

系统编号,消防加压送风部位,,前室送风量,楼梯间送风量,门缝面积,平均压差,漏风门数量,门缝漏风量,门洞面积,门洞风速,开启门数,门洞送风量,阀门面积,漏风阀门数量,阀门漏风量,计算风量,风道截面,风口截面,设计风量,,,,

,层数,部位,Ls=L1+L3(m3/h),Lj=L1+L2(m3/h),A,△P,N2,L2,Ak,v,N1,L1,AF,N3,L3,,按15m/s,按5m/s,,,,,

,,,,,(㎡),(Pa),(个),(m3/s),(㎡),(m/s),(个),(m3/s),(㎡),(个),(m3/s),(m3/h),(㎡),(㎡),(m3/h),,,,

,1,合用前室(1个门),8100,,,,,,3.2,0.70,1,2.24,0.45,0,0.00,8100,0.15,0.45,9720,,,,

,,楼梯间(带前室),,16200,0.018,6,0,0.00,3.2,0.70,2,4.48,,,,16200,0.30,0.90,19440,,表5.1.1-1消防电梯前室的加压送风量,,

,,楼梯间(独立),,29300,0.031,12,4,0.44,3.8,1.00,2,7.68,,,,29300,0.54,1.63,35160,,系统负担高度h(m),加压送风量(m3/h),

,2,合用前室(1个门),16200,,,,,,3.2,0.70,2,4.48,0.45,0,0.00,16200,0.30,0.45,19440,,24≤h<50,"13,800~15,700",

,,楼梯间(带前室),,16200,0.018,6,0,0.00,3.2,0.70,2,4.48,,,,16200,0.30,0.45,19440,,50≤h<100,"16,000~20,000",

,,楼梯间(独立),,40000,0.031,12,4,0.44,3.8,0.70,4,10.64,,,,40000,0.74,1.11,48000,,,,

,3,合用前室(1个门),24200,,,,,,3.2,0.70,3,6.72,0.45,0,0.00,24200,0.45,0.45,29040,,表5.1.1-2楼梯间自然通风,前室、合用前室的加压送风量,,

,,楼梯间(带前室),,16300,0.018,6,1,0.05,3.2,0.70,2,4.48,,,,16300,0.30,0.30,19560,,系统负担高度h(m),加压送风量(m3/h),

,,楼梯间(独立),,16300,0.018,6,1,0.05,3.2,0.70,2,4.48,,,,16300,0.30,0.30,19560,,24<h≤50,"16,300~18,100",

,6,合用前室(1个门),24700,,,,,,3.2,0.70,3,6.72,0.46,3,0.11,24700,0.46,0.46,29640,,50<h≤100,"18,400~22,000",

,,楼梯间(带前室),,16800,0.018,6,4,0.18,3.2,0.70,2,4.48,,,,16800,0.31,0.47,20160,,,,

,,楼梯间(独立),,16800,0.018,6,4,0.18,3.2,0.70,2,4.48,,,,16800,0.31,0.47,20160,,表5.1.1-3前室不送风,封闭楼梯间、防烟楼梯间的楼梯间加压送风量,,

,8,合用前室(1个门),24900,,,,,,3.2,0.70,3,6.72,0.46,5,0.19,24900,0.46,0.46,29880,,系统负担高度h(m),加压送风量(m3/h),

,,楼梯间(带前室),,17200,0.018,6,6,0.27,3.2,0.70,2,4.48,,,,17200,0.32,0.32,20640,,24<h≤50,"25,400~28,700",

,,楼梯间(独立),,17200,0.018,6,6,0.27,3.2,0.70,2,4.48,,,,17200,0.32,0.32,20640,,50<h≤100,"40,000~46,400",

,12,合用前室(1个门),25200,,,,,,3.2,0.70,3,6.72,0.35,9,0.26,25200,0.47,0.35,30240,,,,

,,楼梯间(带前室),,26300,0.018,12,9,0.58,3.2,0.70,3,6.72,,,,26300,0.49,0.49,31560,,表5.1.1-4防烟楼梯间的楼梯间及合用前室的分别加压送风量,,

,,楼梯间(独立),,26300,0.018,12,9,0.58,3.2,0.70,3,6.72,,,,26300,0.49,0.37,31560,,系统负担高度h(m),送风部位,加压送风量(m3/h)

,18,合用前室(1个门),26400,,,,,,3.2,0.70,3,6.72,0.49,15,0.61,26400,0.49,0.49,31680,,24<h≤50,楼梯间,"17,800~20,200"

,,楼梯间(带前室),,26700,0.018,6,15,0.68,3.2,0.70,3,6.72,,,,26700,0.49,0.25,32040,,,合用前室,"10,200~12,000"

,,楼梯间(独立),,26700,0.018,6,15,0.68,3.2,0.70,3,6.72,,,,26700,0.49,0.25,32040,,50<h≤100,楼梯间,"28,200~32,600"

,20,合用前室(1个门),26800,,,,,,3.2,0.70,3,6.72,0.50,17,0.71,26800,0.50,0.50,32160,,,合用前室,"12,300~15,800"

,,楼梯间(带前室),,27000,0.018,6,17,0.77,3.2,0.70,3,6.72,,,,27000,0.50,0.21,32400,,,,

,,楼梯间(独立),,27000,0.018,6,17,0.77,3.2,0.70,3,6.72,,,,27000,0.50,0.21,32400,,注:1表5.1.1-1至表5.1.1-4的风量按开启2.0m×1.6m的双扇门确定。当采用单扇门时,,,

,24,合用前室(1个门),27400,,,,,,3.2,0.70,3,6.72,0.51,21,0.89,27400,0.51,0.51,32880,,"其风量可乘以0.75系数计算,当设有多个疏散门时,其风量应乘以开启疏散门的数量,最",,

,,楼梯间(带前室),,27700,0.018,6,21,0.96,3.2,0.70,3,6.72,,,,27700,0.51,0.19,33240,,多按3扇疏散门开启计算;,,

,,楼梯间(独立),,27700,0.018,6,21,0.96,3.2,0.70,3,6.72,,,,27700,0.51,0.19,33240,,2表5.1.1-1至表5.1.1-4中未考虑防火分区跨越楼层时的情况;当防火分区跨越楼层时应按照本规范公式5.1.4~公式5.1.7重新计算;,,

,26,合用前室(1个门),27700,,,,,,3.2,0.70,3,6.72,0.51,23,0.97,27700,0.51,0.51,33240,,3表中风量的选取应按建筑高度或层数、风道材料、防火门漏风量等因素综合确定。,,

,,楼梯间(带前室),,28000,0.018,6,23,1.05,3.2,0.70,3,6.72,,,,28000,0.52,0.17,33600,,,,

,,楼梯间(独立),,28000,0.018,6,23,1.05,3.2,0.70,3,6.72,,,,28000,0.52,0.17,33600,,,,

,28,合用前室(1个门),28100,,,,,,3.2,0.70,3,6.72,0.52,25,1.

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论