DELTAV设备状态指示灯:
CheckingtheLEDIndicatorsonEachDevice
TheLEDindicatorsonthesystemdevicesshowimportantbasicoperatingdata.Usethefollowingcheckliststomakesureyourdevicesareworkingcorrectly.
Table
3-1
liststheLEDindicatorsfortheSystemPowerSupply(AC/DC)andtheSystemPowerSupply(DualDC/DC).
Table3-1SystemPowerSupplyLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Powerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On
1.Outputsareoutsideoftolerance.
1.Verifyloading
calculations.
2.Inputovervoltage.Unitshutsdown.
2.Checkinputsupplyvoltages.
Table
3-2
liststheLEDindicatorsfortheMD,MDPlus,andMXcontrollers.
Table3-2MD,MDPlus,andMXControllerLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
Internalfault.
Contacttechnicalsupport.
OnforonesecondfollowedbyallLEDsonforfiveseconds.
UnitwentthroughRESETduetoanunrecoverablesoftwareerror.
Contactcustomersupport.
Flashing
Thecontrollerisdecommissioned.
Commissionthecontroller.
Green-Active
On
Off
1.ControllerisaStandby.
1.None-GreenStandbyison.
2.Controllernotcommissioned.
2.Commissioncontroller.
3.Internalfault.
3.Contacttechnicalsupport.
Flashing
Controllerisnotconfigured.
Downloadcontrollerconfiguration.
Green-Standby
Off
On
ControllerisaStandby.
None
Flashing
Controllerisnotconfigured.
Downloadcontrollerconfiguration.
Yellow-
Pri.CN
Communicationsattemptedandindicatorflashing
Off-Communicationsattemptedandindicatornotflashing.
ControllerlacksactiveEthernetcommunicationsonprimaryControlNetworkconnection.
Checkprimarynetworkcableconnectionsandhubconnections.
Yellow-
Sec.CN
Communicationsattemptedandindicatorflashing
Off-Communicationsattemptedandindicatornotflashing.
ControllerlacksactiveEthernetcommunicationsonsecondaryControlNetworkconnection.
Checksecondarynetworkcableconnectionsandhubconnections.
Table
3-3
liststheLEDindicatorsfortheRemoteInterfaceUnit.
Table3-3RemoteInterfaceUnitLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
Internalfault.
Contacttechnicalsupport.
OnforonesecondfollowedbyallLEDsonforfiveseconds.
UnitwentthroughRESETduetoanunrecoverablesoftwareerror.
Contactcustomersupport.
Flashing
TheRemoteInterfaceUnitisdecommissioned.
CommissiontheRemoteInterfaceUnit.
Green-Active
On
Off
1.RemoteInterfaceUnitisnotcommissioned.
1.CommissiontheRemoteInterfaceUnit.
2.Internalfault.
2.Contacttechnicalsupport.
Flashing
RemoteInterfaceUnitisnotconfigured.
Downloadconfiguration.
Green-Standby
Off
(Redundancynotsupported)
Yellow-
Pri.CN
Communicationsattemptedandindicatorflashing
Off-Communicationsattemptedandindicatornotflashing.
RemoteInterfaceUnitlacksactiveEthernetcommunicationsonprimaryControlNetworkconnection.
Checkprimarynetworkcableconnectionsandhubconnections.
Yellow-
Sec.CN
Communicationsattemptedandindicatorflashing
Off-Communicationsattemptedandindicatornotflashing.
RemoteInterfaceUnitlacksactiveEthernetcommunicationsonsecondaryControlNetworkconnection.
Checksecondarynetworkcableconnectionsandhubconnections.
Table
3-4
liststheLEDindicatorsforthemediaconverter.
Table3-4MediaConverterLEDChecklist
LED
CorrectOperatingConditions
FaultIndicators
PossibleCause
CorrectiveAction
Green-Power
On
Off
Powerisnotsuppliedtounit.Possiblelinepowerproblem.
Checkpowersupplyandconnections.
Red-Error
Off
On
Internalfault.
Contacttechnical
support.
Green-Pri.FLnk
On
Off
Fiber-opticcableisincorrectly
connected.
Checkfiber-optic
cableconnection.
(Connectstransmittoreceive.)
Green-Pri.CLnk
On
Off
Twistedpair
cableisincorrectlyconnected.
Checkcablepinouts.Referto
Figure
G-47
.
Green-Sec.FLnk
On
Off
Fiber-opticcableisincorrectly
connected.
Checkfiber-optic
cableconnection.(Connectstransmittoreceive.)
Green-Sec.CLnk
On
Off
Twistedpair
cableisincorrectlyconnected.
Checkcablepinouts.Referto
Figure
G-47
.
Table
3-5
liststhepowerLEDindicatorsontheSinglePortandFourPortFiberSwitches.
Table3-5SingleandFourPortFiberSwitchPowerLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
Internalfault.
Contacttechnicalsupport.
Table
3-6
liststhetwistedpairports'LEDindicatorsontheSingleandFourPortFiberSwitches.
Table3-6SingleandFourPortFiberSwitchTwistedPairPortLEDChecklist
LED
Status
LinkAct
On-Link
Blinking-Activity
Off-Nolink.Checkthecableconnection.
FDCOL
On-FullDuplex
Blinking-Collision
Off-HalfDuplex
10010
On-100MHz
Off-10MHz
Table
3-7
liststhefiber-opticports'LEDindicatorsontheSingleandFourPortFiberSwitches.
Table3-7SingleandFourPortFiberSwitchFiber-OpticPortLEDChecklist
LED
Status
LinkAct
On-LinK
Blinking-Activity
Off-Nolink
Table
3-8
liststhepowerLEDindicatorsontheDeltaVControllerFirewall.
Table3-8DeltaVControllerFirewallPowerLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-PowerSupply1(P1),PowerSupply2(P2)
On
Off
Systempowerisnotsuppliedtounitorvoltageislessthan9.6VDC.
Checksupplypowerandconnections.
Red-Fault
Off
On
Internalfault.
Contacttechnicalsupport.
Table
3-9
liststhedevicestatusLEDindicatorsontheDeltaVControllerFirewall.
Table3-9DeltaVControllerFirewallDeviceStatusLEDChecklist
LED
Status
STATUS-Devicestatus
Flashinggreen-deviceisinitializing
Solidgreen-Deviceisoperational
Table
3-10
liststhetwistedpairports'LEDindicatorsontheDeltaVControllerFirewall.
Table3-10DeltaVControllerFirewallTwistedPairPorts'LEDChecklist
LED
Status
LS/DA1,2,V.24-Linkstatus
Solidgreen-validlink
Blinkinggreen-portisdisabled
Runninglight-initializationphaseafterareset
Off-nolink.Checkthecableconnection.
Table
3-11
liststheLEDindicatorsforthepre-Series2andSeries2AI,8-channel,
4-20mAcard;theAI,8-channel,4-20mA,HARTcard;andtheAI,8-channel,1-5VDCcard.
Table3-11AICardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupply
powerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
pre-Series2andSeries2On
(continuous)
1.Nobussedfieldpower.
1.Checkbussedfieldpowerandconnections.
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
3.Unitfailedself-test.
3.Contacttechnicalsupport.
pre-Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Redundant
Series2Flashing
1.Nobussedfieldpower.
1.Checkbussedfieldpowerandconnections.UsetheDeltaV
DiagnosticsClearSavedFaultInformationcommandwhenproblemfixed.
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
3.Hardwareerror.
3.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
SimplexSeries2Flashing
Controllerisnotscanningcard.
Checkcontrolleroperation.
Yellow-
Ch.1toCh.8
On
Off
1.Inputisoutofrangeandchannelisdisabled.(Seespecificationsin
AppendixC
forcorrectrange.)
1.Checkinputsourceandconnections.
2.Nobussedfieldpower.
2.Checkbussedfieldpowerandconnections.
3.Internalfault.
3.Contacttechnicalsupport.
Flashing
1.Inputisoutofrangeandchannelisdisabled.(Seespecificationsin
AppendixC
forcorrectrange.)
1.Checkinputsourceandconnections.
2.Nobussedfieldpower.
2.Checkbussedfieldpowerandconnections.
3.ChannelisconfiguredforHART,butthereisnoHARTcommunication.
3.CheckHARTinputsourceandconnections.
4.ChannelisconfiguredforNAMURlimitsandtheyhavebeenexceeded.
4.CheckinputlevelscomparedtoNAMURlimits.
RefertotheonlineConfigurationmanualformoreinformationontroubleshootingHARTdevices.
Referto
GettingHelp
forinformationonaccessingtheDeltaVonlinebooks.
Table
3-12
liststheLEDindicatorsfortheSeries2AI,16-Channel,40-20mA,HARTcardinSimplexmode.
Table3-12AI16-ChannelCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On
1.Nobussedfieldpower.
1.Checkbussedfieldpowerandconnections.
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
3.Unitfailedself-test.
3.Contacttechnicalsupport.
Flashing
1.Nobussedfieldpower.
1.Checkbussedfieldpowerandconnections
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
3.Hardwareerror.
3.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-13
liststheLEDindicatorsforthepre-Series2andSeries2AO,8-channel
4-20mAcardandtheAO,8-channel,4-20mA,HARTcard.
Table3-13AOCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblems.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
pre-Series2andSeries2On(continuous)
1.Unitfailedself-test.
1.Contacttechnicalsupport.
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
pre-Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailed
self-test.
2.Contacttechnicalsupport.
3.Addressconflict.
3.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
RedundantSeries2Flashing
1.Nobussedfieldpower.
1.Checkbussedfieldpowerandconnections.UsetheDeltaVDiagnosticsClearSavedFault
Informationcommandwhenproblemfixed.
2.Controllerisnotscanningcard.
2.Checkcontrolleroperation.
3.Hardwareerror.
3.Replacewithknowngoodcardofsametype;contacttechnicalsupport.
SimplexSeries2Flashing
Controllerisnotscanningcard.
Checkcontrolleroperation.
Yellow-Ch.1to
Ch.8
On
Off
1.Nooutputdevice(load)andchannelisdisabled.
1.Checkoutput
connections.
2.Bussedfield
powernotsuppliedtounit.
2.Checkbussedfieldpowerand
communications.
3.Internalfault.
3.Contacttechnicalsupport.
Flashing
1.Nooutputdevice(load)andchannelisenabled.
1.Checkoutputconnections.
2.Bussedfieldpowernotsuppliedtounit.
2.Checkbussedfieldpowerand
connections.
3.ChannelisconfiguredforHART,butthereisnoHARTcommunication.
3.CheckHARTinputsourceandconnections.
4.Internalfault.
4.Contacttechnicalsupport.
RefertotheonlineConfigurationmanualformoreinformationontroubleshootingHARTdevices.
Referto
GettingHelp
forinformationonaccessingtheDeltaVonlinebooks.
Table
3-14
liststheLEDindicatorsfortheAS-Interfacecard
Table3-14AS-InterfaceCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailed
self-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Address
conflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Port1andPort2
On
Off
Nocommunications.
Checkconnections,cable,andexternaldevice.
Flashing
Communicationserroronthisport.
Checkconnections,cable,andexternaldevice.
Table
3-15
liststheLEDindicatorsfortheDeviceNetandSeries2DeviceNetcards.
Table3-15DeviceNetCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Port1
Port2(reserved)
On
Off
1.Nocommunications.
1.Checkconnections,cable,andexternaldevice.
2.Portnotenabled.
2.Enableport.
3.Noconfigurationforthisport.
3.Configureport.
Flashing
Communicationerroronthisport.
Checkconnections,cable,andexternaldevice.
Table
3-16
liststheLEDindicatorsforthepre-Series2andSeries28-channelDIcards(24VDCisolatedanddrycontact,and120/230VACisolatedanddrycontract)
Table3-16DICardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
pre-Series2andSeries2On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
pre-Series2-Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacewithknowngoodcardofsametype;contacttechnicalsupport.
Series2-Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Hardwareerror.
2.Replacewithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Ch.1toCh.8
On=input>detectionlevel.
Off=input<detectionlevel.Seetablesin
AppendixC
fordetectionlevelsforeachDIcardtype.
.
Table
3-17
liststheLEDindicatorsfortheDI,32-channel,24VDC,drycontactandtheSeries2DI,32-channel,24VDC,drycontact.
Table3-17DI,32-channel,24VDC,DryContactCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Powerisnotsuppliedtounit.
1.Checksupply
powerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On
(continuous)
Communicationserror.
Checkconnections,cable,andexternaldevice.
Flashing
Address
conflict.
Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-18
liststheLEDindicatorsforthepre-Series2andSeries28-channel,DOcards(120VAC/230VACisolatedandhighsideand24VDCisolatedandhighside).
Table3-18DOCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red
Off
pre-Series2andSeries2On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
pre-Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacewithknowngoodcardofsametype;contacttechnicalsupport.
Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Hardwareerror.
2.Replacewithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Ch.1toCh.8
Dependsonsetpointandconfiguration.
Table
3-19
liststheLEDindicatorsfortheDO,32-channel,24VDC,high-sideandSeries2DO,32-channel,24VDC,high-side.
Table3-19DO,32-Channel,24VDC,High-SideCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Powerisnotsuppliedtounit.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
Communicationserror.
Checkconnections,cable,andexternaldevice.
Flashing
Addressconflict.
Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-20
liststheLEDindicatorsfortheFieldbusH1cardandtheSeries2FieldbusH1card.
Table3-20FieldbusH1Checklist
LED
CorrectOperating
Condition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
pre-Series2
Flashing
Series2
Flashing
Series2Red:
Active-Flashing
Stby-Flashing
Incorrectterminalblockforconfiguredcardtype.
InstallredundantterminalblocksforSeries2redundantcardsandsimplexterminalblocksforsimplexand/orpre-Series2cards.
Red-Error
Off
pre-Series2andSeries2
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
pre-Series2
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Hardwareerror.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Port1
andPort2
On
Off
1.Nocommunications.
1.Checkconnections,cableandexternaldevices.
2.Portnotenabled.
2.Enableport.
3.Configurationmismatch.(Suchasredundantcardconfiguredindatabaseandsimplexcardinstalled.)
3.Fixconfigurationerrors.
Flashing
1.Communicationerroronthisport.
1.Checkconnections,cable,andexternaldevice.
2.Noconfigurationforthisport.
2.Configureport.
Table
3-21
liststheLEDindicatorsfortheSeries2IsolatedInputcard.
Table3-21Series2IsolatedInputCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndicators
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(Continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-22
liststheLEDindicatorsfortheMultifunctioncard.
Table3-22MultifunctionCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-23
liststheLEDindicatorsfortheProfibusDP,Series2ProfibusDP(Simplex)andSeries2PlusProfibusDP(SimplexandRedundant)cards.
Table3-23ProfibusDPCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
ProfibusDP-On
Series2ProfibusDPSimplex-On
Series2PlusProfibusDPRedundant
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailed
self-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Port1
Port2(reserved)
On
Off
1.Nocommunications.
1.Checkconnections,cable,andexternaldevice.
2.Portnotenabled.
2.Enableport.
3.Noconfigurationforthisport.
3.Configureport.
Flashing
Communicationerroronthisport.
Checkconnections,cable,andexternaldevice.
Table
3-24
liststheLEDindicatorsfortheRTD,ohmsandThermocouple,mVcards.
Table3-24RTD,ohmsandThermocouple,mVLEDChecklist
LED
CorrectOperatingConditions
FaultIndicators
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Ch.1toCh.8
On
Off
1.Channelnotconfigured.
1.Enablechannelanddownloadcard.
2.Internalfault.
2.Contacttechnicalsupport.
Flashing
1.Invalidconfiguration.
1.Checkconfiguration.
2.Inputisoutofrange.(Seespecificationsin
AppendixC
forcorrectrange.)
2.Checkinputsourceandconnections.
3.Internalfault.
3.Contacttechnicalsupport.
Table
3-25
liststheLEDindicatorsfortheSequenceofEventscard.
Table3-25SequenceofEventsCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Powerisnotsuppliedtounit.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
Communicationserror.
Checkconnections,cable,andexternaldevice.
Flashing
Addressconflict.
Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Table
3-26
liststheLEDindicatorsforthepre-Series2andSeries2SerialCard,2Ports,RS232/RS485.
Table3-26SerialCardLEDChecklist
LED
CorrectOperatingCondition
FaultIndication
ProbableCause
CorrectiveAction
Green-Power
GreenPower/Active
pre-Series2-On
Series2Simplex-On
Series2Redundant:
Active-On
Standby-Flashing
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
pre-Series2andSeries2-On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
pre-Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Series2Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Hardwareerror.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-Port1andPort2(configuredasMaster)
On
Off
Nocommunications.
Checkconnections,cable,andexternaldevice.
Flashing
Communicationserroronthisport.
Checkconnections,cable,andexternaldevice.
Yellow-Port1andPort2(configuredasSlave)
On-Communicating
Off-Nocommunication
Flashing-Intermittentcommunication
Table
3-27
liststheLEDindicatorsfortheI.S.AI,8-Channel,4-20mAHARTcard.
Table3-27I.S.AI,8-Channel,4-20mA,HARTCardLEDChecklist
LED
CorrectOperatingConditions
FaultIndications
ProbableCause
CorrectiveAction
Green-Power
On
Off
1.Systempowerisnotsuppliedtounit.Possiblelinepowerproblem.
1.Checksupplypowerandconnections.
2.Internalfault.
2.Contacttechnicalsupport.
Red-Error
Off
On(continuous)
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Unitfailedself-test.
2.Contacttechnicalsupport.
Flashing
1.Controllerisnotscanningcard.
1.Checkcontrolleroperation.
2.Addressconflict.
2.Replacecardwithknowngoodcardofsametype;contacttechnicalsupport.
Yellow-
Ch.1toCh.8
On
Off
1.Inputisoutofrange.(Seespecificationsin
AppendixC
forcorrectrange.)
1.Checkinputsourceandconnectio
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 分配方案异议申请书
- 土地非诉行政执行“裁执分离”制度研究
- 部分功率双向DC-DC变换器拓扑结构研究
- 2025至2030年电热设备粉云母板项目投资价值分析报告
- 2025至2030年分鱼用刀叉连盒项目投资价值分析报告
- 基于多因子分析和TCN-CBAM-BiGRU模型的股价预测研究
- 2025年防水压力传感器项目可行性研究报告
- 2025年立式滑板注塑机项目可行性研究报告
- 公司转让代销合同范本
- 农场转让设备合同范本
- 供电工程施工方案(技术标)
- 2023届江西省九江市高三第一次高考模拟统一考试(一模)文综试题 附答案
- 2024年共青团入团积极分子、发展对象考试题库及答案
- DBJ∕T 13-478-2024 福建省瓶装液化石油气信息管理与数据采集技术标准
- 2025年度院感管理工作计划(后附表格版)
- 化肥销售工作计划
- 2024浙江华数广电网络股份限公司招聘精英18人易考易错模拟试题(共500题)试卷后附参考答案
- 飞行器小学生课件
- 2024年山东省济南市中考英语试题卷(含答案解析)
- 2024年定融认购协议合同范文
- 2024年社区警务规范考试题库
评论
0/150
提交评论