德国赛巴TDR实测海底电力电缆波形第1页/共96页HVDC-Cable–200kmUndersea-cable

withafewjointsCablewith

numerousjointsHV-CabelØ120mm(c)SebaKMT,allrightsreserved第2页/共96页HVDC–Cable-200km:TDR–TeleflexVXSeaCable

openendSeaCable

withJoints(c)SebaKMT,allrightsreserved第3页/共96页HVDC-Cable–200km:TDR-JointsOverlandcable

withjoints(c)SebaKMT,allrightsreserved第4页/共96页TheTeleflexVXin19”FormatTeleflexVX,(c)SebaKMT2012,allrightsreserved5第5页/共96页ProRangeTeleflexVX,(c)SebaKMT2012,allrightsreserved6Distancedependingamplitudede-attenuation

asknownfromourTelecomunits.Important:

Thisisnotarampgain,butanexponentialde-attenuation!De-attenuation=offDe-attenuation=onCable:4x1km=4km;TypeRG58withopenend

WithactivatedProRangefunction,theendistmuchbettervisible第6页/共96页AdjustabletracethicknessTeleflexVX,(c)SebaKMT2012,allrightsreserved7Thesystemsbecomebetter,moreaccurateandhaveahigherresolution

Problem:Thetraceshowstoomanydetailsandthesedetailscan

beconfusing.Nowitispossibletoshowthetracewithathickerline,SameforprintingThetracethicknessisadjustablefrom1to9pixels.第7页/共96页19”InstallationversionsTeleflexVX,(c)SebaKMT2012,allrightsreserved8118304460 TeleflexVX-ClassicTeleflexVXin19“designassystemintegrationversionforClassicandothercomparablefaultlocationsystems.

(FornewSystemsandretrofitofexistingsystems)InclusiveadaptationsettotheClassicSystem15"SXGATFTDisplaywithCCFL-backlight,300cd/m²118308241 TeleflexVX-R30TeleflexVXin19“designassystemintegrationversionforR30andothercomparablefaultlocationsystems(FornewSystemsandretrofitofexistingsystems)InclusiveadaptationsettotheR30System

15"SXGATFTDisplaywithCCFL-backlight,300cd/m²第8页/共96页TeleflexVXPortableTeleflexVX,(c)SebaKMT2012,allrightsreserved9118308242 TFXVXPTeleflexVXPportablewithcaseAsStandAloneVersionforthedirectreflectionmeasurementorascombinationwithotherfaultlocationequipment.15"SXGATFTDisplaywithCCFL-backlight,300cd/m²Releasedate:Autumn2012第9页/共96页DataParameterTeleflexMXTeleflexVXMeasuringrange@80m/µs50m…160km20m…1280kmPulseamplitudeNotadjustablemax.55VAdjustablefrom30…160V0,1mby80m/µs0,1m@80m/µs,1,0cm@V/2<40m/µs„Real“sampleRateUpto100MHzUpto400MHzGain-42dB…+54dB,

-37…+37dBPulsewidth50ns…5µs20ns…10µsCompensation25,4Ω…1,6kΩandoff=∞8Ω…2kΩandoff=∞ARMTriggerTriggerlevelinfoursteps,250mVto2VAutomaticbyΔU-Trigger.DelaytimeNotadjustableAdjustablefrom

0…7msin256µsStepsDistancedependingde-attenuationNotavailableProRange0…100%,max.22dB)ARMslideNotavailable15ARM-SlideMeasurementsinoneshotCloserangeresolutionSmalllimitationsOptimisedinputcircuitMemoryFlash256MBforDataandProgram2GBforProgrammand

2GBforDataHighsafetybyseparatedhardware2GBinternalforrecoveryOperatingsystemLinuxKernel2.4LinuxKernel6.2InternalRecoveryNotavailableHighsafetybyRecoverysystemUSBV1.1V2.0ExternalcouplingviaISA-BUSviaEthernetDisplayStandard(analogue)17"TFTSXGA,CCFL-Backlight,300cd/m²KühlungCoolerfanforDisplayNocoolingfanrequiredRemoteDesktopf.OWTSAnbindungNotavailableAvailableTracethickness1PixelTracethicknessadjustableTeleflexVX,(c)SebaKMT2012,allrightsreserved10第10页/共96页11SebaKMT–Productrange2.ComprehensiveFaultLocationSystems:

EZGenerationSurgeflex–Portable,fullyautomaticfaultlocationsystemR30–Cablefaultlocationsystemupto400kV

DigiphonePlus–Excellentsurgewavereceiverforacousticandelectromagneticfaultpinpointing

MFM-10-SheathFaultLocationSystemTesting,PrelocationandPinpointingofsheathfaults

ESGNT–Earthfaultlocator

(c)SebaKMT,allrightsreserved第11页/共96页

Thenew“EZ”GenerationTheEZGeneration12第12页/共96页TheEZGeneration132ndGenerationEZ-RESTOREOVERDRIVE2ndGenerationEZ-THUMP2ndGenerationSMART-THUMPT3060

IRG2000BaurKillerNewGenerationSURGEFLEXT3090

T3050SuccessorSMARTE-TRAYOverwiewoftheE-TRAYProduktline

第13页/共96页EasiestOperationandHandlingWiththedevelopmentofthe“EZ”productline,SebaKMThasnowanewgenerationofportablefaultlocationsystem.ThemainfeaturesoftheseSystemsare: -EasiestOperation -Automaticdisplayoffaultdistance -Brightcolordisplay -NoTDRknowledgerequired -Notrainingrequired -AutomaticEnddetection -AllinoneunitOneuniqueFrontEndforallSystems!

14第14页/共96页UniqueFeaturesWiththenew,centralcontrolofthe„E-Tray“theelectronicsforallthesesystemsareinonesealed,independentenclosure.

Onetrayservesall.

Theuniquefeatureofthistrayisthelogicalprocess,

whichwasdevelopedtodeterminetheconditionofthetestobjectandtodecideautomaticallywhichisthemostreasonableapproachtocontinue,andtoprovideessentialdetailstotheoperator.TheE-Trayconsistsofabrilliant,sunreadable,

transflective5.7”colour,displayfordirectoutsideoperation,eveninverybrightSunlight.15第15页/共96页TransformerandJointrecognitionOneoftheoptionalfeaturesoftheEZTrayistheautomaticdetectionoftransformersorjoints.WiththeirknownpositionasaresultofGISordetailedrecording

itispossibletocorrelate

thesepositionswiththe

geographicallayouts,and

dependingonthequality

anddetailsofthisknowledge

toisolatethefaulteven

withoutpinpointing.

16第16页/共96页Thepurposeofthisunitisnotthefaultlocation(pinpointing),butjusttodeterminethefaultysectionbetweentwotransformersandtoisolateit.ModesofOperation: DCHipottesting Prelocation

SurgeEnergy: 500or1000JMax.Voltage: 12kVWeight: only34kg

SurgeSequence 10SecondsSupply: 12or120/230V

AutomaticTestSequenceAutomaticInterpretationanddetectionof:

EndofCable “OPEN”or“SHORT”

DistancetoFault Detectionanddisplayoftransformers

17EZ-Restore™/Overdrive17第17页/共96页3ModesofOperation: DCHipottesting Prelocation

PinpointingSurgeEnergy: 500JMax.Voltage: 12kVVersionMV

4kVVersionLVSurgeSequence: 10SecondsSupply: Batteryor120/230V

AutomaticTestSequence AutomaticInterpretationanddetectionof:

EndofCable “OPEN”or“SHORT”

DistancetoFault Weightonly34kgEZ-THUMP™18第18页/共96页

3ModesofOperation DCHipottesting5kV Prelocation ARMandICE

PinpointingSurgeEnergy 1000JMax.Voltage 2and4kV

SurgeSequence10Seconds BatteryOperationor120/230V AutomaticTestSequence AutomaticInterpretationanddetectionof

EndofCable “OPEN”or“SHORT”

DistancetoFault Weightonly110kg19Smart-THUMP™5kVSMART-THUMPTM519第19页/共96页

3ModesofOperation: DCHipottesting Prelocation ARMandICE

Pinpointing SurgeEnergy: 1150J Max.Voltage: 7,5and15kV

Weight: 110kg

Supply: InternalBatteryor120/230V

AutomaticTestSequence AutomaticInterpretationanddetectionof

EndofCable “OPEN”or“SHORT”

DistancetoFault

20Smart-THUMP15SMART-THUMPTM1520第20页/共96页DCHipottestingupto16kVwithBreakdownrecognition ISOTesting20k…10M Currentmeasurement Prelocation ARMandICE

Pinpointing

Sheathtestingandpinpointing SurgeEnergy 1500J Max.Voltage 8and16kV

IntegratedF-OhmSafetySystem

SurgeSequence10Seconds BatteryOperationor120/230V AutomaticTestSequence AutomaticInterpretationanddetectionof

EndofCable,OPEN,SHORT,DistancetoFault Weight140kg21ThenewSmart-THUMP1621第21页/共96页DetailsSmartThump1622820021145,SmartThump16DetailsforSystemwithoutBatteryandTruckmountVersionwillfollowSalesPrice: 22.500€OfficialAvailabilityandMarketingasusual

withthePowerInfoMail!第22页/共96页Versions23:ThereisnotonlythefullfeatureSystemWehavealwaystheoptionof:1.Portable2.PortablewithoutBatteryandInverterand3.TruckmountversionTheTruckMountVersionSystemwithoutBatteryandInverter第23页/共96页EZ-andSMARTTHUMPoperationForamoredetaileddemonstrationthere

istheEZTraydemosoftwarewhichdemonstratesAndexplainsallversionsandfunctionalities.24第24页/共96页Howistheinterpretationdone?Simplybyalogicalevaluation,basedoncommonfaultlocation

knowledgeandexperience.Example:OpenorinterruptAutomaticHipotTEST NOFlash-over

2.AutomaticTDRReferenceTrace CableEnd“OPEN”

3.AutomaticARM®Trace NOFlash-over

4.Basedontheseresults,thesoftwareconcludesthatcablemustbe

either“GOOD”orthatcablehas“burntintheclear”thereforeitis

suggestedtotheoperatortoconfirmthisresultbyatestfromthe

otherside,byshorteningtheotherend,orjusttoverifythelength!EZ-andSMARTTHUMPoperationbytheE-tray25第25页/共96页26

PortableFaultLocationSystem,consistingof:SurgeGeneratorSPG32with

0...4/8/16/32kV,1750J,-->continiousdutyDCTest,InternalARM®Filter,DecayandCurrentCoupler(ICE),PulsedSheathFaultMode0...5kV,ShortTermBurning(faultconditioning),TestVanmountedorruggedframewithwheels,ReflectometerTeleflexT30-EwithOne-Button-Operation,OperatorGuidingSoftwareSurgeflex32with1750(3500)Joules(c)SebaKMT,allrightsreserved第26页/共96页27HV-ModuleSPG32 typicallyequippedwithTDRTeleflexT30E (incl.DecayandImpulsecurrentmethod)DCTesting 0...32kVDCSurging 0…4kV;1200J 0…8kV;1750J 0...16kV;1750J

0...32kV;1750JSurgerate 3...10s,SinglepulseBurning 0...32kV;160mASheathfaultlocating 0...5kV;160mA

PhysicalDataofSystemConnectingcable 6m(standard)Mainssupply 230V;50/60Hz,2kVADimensions(WxHxD) 800x1280x800mmWeight 135kgPortable (142kgincl.4kVOption)

Surgeflex32:TechnicalData(c)SebaKMT,allrightsreserved第27页/共96页28One-Button-Operation10.4“VGAColourTFTHiBrite-

FullySunreadableDisplayQuickSteps®-ModewithautomaticTestProceduresStep-by-StepEasyModefor

OperatorGuidingSoftwarewithOnline-HelpExpert-ModewithaccesstoallParametersAutomaticFaultRecognitionand

DistanceIndicationAutomaticCableEndRecognitionHighResolutionduetospecialPulseShapeDisplayof3Traces(colorseparated)ARM®-ModeImpulseCurrentMethodDecayMethodTeleflexT30-E(c)SebaKMT,allrightsreserved第28页/共96页29Range 10m…50km(TransientMethods20m…100km)Pulsewidth 35nsto4µsSamplingrate 200MHzAccuracy ±0.1%ofrangeDisplay 10.4“VGAcolourTFTdisplayV/2 50m/µs...150m/µsModes DirectL1,L2

ComparisonL1,L2,Memory DifferenceL1,L2,Memory ARM®-Mode ImpulseCurrentMode,DecayModeMemory 100TracesInterface USBforPCandprinterOperatingtemperature -15°C...50°CDimensions(WxHxD) 360x160x270mmSupply InternalNiMhbattery,110/250VWeight 6kg

TeleflexT30-E:TechnicalData(c)SebaKMT,allrightsreserved第29页/共96页HVOperationfromonesingleunitonly(c)SebaKMT,allrightsreserved第30页/共96页31Faultlocationupto400kVR30theTestVansystemforanyapplicationDCTestingupto110kVOptionsupto150kVand400kVFaultlocationinallknowntechnologiesARMandICEupto50kVDecay110kVOptionalDecayMethodupto400kVFullyintegratedsafetyconceptComparablylowweightandvolumeLowpowerconsumptionR30themostpowerfulFaultLocationSystem(c)SebaKMT,allrightsreserved第31页/共96页digiPHONE+SystemThedigiPHONE+Systemconsistsof: theReceiver theSensor andtheHeadset(c)SebaKMT,allrightsreserved第32页/共96页Carefulhandling,nightworkandfilteringishistorynow:TodaywehaveanewdefinitionofsilenceTheinnovationinfaultpinpointingSeveralnew,innovativemethodsofthedigiPHONE+willensurethesilence

Thetechnologythatletsyouhearthefault–onlythefault! Notraffic! Nohighheels! Notalking! Nonoise!Youhearonlywhatyouwanttohear, -“THE”Fault!Yourearswilllikeit!digiPHONE+System(c)SebaKMT,allrightsreserved第33页/共96页Features/BenefitsHighestacousticqualityandexternalnoiseimmunityAutomaticVolumeMutewith„Bangprotection“Bright,suncapabledisplayEasiestOperationErgonomical,adjustabletelescopichandleDistancemeasurementinMillisecondsormetersSelectablevolumelimitationto84dB(A)Easytracingwithleft–rightindicationFaultdirectionindicationAutomaticadjustmentformagneticandacousticchannelWeatherproofIP65Sensor,betterIP54receiverHighgroundstabilityofthesensorupto45°New,highperformanceconnectors!(c)SebaKMT,allrightsreserved第34页/共96页SensorAdjustablehandleExchangeabletipsActiveElektronic–theevaluationhappenscompletelyinthesensor!Housing: Dualshelldiecastingwithtelescopichandle SoftrubberrimsforacousticshieldingDimensions: Diameter230mm(attheouterlip)Height: 140mmHandlelength: 450…750mmWeight: SensormitTeleskopstabca.2kgDynamicrange: acousticchannel>110dBDynamicrange: magneticchannel>110dBFrequencyrange: 100...1500Hz4Filtersettings: OFF 100…1500Hz Lowpass 100…400Hz Bandpass 300…500Hz Highpass 700…1500Hz(c)SebaKMT,allrightsreserved第35页/共96页ReceiverJogdialON/OFFManualMuteKeyThereceiverisonlyforthedisplayofthedatageneratedfromthesensorandthesignalprocessingofthesignalsfortheheadset.Dimensions(withrubberframe):65mmx225mmx100mm(HxWxD)Weight: app.1kg(incl.Batteries)Supply: 6piecesMignoncellsTypIECR6(Alkali-Mangan)Operationtime: @Mignoncellswith2500mAhcapacity:>10Std.Display: ColorTFT-320x240PixelAdjustment Selectablelimitationto84dB(A),VolumeAkusticGain: >120dB(c)SebaKMT,allrightsreserved第36页/共96页TracingAgreencablesymbolbeneaththesensorsymbolinthecenterofthedigiPHONE+displayshowsthesidepositionofthesensorinrelationtothecabletrace.Thisensuresautomatically,thattheuserremainswiththesensordirectlyontopofthecable,whichmakesthefaultlocationmoreaccuratebutalsoeasier.Weakfaultaremuchfasterdetectedandlocated.Acrossmeasurementisnotrequired,sincethesystemispositionedautomaticallyintheY-axisontopofthecable(c)SebaKMT,allrightsreserved第37页/共96页TheCompassThe„Compass“functionofthedigiPHONE+recognisesfromthedata,especiallyfromthedifferencetimemeasurement,iftheuserismovingtowardsthefault.Thisisindicatedbythearrowinthedisplay.TheuserfollowsthearrowandppoachesautomaticallythefaultpositionIfthedigiPHONE+detectsanincreaseofthedifferencetime,itmeans,thattheuserhaspassedthefaultalready.Inthiscaseabentarrowindicatesthisandrequeststheusertomovebackward.Beforethefault:ThenewvalueislowerthantheolddifferencevalueAfterthefault:Thenewvalueishigherthantheolddifferencevalue(c)SebaKMT,allrightsreserved第38页/共96页MFM10(c)SebaKMT,allrightsreserved第39页/共96页(c)SebaKMT,allrightsreserved40ExamplefromGreece第40页/共96页41BadworkmanshipasstandardproblemMoreandmoreunitsareinstalledbyun-experiencedcheap

servicecompaniesworldwide.MFM-10SheathfaultlocatorrequiredExample(c)SebaKMT,allrightsreserved第41页/共96页42MFM10(c)SebaKMT,allrightsreserved第42页/共96页DieOpticalappearance43ClearfrontendwithfewoperatingelelmentsAlsointhenewMFM10theeasygopriciplewithjogdialandaccordingopticalfeedbackofthejogdialmotionisrealisedIntuitiveeasiestoperationwithalargedisplayLessconnectioncablesSolidPelicase(c)SebaKMT,allrightsreserved第43页/共96页44MFM10-FeaturesTestvoltageupto10kVDC(bipolar!)Upto750mAcontinuouscurrentdrivingcapability(dependingonoutputvoltage(30mAat10kV)withincertainlimitsusefulasburnunit!FlickeraswellasignitionsoffaultsduringtestingarerecognizedanddisplayedWiderangemainssupply88to264VFaultlocatingusingthewellknownvoltagedropmethodimprovedaccuracyduetolow-noisepreamplifierLoggingisdonebyEasyprotEasiest,menuguidedoperationForprelocationtheMFM10checksforwrongconnectionsandinformstheoperatoraccordingly.EasyGorotaryknobsupplementedbyatouchscreen(c)SebaKMT,allrightsreserved第44页/共96页TheHandling45Easy,menuguidedoperationwithrotaryencoderandtouchscreenWeightreductionofmorethan30%comparedtotheMFM5-1bynewtechnologiesOnlyonesingleHVconnectioncable,thepermitstesting,prelocationandpinpointingwithoutreconnectingThetestofallconnectedtestleadyavoidsfalsemeasurementsandacceleratesthecompleteprocedureThemonitoringduringthetest,especiallyduringthevoltagerampupphasedetectsshorttimevoltageorcurrentchanges,whichmightindicateafaultanddisplaystheseafterthetesttotheoperator.Bythisway,alsomultiplefaultscanbedetectedwithoutapermanentobservationofthedisplay..PelicasewithTrolleyforeasiesttransportability(c)SebaKMT,allrightsreserved第45页/共96页Theoperationalspeed-Conclusion46Acompleteprelocationisjust15secondsEasiestoperationgOnlyoneHVconnectioncableBatteryoperationforatleast2hoursAllofthesefeaturespermitaveryfasttestandmeasurement

Cablemanufacturersaremoreandmoreinterestedincheckingthequalityoftheircontractorcompaniesdoingtheinstallationofthecables.

OurnewMFM-10isthedefinitelyagreattooltodothis.

(c)SebaKMT,allrightsreserved第46页/共96页47Data(c)SebaKMT,allrightsreserved第47页/共96页ESGNT–

Earthfaultlocator第48页/共96页ThenewESGNT第49页/共96页ReplacementoftheESG80AmodernMFM10requiresalsoamodernpinpointingtechnology

WiththenewESGNT,manyrequirementsfromthefieldandsaleswererealizedAutomaticzeroadjustmentAutomaticdetectionofthepulserateEasyhandlingwithoutpermanentadjustmentHighersensitivityLessmix-upbyclearcolorcodingEarthRodsBetterhandlingSaferbyinsulatedconstructionMoreforcefortheinsertionintotheground第50页/共96页TheeasymeasurementTargetwasmostcloseorientationontheconventionalpointerinstrumentQuasianaloguedisplaywiththenormalconventionaldisplayHistoryDisplay,theresponseofupto7pulses(ca.15seconds)isdisplayed第51页/共96页ThemeasurementprocedureAsvoltagegradientsinducedbythecurrentflowingbackfromthefaultpositionexistaroundtheearthingpointofthegenerator,themeasuremightbeelevated(pos.1)indicatesthedirectionofthefaultpositionatthispoint.Athalf-waypointbetweenthegeneratorandthefaultposition,thesignalstrengthreachesaminimum(pos.2)signalstrengthincreasesagain.Themaximumsignalstrengthismeasuredwhenoneoftheearthspikesisdirectlyabovethefault.Ifthefaultisexactlybetweenthetwoeartheindicatorunitdoesnotdisplayareading.Ifthefaultpositionispassedby,thepolaritychanges(pos.5)indicatorunitpointstotheotherdirection.第52页/共96页DisplayMessbildschirm

MenübildschirmeMeasuringDisplayMenueDisplay第53页/共96页DisplayBargraphforactualValuedisplayactualValueZoomLevelActiveFunctionsBatteryStatus第54页/共96页FeaturesHighersensitivity–Measuringrange0,01mV…200VAutomaticadaptationtothevoltageSuppressionofexternaldisturbances(50/60Hz,16⅔Hz,100/120Hz)EliminationofDCinfluencesAutomaticzeroadjustmentAutomaticdetectionofthepulserateEasierhandlingwithoutpermanentadjustmentMechanicallystrongandelectricallysafeconstructionoftheearthrodsDisplayunitIP54第55页/共96页TheEarthRodconceptCableholdersDividableRodsIsolatedupperpartSolidtipsColorcodingUniqueSebaKMTdesign第56页/共96页TheTransportcase第57页/共96页ThevehiclemountingAsforthedigiPHONE+theESGNThasanownvehicleholder.Generally,weoffereitherthecaseorthevehicleholder.Thereisnoobjectiontoofferboth第58页/共96页ScopeofDeliveryEarthfaultprobeESGNT1xDisplayESG-NT 1183059332xEarthrodsESG-NT 1183066921xTestlead2mred 8100031811xTestlead2mblack 8100031801xManualESGNT1xTransportBag 118302978 1xInserttransportbagESG 118306092第59页/共96页AvailabilityAvailablefromMay2012Versions: ESGNT CombiunitwithdigiPHONE+第60页/共96页61SebaKMT–Productrange4.VLF(VeryLowFrequency)CR(CosineRectangular)CableTestingsystems:Mostpowerfultestingapproach,inparticularfor(very)longcables

Waveformsimilarto50Hz–powerfrequency:

Strongincreaseduringzero-crossing

Fullyautomatic,easytousesystemTestmethodaccordingtointernationalstandards

(c)SebaKMT,allrightsreserved第61页/共96页(c)SebaKMT,allrightsreservedProductsVLFCRtechnology–PortablesolutionsIVLFCR-28 (899005936)4.6µF@28kV7.0µF@18kV11.0µF@12kVVLFCR-40-B (899004500)2.2µF@40kV2.5µF@35kV5.0µF@18kVVLFCR-60-B (899007186)VLFCR-60-B-OFFS (890025374) 0,8 µF@ 60kV 1,7 µF@ 35kV 3,0 µF@ 18kVVLFCR-60-P (899007187)VLF verylowfrequencyCR CosineRectangleB BasisP Plus(symmetrical)PZ Prüf-Zusatz(testaddon)CEN CentrixOFFS Offshore(groutedHVoutputline)第62页/共96页(c)SebaKMT,allrightsreservedProductsVLFCRtechnology–PortablesolutionsIIVLFCR-40-P (899004501)VLFCR-40-P-PZ-CEN (890022741)4,4µF@40kV5,0µF@35kV10,0µF@18kVVLFCR-60-P-OFFS (890025376)VLFCR-60-P-PZ-CEN (890022745) 1,6 µF@ 60kV 3,0 µF@ 35kV 5,5 µF@ 18kVVLF verylowfrequencyCR CosineRectangleB BasisP Plus(symmetrical)PZ Prüf-Zusatz(testaddon)CEN CentrixOFFS Offshore(groutedHVoutputline)第63页/共96页(c)SebaKMT,allrightsreservedProductsVLFCRtechnology–TestvansolutionsIVLFCR-54-PZ-CEN1 (890002585)VLFCR-54-PZ-CEN3 (890003040)VLFCR-54-PZ-CLASSIC (893016159)VLFCR-54-PZ-R30 (892473488)5,0µF@54kV8,0µF@36kV21,0µF@18kVVLFCR-80-B (890012125)VLFCR-80-B-PZ-CEN (890012123)2,0µF@80kV (45kV)3,0µF@60kV (36kV)4,5µF@40kV4,8µF@36kV9,9µF@20kV第64页/共96页(c)SebaKMT,allrightsreservedProductsVLFCRtechnology–TestvansolutionsIIVLFCR-60-HP (890022222)6,5µF@60kV10,3µF@38kVVLFCR-60-25µF (890025800)VLFCR-60-25µFtrailer (110000000)25,0µF@60kVHP:HighPower(6,5µF-symmetrical)25µF:ConEdversion(symmetrical)VLFCR-80-P (890012124)VLFCR-80-P-PZ-CEN (890012122)2,5µF@80kV4,5µF@60kV7,0µF@40kV7,7µF@36kV14µF@20kV第65页/共96页66ProductOverviewVLFSinustechnology

VLFSinus34kV:Testvoltage: 34kVTestcapacity0,1Hz: 0,6µFTestcapacity0,01Hz: 3,5µFTestfrequency: 0.1Hz(0.1Hz–0.01Hz) (automaticfrequencyadaption)NOTE:TheVLFSinus34hasbeendesignedfortheIEEEmarketformaintenancetestingcablesupto25kV.第66页/共96页670,7µF0.1Hz,30kVpeak(20kVRMS)5,0µF0.01Hz,30kVpeak(20kVRMS)Load-detectionRandCBreakdownrecognitionManualandautomaticfrequency-adaptionF-OhmTestmodes:Sinus,DC+,DC-,rectangularwave,pulsedDCvoltageforsheath-faultlocating.ProtocollingandupdateviaUSBProtectionclassIP20/IP67Robustcasing=PELI-Case1440

withintegratedtrolleyOption:tanDeltatestattachmentVLF-Sinseries

Technicaldetails30(34)kV第67页/共96页68VLF-Sinseries

Technicaldetails54kVTestvoltage: 54kVTestcapacity0,1Hz: 1µFTestcapacity0,01Hz: 5,0µFTestfrequency: 0.1Hz(0.1Hz–0.01Hz) (automaticfrequencyadaption)FirsttestvanshassuccessfullybeendeliveredtoEDFFrance,integratedinCentrix1and3-phase.第68页/共96页VertriebstagungBaunach2009,(c)SebaKMT2009,allrightsreserved.VLFTanDeltaSystemdescription/theoreticalexplanationsSebaKMT2012第69页/共96页VLFTanDelta

TanDeltabasicsAllMVandHVpowercableshaveahighvoltagelifeexpectancy;Duringthewholeservicelifetheyaresubjectedtothermal,electrical,mechanicalandenvironmentalstresses;Thesestresseswillchangethemorphologicalpropertiesoftheinsulation,sowillage/degradetheinsulationmaterial;Resultisadecreaseofthebreakdown-strengthoftheinsulation;Decreaseoftheinsulationbreakdown-strengthwillintheendleadtocablefailures;Toavoidfailuresintheinsulationthemeasurementofthedielectriclossescouldbeahelpfultool.第70页/共96页VLFTanDelta

TanDeltabasicsUICIRIδDielectriclossesaremainlydominatedbytheconductivelossesthatoccurintheinsulationmaterial,incaseofpaper-masscablesalsothepolarization-losseswillinfluencethedielectriclosses.TheDielectriclosses(TanDelta)canbecalculatedaccordingto:Visuallygivenby:Insimpleterms,theinsulationresistanceisinverselyproportionalwiththeTanDelta.第71页/共96页(c)SebaKMT2009,allrightsreserved.VLFTanDelta

TanDeltabasicsThemostimportantageingphenomenonforPILCcablesisthedegradationofcellulose,whatbasicallymeansthatmoisturecomesfreefromthepaperinsulationbecauseofthermalandchemicalprocesses.Thismoisturecontentwilldecreasetheinsulationresistance,resultinginanincreaseinTanDelta.ItisclearthatwithPILCcablesexternalwateringresswillalsoinfluencetheTanDelta!ForXLPEcablesthermalageingishardlymeasurablewiththeTanDeltamethod,theIRC-methodhoweveriscapableofdetectingthattypeofageing.Thef

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论