1、,附表2:B1变电所(公用变配电所TM13)负荷计算表,序号,设备名称(户型-面积),单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台)m2,Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,A栋-1梯,(A-230/325),75w/m2,24层复式+1层,407.3,0.75,305.4,0.85,189.3, ,(B-137),75w/m2,25层,256.9,0.75,192.7,0.85,119.4,(C-118),75w/m2,25层,221.3,0.75,165.9,0.85,102.8

2、,2,A栋-2梯, , ,(D-130),75w/m2,25层,253.5,0.75,190.1,0.85,117.8,(E-130),75w/m2,25层,243.8,0.75,182.8,0.85,113.3,3,A栋-3梯, ,(F-110),75w/m2,25层,206.3,0.75,154.7,0.85,95.9,(G-106),75w/m2,25层,198.8,0.75,149.1,0.85,92.4, ,住宅小计,1787.6,0.45,804.4,0.85,498.5, ,共167户4,塔楼电梯,20kW,4,80.0,0.80,64.0,0.60,85.3,5,梯间照明,10

3、kW,3,30.0,1.00,30.0,0.80,22.5,照明按150w/层/梯计算(共25层)6,平台景观照明,13kW,3,39.0,0.80,31.2,0.80,23.4,含架空层照明 ,合计,1936.6,0.48,929.6,0.83,629.8,1122.87, ,补偿容量,200.0,补偿后,929.6,0.91,429.78,1024.17,变压器同时系数,0.80,743.7,819.33,变压器容量复核:6kWx167户=1002kW ,选用变压器容量(kvA),1000,负荷率,81.93%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,750.7,444.8,8

4、72.57,序号,设备名称(户型-面积),单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台)m2,Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,B栋-1梯,(F-110),75w/m2,25层,206.3,0.75,154.7,0.85,95.9, ,(G-106),75w/m2,25层,198.8,0.75,149.1,0.85,92.4,2,B栋-2梯,(H-125),75w/m2,25层,234.4,0.75,175.8,0.85,108.9,(H-125),75w/m2,25层,234.4

5、,0.75,175.8,0.85,108.9,3,B栋-3梯,(J-101),75w/m2,25层,189.4,0.75,142.0,0.85,88.0,(K-94),75w/m2,25层,176.3,0.75,132.2,0.85,81.9, ,住宅小计,1239.4,0.60,743.6,0.85,460.9, ,共150户4,塔楼电梯,20kW,3,60.0,0.85,51.0,0.60,68.0,5,梯间照明,10kW,3,30.0,1.00,30.0,0.80,22.5,照明按150w/层/梯计算(共25层)6,平台景观照明,13kW,3,39.0,0.80,31.2,0.80,23

6、.4,含架空层照明 ,合计,1368.4,0.63,855.8,0.83,574.8,1030.91, ,补偿容量,200.0,补偿后,855.8,0.92,374.76,934.28,变压器同时系数,0.80,684.7,747.42,变压器容量复核:6kWx150户=900kW ,选用变压器容量(kvA),1000,负荷率,74.74%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,691.7,389.8,793.92,序号,设备名称(户型-面积),单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台)m2,Pe(kW),

7、Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,C栋-1梯,(J-101),75w/m2,24层,181.8,0.75,136.4,0.85,84.5,(K-94),75w/m2,24层,169.2,0.75,126.9,0.85,78.6,2,C栋-2梯, ,(L-103),75w/m2,24层,225.0,0.75,168.8,0.85,104.6,(M-80),4kW/户,24层,96.0,0.75,72.0,0.85,44.6,(N-116),75w/m2,24层,225.0,0.75,168.8,0.85,104.6, , ,住宅小计,897.0,0.60,538.2

8、,0.85,333.5, ,共120户3,塔楼电梯,20kW,2,40.0,0.85,34.0,0.60,45.3,4,梯间照明,10kW,3,30.0,1.00,30.0,0.80,22.5,照明按150w/层/梯计算(共24层)5,平台景观照明,12kW,3,36.0,0.80,28.8,0.80,21.6,含架空层照明6,住宅低区生活水泵,30.0,0.90,27.0,0.80,20.3,7,住宅中区生活水泵,45.0,0.90,40.5,0.80,30.4,8,住宅高区生活水泵,60.0,0.90,54.0,0.80,40.5,9,住宅入口电梯及照明,20+5kW,4,85.0,0.8

9、0,68.0,0.60,90.7, ,合计,1223.0,0.67,820.5,0.80,604.8,1019.30, ,补偿容量,250.0,补偿后,820.5,0.92,354.77,893.91,变压器同时系数,0.85,697.4,759.83,变压器容量复核:6kWx96户+4kWx24户=672kW ,选用变压器容量(kvA),1000,负荷率,75.98%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,704.4,369.8,795.58,2326.58613231521 ,共437户,附表3:B2变电所(专用变配电所TM12)负荷计算表,序号,设备名称,单台功率(kW)或

10、用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台、m2),Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,负一夹层商辅用房动力照明,50w/m2,2770,138.5,0.70,97.0,0.80,72.7,含下沉式广场/排烟新风机22.5kW2,一层商场动力照明,50w/m2,3300,165.0,0.70,115.5,0.80,86.6,3,二层商场动力照明,50w/m2,3900,195.0,0.70,136.5,0.80,102.4,含自动扶梯14部、防火卷帘4,三层商场动力照明,50w/m2,4150,20

11、7.5,0.70,145.3,0.80,108.9,5,四层商场动力照明,50w/m2,4150,207.5,0.70,145.3,0.80,108.9,6,五层餐饮动力照明,60w/m2,4500,270.0,0.60,162.0,0.80,121.5,7,一五层中央空调制冷主机,364,2,728.0,0.90,655.2,0.85,406.1, ,合计,1911.5,0.76,1456.7,0.82,1007.1,1770.92,补偿容量,400.0,补偿后,1456.7,0.92,607.14,1578.12,变压器同时系数,0.8,1165.3,1262.49,选用变压器容量(kvA

12、),1600, ,负荷率,78.91%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,1172.3,622.1,1327.18,序号,设备名称,单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台、m2),Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,一五层中央空调冷冻却水泵,45+55,2+2,200.0,0.90,180.0,0.80,135.0,2,一五层中央空调空调末端,40+50+45+45+45,225.0,0.90,202.5,0.80,151.9,3,一五层中央空调冷却塔,15,

13、2,30.0,0.90,27.0,0.80,20.3,4,架空层泳池及休闲广场,50.0,0.90,45.0,0.80,33.8,5,餐饮电梯,20,2,40.0,0.91,36.4,0.80,27.3,6,裙楼消防电梯,20,1,20.0,1.00,20.0,0.80,15.0,7,地下三层排烟新风机,22+11,3+2,88.0,1.00,88.0,0.80,66.0,8,地下三层照明,3.5w/m2,6800,23.8,1.00,23.8,0.80,17.9,455.09,地下四层排烟新风机,11+18.5,4+2,81.0,1.00,81.0,0.80,60.8,10,地下四层照明,3

14、.5w/m2,6800,23.8,1.00,23.8,0.80,17.9,11,室外绿化及道路照明,100.0,1.00,100.0,0.75,88.2, 12,建筑立面照明,200.0,0.80,160.0,0.75,141.1,13,商业户外广告照明,100.0,1.00,100.0,0.75,88.2,14,商业生活供水泵及空调水泵,22+22,45.0,0.90,40.5,0.80,30.4,15,电信设备房,80kW,1,80.0,1.00,80.0,0.80,60.0,16,网络设备房,50kW,1,50.0,0.80,40.0,0.80,30.0, ,合计,1356.6,0.92

15、,1248.0,0.79,983.5,1588.95,补偿容量,400.0,补偿后,1248.0,0.91,583.49,1377.67,变压器同时系数,0.8,998.4,1102.13,选用变压器容量(kvA),1600, ,负荷率,68.88%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,1005.4,598.5,1170.05,1,消防栓供水泵,110.0,1.00,110.0,0.80,82.5,火灾时不供电,平时供电2,地下室潜水排水泵,110.0,0.60,66.0,0.80,49.5,3,裙楼及地下室正压送风机,7.5+5.5,6+2,56.0,1.00,56.0,0.

16、80,42.0,附表4:B3变电所(专用变配电所TM12)负荷计算表,序号,设备名称,单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台、m2),Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,地下一层超市动力照明,70w/m2,6700,469.0,0.80,375.2,0.75,327.9,地下一层夹层餐饮快餐,80w/m2,550,44.0,0.80,35.2,0.75,30.8,2,超市空调辅机,含地下一层夹层餐饮550m,冷冻却水泵,37+45,2+2,164.0,0.80,131.2,0.

17、80,98.4,空调末端,20+90+83,193.0,0.80,154.4,0.80,115.8,冷却塔,15,2,30.0,0.80,24.0,0.80,18.0,387.03,超市扶梯,10,5,50.0,0.90,45.0,0.65,52.6,6,地下二层排烟新风机,22,3,66.0,1.00,66.0,0.80,49.5,4,超市货梯,20,2,40.0,0.91,36.4,0.80,27.3,5,地下一层排烟新风机,22,3,66.0,1.00,66.0,0.80,49.5, ,合计,1122.0,0.80,933.4,0.77,769.7,1209.85,补偿,400.0,补偿

18、后,933.4,0.93,369.75,1003.97,变压器同时系数,0.90,840.1,903.57,选用变压器容量(kvA),1250,两台1250kVA,应甲方要求,负荷率,72.29%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,847.1,384.7,930.34,序号,设备名称,单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负荷,计算功率,功率因数,无功功率,计算容量,备注,(台、m2),Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,地下二层超市动力照明,70w/m2,6700,469.0,0.80,375.2,0.75,32

19、7.9,2,超市空调,制冷主机,345,2,690.0,0.80,552.0,0.85,342.1, ,合计,1159.0,0.80,927.2,0.81,670.0,1143.92,补偿,300.0,补偿后,927.2,0.93,369.97,998.29,变压器同时系数,0.90,834.5,898.46,选用变压器容量(kvA),1250,两台1250kVA,应甲方要求,负荷率,71.88%,变压器损耗,7.0,15.0,变压器高压侧计算负荷,841.5,385.0,925.36,附表:火灾时消防应急负荷计算表,序号,设备名称,单台功率(kW)或用电指标,数量,设备容量,需用系数,计算负

20、荷,计算功率,功率因数,无功功率,计算容量,备注,(台、m2),Pe(kW),Kx,Pjs,COS,Qjs(kvar),Sjs(kvA),1,住宅A,B,C塔楼电梯,20kW,9,180.0,0.40,72.0,0.60,96.0,三部消防电梯2,住宅A,B,C梯间照明,30kW,3,90.0,1.00,90.0,0.80,67.5,照明按150w/层/梯计算(共25层)3,住宅入口电梯及照明,20+5kW,4,85.0,0.50,42.5,0.60,56.7,一部消防电梯4,地下一四层排烟新风机,301.0,-,88.0,0.80,66.0,按最大容量层计算(地下三层)5,正压送风机,7.5

21、+5.5,6+2,56.0,1.00,56.0,0.80,42.0,6,消防栓供水泵,110.0,1.00,110.0,0.80,82.5,7,地下室潜水排水泵,110.0,0.50,55.0,0.80,41.3,8,一五层商场应急照明,3w/m2,19900,59.7,1.00,59.7,0.80,44.8,9,地下三四层及夹层应急照明,1w/m2,16600,16.6,1.00,16.6,0.80,12.5,10,地下一二层及夹层应急照明,3w/m2,13950,41.9,1.00,41.9,0.80,31.4,11,超市货梯,20,2,40.0,0.91,36.4,0.60,48.5,一

22、部消防电梯12,裙楼消防电梯 ,20,3,60.0,0.85,51.0,0.60,68.0,(含餐饮电梯2部)共2部消防电梯 ,合计,1150.2,0.63,719.1,0.74,657.1,974.05, ,发电机同时系数,0.70,503.3,681.83,位于南区(按一个着火点计算),附表1:总用电负荷统计表,序号,设备名称,单台功率(kW)或用电指标,数量,设备容量,(台、栋、户),Pe(kW),1,A栋住宅,每户80m2者按4kW/户,80m2者按75W/m2,167,1787.6,2,B栋住宅,150,1239.4,3,C栋住宅,120,897.0,4,塔楼住宅电梯,20kW,13

23、,260.0,5,梯间照明,30kW,3,95.0,6,平台景观照明,1213kW,3,114.0,7,住宅生活水泵,135.0,8,一五层商场动力照明,50w/m2,22770,1183.5,9,一五层中央空调, , ,1183.0,10,架空层泳池及休闲广场,50.0,11,裙楼电梯,20,3,60.0,12,地下三层排烟新风机,22+11,3+2,88.0,13,地下三层照明,3.5w/m2,6800,23.8,14,地下四层排烟新风机,11+18.5,4+2,81.0,15,地下四层照明,3.5w/m2,6800,23.8,16,裙楼及地下室正压送风机,7.5+5.5,6+2,56.0

24、,17,室外绿化及道路照明,100.0,18,建筑立面照明,200.0,19,商业户外广告照明,100.0,20,商业生活供水泵及空调水泵,22+22,45.0,21,电信设备房,80kW,1,80.0,22,网络设备房,50kW,1,50.0,23,消防栓供水泵,110.0,24,地下室潜水排水泵,110.0,25,地下一二层超市动力照明,70w/m2,13400,938.0,26,地下一二层超市中央空调, ,1,1077.0,27,地下一层夹层餐饮快餐,80w/m2,550,44.0,28,超市扶梯,10,5,50.0,29,地下二层排烟新风机,22,3,66.0,30,超市货梯,20,2,40.0,31,地下一层排烟新风机,22,3,66.0, ,合计,10353.1,附表6:总电力供应主要指标,序号,名 称,单位,数量,备 注,1,设备安装容量,kW,10353.1

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论