1、PD481300-32/63DEP直流配电柜用户手册PD481300-32/63DEPDC Distribution CabinetUser ManualE1-20040729-C-1.1艾默生网络能源有限公司Emerson Network Power Co., Ltd.PD481300-32/63DEP直流配电柜用户手册PD481300-32/63DEPDC Distribution CabinetUser Manual资料版本: E1-20040729-C-1.1BOM编号:31010963Version: E1-20040729-C-1.1BOM: 31010963艾默生网络能源有限公司
2、为客户提供全方位的技术支持,用户可与就近的艾默生网络能源有限公司办事处或客户服务中心联系,也可直接与公司总部联系。艾默生网络能源有限公司版权所有,保留一切权利。内容如有改动,恕不另行通知。艾默生网络能源有限公司地址:深圳市南山区科技工业园科发路一号邮编:518057公司网址:客户服务热线-mail:infoEmerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or servic
3、e center.Copyright © 2004 by Emerson Network Power Co., Ltd.All rights reserved. The contents in this document are subject to change without notice.Emerson Network Power Co., Ltd.Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen ChinaHomepage: E-mail: suppor
4、t目 录第一章 配电柜概述11.1 产品型号说明11.2 直流配电柜的结构21.3 直流配电柜原理31.3.1 系统主电路工作原理41.3.2 B141HFC1报警板的工作原理和接口51.4 直流配电柜技术参数8第二章 直流配电柜的安装102.1 机柜的安装102.2 外接电缆(端子)设计102.2.1 设计依据102.2.2 外接电缆(端子)的选取112.3 配电柜的对外连接132.3.1 电缆连接的原则132.3.2 配电柜的外部连接说明132.3.3 电缆走线说明15第三章 直流配电柜的使用维护183.1 监控框的操作说明183.2 配电框操作面板的操作说明193.3 配电柜的使用203
5、.4 配电柜的常见故障213.5 系统维护22第一章 配电柜概述 9第一章 配电柜概述PD481300-32/63DEP直流配电柜是专门为华为技术的交换设备设计的配套产品,用于完成48V电源的多路分配。机柜采用与交换设备相同的结构,以便与这些设备并柜使用。该配电柜采用直流双电源输入双电源输出的方式,两路电源互为备用,为需要双电源的负载供电,当任何一路供电电源发生短路或因其它线路故障而中断,不影响负载的正常供电。1.1 产品型号说明配电柜型号说明艾默生公司内部型号:产品编码: 02400350 交付的产品中包括:u 配电柜机柜 1个u 安装附件 1套安装附件的内容参见装箱单。1.2 直流配电柜的
6、结构直流配电柜由机柜、一个监控框和四个配电框组成。(1)监控框 (2)配电框1 (3)配电框2 (4)配电框3 (5)配电框4 图1-1 直流配电柜外形结构配电柜外形尺寸(不带门):800mm(宽)×550mm(深)×2000 mm(高)内部结构如图1-2所示。(1)电源-48V1 GND (2)输出空气开关 (3)电源-48V1分支母排 (4)电源-48V2分支母排 (5)电源-48V2负母排 (6)电源-48V2防雷器 (7)电源-48V2GND (8)告警板 (9)电源-48V1防雷器(10)电源保护地排PGND (11)电源-48V1负母排 (12) 配电柜机柜(1
7、3)运输支撑件 图1-2 直流配电柜示意图1.3 直流配电柜原理PD481300-32/63DEP直流配电柜实现将电流分配到各负载分路的功能,主要包括主电路和报警电路两部分。1.3.1 系统主电路工作原理配电柜主电路包括电源引入、电流分配、电源输出,采用双电源接入、双电源输出方式。配电柜采用分离式正母排结构形式。输出分路采用空气开关,提供输出的短路保护功能。系统主电路原理如图1-3所示。两路48V直流电源通过直流输入正母排和48V1、48V2直流输入负母排引入系统。电源引入之后,通过分支母排分配到各个空气开关以达到电流分配的目的,同时空气开关提供短路保护功能。保护地线引入到柜内保护地排PGND
8、,各负载机柜保护地也从该地排引出。配电柜的正、负母排分别与防雷器相连,防雷器的接地端就近接机架,可提供浪涌保护保护。负载分别从48V1、-48V2两路电源引出,当一路电源故障时,不影响负载供电。图1-3 配电柜主电路原理图1.3.2 B141HFC1报警板的工作原理和接口B141HFC1告警板对每分路的空气输出端检测,一旦空气开关分断,该分路所对应的告警板上的LED发光二极管点亮,指示故障分路位置,同时报警板通过蜂鸣器和故障指示灯输出声、光告警,并可通过光耦把报警信号送到上级监控。告警信号的检测原理如图1-4所示。图1-4 报警板原理框图当空气开关闭合时,采样电平为低,系统工作正常。当空气开关
9、处于分断状态,这时采样电平为高,在其驱动下,点亮指示故障支路空开位置的发光二极管,同时触发报警电路,发出声、光报警信号。B141HFC1报警板的接口报警板对外接口示意如图1-5。图1-5 报警板对外接口示意图报警板(B141HFC1)接口定义接口名管脚序号信号含义管脚序号信号含义J1、J3、J10、J12(P101-8)1空开告警信号输入2空开告警信号输入3空开告警信号输入4空开告警信号输入5空开告警信号输入6空开告警信号输入7空开告警信号输入8空开告警信号输入J2、J4、J11、J13(P101-8)1空开告警信号输入2空开告警信号输入3空开告警信号输入4空开告警信号输入5空开告警信号输入6
10、空开告警信号输入7空开告警信号输入8空J5(P101-4)1报警板电源开关+输入2报警板电源开关+输出3报警板电源开关-输入4报警板电源开关-输出J6(P101-2)1告警指示灯+12V2告警指示灯0VJ7(P101-4)1电源1工作指示灯+48V2电源1工作指示灯0V3电源2工作指示灯+48V4电源2工作指示灯0VJ8(P2500J-2)1告警信号光耦隔离输出+2告警信号光耦隔离输出-J9(P101-8)1故障指示LED负极2告警板测试信号+输出3告警板测试信号 - 输出4消音开关 - 输出5消音开关+输出6故障指示LED正极7工作指示LED负极8工作指示LED正极J14(P101-4)1告
11、警板电源+2告警板电源 - 来自-48V13预留4告警板电源 - 来自-48V2J15(P101-4)1防雷器1告警信号输入2告警信号基准3防雷器2告警信号输入4告警信号基准J16、J17(P101-3)1告警信号基准2告警信号基准3告警信号基准1.4 直流配电柜技术参数环境条件工作温度-540储存温度-4070相对湿度90%RH(40±2)海拔高度3000m(超过时需降额使用)其它没有导电尘埃和腐蚀性气体,没有爆炸危险直流输入直流输入方式双电源输入输入电压40V60VDC最大输入电流1300A输出参数输出额定电压40V60VDC输出额定电流1300A屏内压降0.5V负载分路数额定电
12、流(A)配置空气开关额定容量(A)双10 路6363双20 路3232告警任一负载分路分断时发出声光告警,并指示出相应分路号码。绝缘电阻在温度处于1535,相对湿度90%RH的环境中,施以试验直流电压500V,机柜中各带电回路的对地电阻10M。绝缘强度直流对地之间能承受50Hz,1000V的交流电压1min,无击穿、无飞弧现象,漏电流小于10mA。不与主回路直接连接的辅助电路对地之间能承受50Hz,500V的交流电压1min,无击穿、无飞弧现象,漏电流小于10mA。PD481300-32/63DEP直流配电柜 用户手册第二章 直流配电柜的安装 17第二章 直流配电柜的安装2.1 机柜的安装配电
13、柜的框架结构与交换设备相同,其安装接口也与交换设备一致,因此机柜的安装可参照交换设备的安装方法。2.2 外接电缆(端子)设计配电柜对外连接包括电源输入、负载输出和告警信号输出,主要通过电缆进行连接。2.2.1 设计依据外接电缆的设计应依据直流配电柜的连接端子的规格和各电缆流过的电流来设计。直流配电柜的连接位置的端子规格及数量见表2-1。表2-1 直流配电柜的连接端子连接位置端子规格数量用途电源-48V1负母排M10螺钉5上出线可接3个或下出线接3个电源-48V2负母排M10螺钉5上出线可接3个或下出线接3个电源-48V1 GNDM10螺钉4输入连接3个和短接连接1个M8螺钉30输出连接电源-4
14、8V2 GNDM10螺钉4输入连接3个和短接连接1个M8螺钉30输出连接负载输出空气开关M8螺钉60输出连接PGNDM10螺钉4输入连接12个M8螺钉30输出连接配电柜通过4个配电框输出各分路的直流负极(-48V)。各配电框的输出支路、所属电源、额定输出、空气开关容量的对应关系如下表:输出支路所在配电框归属电源额定输出空气开关容量告警序号151电源1(-48V1)63A63A1561532A32A61516202电源2(-48V2)63A63A1620213032A32A213031353电源1(-48V1)63A63A3135354532A32A354546504电源2(-48V2)63A6
15、3A4650556032A32A55602.2.2 外接电缆(端子)的选取在满配置条件下推荐采用如下规格的电缆和端子头,电缆和端子头采用冷压接的加工方式。在负载电流达不到满配置时,可根据实际负载酌情配置电缆,但需考虑将来扩容引起的负载增加。表2-2 满配置时配电柜的电源输入电缆参数连接用途线色电缆截面积(mm2)电缆根数端子头GND红/黑2406JG240-10-48V1兰2403JG240-10-48V2兰2403JG240-10PGND黄绿951JG95-10& 注意由于该直流配电柜的-48V1、-48V2电源引入采用1300A电流分布接入的设计,在每路电源的输入负极采用了3根电缆
16、以并联方式接入相应母排的不同连接点。表2-3 配电柜的负载输出电缆参数63A分路32A分路连接用途颜色截面积(mm2)根数端子头颜色截面积(mm2)根数端子头GND红/黑2520OT(JG)25-8红/黑1640OT(JG)16-8-48V1兰2520OT(JG)25-8兰1640OT(JG)16-8-48V2兰2520OT(JG)25-8兰1640OT(JG)16-8PGND黄绿2510OT(JG)25-8黄绿1620OT(JG)16-8上表按配电柜的两路电源GND单独输出的接线方式配置。电缆的截面积与工程现场情况有关,相同的载流量下,电缆截面积与电缆的压降、长度相关联,按工程中最可能情况,
17、表2-4给出其2个例子。而表2-3只选其中一种情况配置。表2-4 不同截面积电缆在不同的压降要求下的电缆长度线类负载电流电缆截面积(mm2)压降不大于3V时的电缆长度(25)(m)压降不大于1.5V时的电缆长度(25) (m)63A分路63A3547.523.72534171621.710.832A分路32A2566.8331642.7211026.713注:1.上述压降仅指从配电柜到设备端。 2.使用的为铜电缆。 3.忽略接触压降。2.3 配电柜的对外连接2.3.1 电缆连接的原则1、先接电源输入电缆,后接负载输出电缆,以免相互阻挡。2、配电柜上出线时:输出分路的连接由上至下。3、配电柜下出
18、线时:输出分路的连接由下至上。4、电缆布放不可交叉,不同颜色电缆不能混掺成一束。5、电缆连接时,两端要贴上标签,标签距电缆根部5cm。2.3.2 配电柜的外部连接说明能源连接直流配电柜与输入电源和负载设备的连接示意见图2-1。(1)直流电源设备 (2)机房地线汇流排 (3)电源-48V1GND (4)电源-48V1输出 (5)电源-48V1分支母排 (6)电源-48V2输出(7)电源-48V2分支母排 (8)电源-48V1和-48V2 GND短接电缆(9)电源-48V2负母排 (10)电源-48V2 GND (11)直流配电柜(12)保护地排PGND (13)电源-48V1负母排图2-1 直流
19、配电柜连接示意图本配电柜采用双路输入电源的GND相互独立的结构,GND的连接有两种方式:1. 两路电源的GND单接入配电柜。此时图2-1所示的短接电缆“8”不需连接,两路电源的GND相互独立。2. 两路电源的GND合并接入配电柜。此时两个GND排需使用短接电缆短接,输出连接时注意均匀分配两GND排的电流,尽可能减少流过短接电缆的电流量。信号连接直流配电柜的告警信号通过B141HFC1报警板的J8接口输出(详见图1-5),该接口输出信号参数如表2-5所示。表2-5 告警隔离光藕接口信号类型上拉电阻阻值Vcc(V)Vcc上限(V)对外接口正常状态故障状态隔离开关量5k1215J8集电极开路集电极短
20、路2.3.3 电缆走线说明出线位置说明在机柜的顶部和底部均有出线孔,用于电缆的进/出线,进/出线的电缆尽可能靠边布置。出线孔有防鼠条,当电缆靠边布置时,出线孔空余的部分用防鼠条遮挡。各部分接线在出线孔的分配见图2-2所示。配电柜正面 配电柜背面图2-2 电缆出线分配示意图说明:“1区出线”指的是此处所接的电缆线应通过顶部或底部的1区出线,其它类推。电缆柜内布放连接电缆的柜内布防如图2-3所示。 背面a 背面b图2-3 直流配电柜电缆布放图电源线接好以后,要捆扎整齐美观。第三章 直流配电柜的使用维护 23第三章 直流配电柜的使用维护3.1 监控框的操作说明监控框操作面板如图3-1所示,装有一块告
21、警指示和几个操作开关。图3-1 监控框操作面板1、拉手条 2、告警指示灯面板3、工作指示灯 4、告警指示灯5、消音功能开关(Mute) 6、测试功能开关(Test)7、告警功能开关(Monitor) 8、告警框面板可翻转维护标示 告警消音功能开关(Mute):置于“ON”时,可消除配电柜故障告警时产生的告警声。测试功能开关(Test):用于检测配电柜告警电路板功能是否正常。 告警功能开关(Monitor):置于“ON”时,配电柜具有告警监测功能,置于“OFF”时,关闭告警监测功能。当告警板需要维护时,可以松开监控框上部的固定螺钉,将监控操作面板向下翻转后再进行检修。 3.2 配电框操作面板的操
22、作说明配电柜共配置有4个配电框,各个配电框的配置情况见节2.2.1。各配电框的面板除丝印外,其它类似。配电框1的操作面板如图3-2所示。图3-2 配电框1操作面板1、大电流警告标示 2、拉手条 3、空气开关 4、空开操作防护盖5、用户标签 6、负载分路丝印空开防护盖该空开防护盖是我司的专利设计,用于防止空开被误触及而发生分断(例如清洁面板等操作)、导致重要的通信设备供电意外中断。用户标签配电柜的附件中提供的用户标签,可以用于填写负载名称,并放置在空开保护盖的标签槽内;负载分路丝印3.3 配电柜的使用配电柜通电当机柜安装完成后,请按以下步骤进行配电柜通电:1、通电前,配电柜的所有空气开关应置于断
23、开状态,所有负载设备的电源开关置于断开状态,两路电源的输出熔断器应断开。2、检查输入正负母排之间、输出正负极之间是否存在短路现象;3、接通直流电源1的熔断器,电源1通电;4、接通直流电源2的熔断器,电源2通电;5、分别合上负载设备的电源开关;6、分别合上配电柜的空气开关,给负载设备供电。至此,配电柜通电工作已经完成。配电柜的测试1、将监控框面板上的告警功能开关(Monitor)置于“ON”,观察电源指示灯(work)是否亮;如不亮,参照常见故障“直流电源指示LED不亮”的处理方法处理。2、检查输出电压(48V1、48V2)的极性、大小是否正确;正确极性是:输出母排为正,通过空开的输出端子为负。
24、3、告警测试开关“Test”置于“ON”,告警板上的指示灯全亮,并有声、光告警;将告警消音开关(Mute)置于“ON”可消除告警声,将“Test”置于“OFF”,告警消失;恢复“Mute”至“OFF”位置。测试以上功能正常后,合上输出空气开关,系统即投入使用。3.4 配电柜的常见故障直流电源指示LED不亮1、直流电源指示灯坏,更换LED。2、两路直流电源均异常,更换或修复直流电源。系统误告警1、B141HFC1告警板的信号接口或空气开关的采样连接点连接不可靠,可通过检查以上两类连接点的连接排除故障。2、B141HFC1告警板损坏,此时系统蜂鸣器鸣叫、无告警指示、无位置指示,需更换告警板解决。系
25、统故障时无声、光告警输出B141HFC1告警板损坏后可造成系统告警时只有位置指示灯被点亮(亮度比正常告警时暗),无声、光告警输出。对于此类故障,更换告警板。3.5 系统维护更换B141HFC1告警板更换告警板不影响系统主电路工作,告警板的更换方法如下:1、更换告警板之前请做好防静电措施。2、把Monitor开关打到OFF状态。3、拆下告警面板上方的两颗螺钉,小心翻开告警面板,拆下报警板防护罩板。4、小心拔掉J7 (见图1-5告警板接口示意图),然后拔掉告警板上的其它所有接口插座。5、拆下告警板的6个安装螺钉,拆下故障板,更换新板,用螺钉装好新板,先连接好J7外其它所有接口插座,后连接J7,合上
26、告警面板,用螺钉固定。6、检查Monitor 开关、Test开关、Mute开关功能是否正常维护工作完毕。& 注意如果仅限于告警板的维护,可以通过翻转监控操作框的安装面板直接在机柜正面进行。更换空气开关更换空气开关的方法如下:1、做好各种金属工具的绝缘处理,准备好绝缘胶带,以备对拆卸下来的电缆端子头进行绝缘。2、断开告警面板Monitor开关,用螺丝刀拆开被维护空气开关所在框的面板(为操作方便,可同时拆开上一框的面板)。3、断开被维护的空气开关,用做好绝缘处理的扳手小心拆下被维护的空气开关所接的支路负载电缆,用绝缘胶带包扎好负载端子头。对于不是采用双路供电的负载设备,为免上述操作造成供电
27、中断,建议采用备用线路进行复接。4、用螺丝刀拆下被维护空气开关上方的的空开输出小铜排、下方的与母排相连的空开接入小铜排。5、用小的一字螺丝刀伸入空气开关下端的装配夹中,右手用螺丝刀撬起空气开关装配夹,左手扶住空气开关往上揭起,取下空气开关。6、把空气开关卡上安装导轨,用力一推,空气开关安装完成。7、恢复被维护空气开关上方的的输出接线端子、下方的与母排相连的空开接入端子,恢复负载接线,装上面板,确认主电路接线无误之后闭合被维护支路电源,合上告警面板上的Monitor 开关,检查告警板应处于正常工作状态。整个维护过程完成。ContentsChapter One Overview11.1 Model
28、 of the distribution cabinet11.2 Structure of DC Distribution Cabinet21.3 Theory41.3.1 Theory of Main Circuit41.3.2 Theory and ports of B141HFC1 Alarm Board51.4 Technical Specifications8Chapter two Installation112.1 Mounting of cabinet112.2 Selecting of External Cables and Terminals112.2.1 Selection
29、 Basis112.2.2 Selecting of External Cables and Terminals122.3 External Connection142.3.1 Guideline142.3.2 Connection152.3.3 layout of Cabling16Chapter Three Use and Maintenance193.1 Introduction of Monitoring Unit193.2 Introduction of Power Distribution Unit203.3 Direction for Use213.4 Troubleshooti
30、ng223.5 Maintenance of the Cabinet23Chapter One Overview 9Chapter One OverviewForming a complete set with the exchange equipment made by Huawei Technologies, PD48/1300-32/63EP DC distribution cabinet is used for the distribution of -48V DC power source. The cabinet has the same structure with the ex
31、change equipment so that it can be placed with it side by side.The cabinet uses the DC dual-power source input/output mode, each as the backup for the other, to feed the load that requires two input power sources. Thus, the load can work normally when either of its power sources fails due to short-c
32、ircuit or fault of other circuits.1.1 Model of the distribution cabinetmodelInternal model of Emerson:Product code: 02400350 The equipment delivered consist of the following:1 Distribution cabinet1 set of installation accessoriesThe installation accessories are listed in the packing list.1.2 Structu
33、re of DC Distribution CabinetDC distribution cabinet consists of one cabinet, one monitoring unit and four distribution units.Size(without door): 800mm(width)×550mm(depth)×2000mm(height)(1) Monitoring unit (2) Distribution unit 1 (3) Distribution unit 2 (4) Distribution unit 3(5) Distribut
34、ion unit 4 Figure 1-1 Outline of DC distribution cabinetInternal structure is shown in figure 1-2: Input positive busbar (GND) of power supply -48V1 Output CBS Negative branch-circuit busbar of power supply 48V1 Negative branch-circuit busbar of power supply 48V2 Negative busbar of power supply 48V2
35、 SPD for power supply -48V2 Input positive busbar (GND) of power supply -48V2 Alarm board (9) SPD for power supply -48V1(10) Power protection ground bar PGND(11) Negative busbar of power supply 48V1 (12) cabinet(13) Carriage for transpotationFigure 1-2 Internal structure of DC distribution cabinet1.
36、3 TheoryFormed by main circuit and alarm circuit, PD481300-32/63DEP DC distribution cabinet realizes the function of distributing the current to each branch-circuit load1.3.1 Theory of Main CircuitThe main circuit of distribution cabinet includes power supply input unit, current distribution unit, p
37、ower supply output unit. The cabinet use dual power supply input and output mode in which both positive busbar are separated and the CB which provide short-circuit protection function is used in output branch-circuit. The theory of main circuit is shown in figure 1-3.Two 48V DC power supply (named -
38、48V1 and -48V2, or power supply 1 and power supply 2) are introduced into the system through 2 DC input positive busbar and 2 DC input negative busbars.The introduced power supply is input into multiple MCBs that have short circuit protection function through branch busbars to realize current distri
39、bution.The protection ground line of power supply is connected to the PGND ground busbar inside the cabinet, so does the protective earth of each load equipment.The positive and negative busbars are connected with the surge protection device(SPD) and PGND of SPD is connected with the nearest frame t
40、o provide lightning protection function.The load is connected with power supply 48V1 and 48V2 respectively, thus the failure of either of power supplies won't interrupt to feed the load.Figure 1-3 Theory of main circuit of distribution cabinet1.3.2 Theory and ports of B141HFC1 Alarm BoardB141HFC
41、1 alarm board detects each output CB and in case CB of one branch-circuit is off, the corresponding LED indicator on the alarm board relative to the branch-circuit will light to indicate the fault branch-circuit and the alarm board will send out audible and visual alarm and send the alarm signal to
42、uplink monitoring center through optically coupled isolator.System alarm signal detection theory is shown in figure 1-4.Figure 1-4 Theory of alarm boardWhen CB is ON, the sampling voltage level is low and the system operates normally.When CB change over to OFF, the sampling voltage level change to b
43、e high level which will light the LED that indicate the circuit breaker in the corresponding fault branch circuit and at the same time trigger the alarm circuit to send out audible and visual alarm signalsPorts of B141HFC1 alarm boardThe ports of alarm board are illustrated in Fig. 1-5.Figure 1-5 Po
44、rts of alarm boardDefinition of portsName of portsPin NoFunctionPin NoFunctionJ1, J3, J10, J12(P101-8)1Circuit breaker alarm signal input2Circuit breaker alarm signal input345678J2, J4, J11, J13(P101-8)12345678NullJ5(P101-4)1Input + of power switch of alarm board2Output + of power switch of alarm bo
45、ard3Input - of power switch of alarm board4Output - of power switch of alarm boardJ6(P101-2)1+12V for alarm indicator20V for alarm indicatorJ7(P101-4)1+48V for the operation indicator of power 120V for the operation indicator of power 13+48V for the operation indicator of power 240V for the operatio
46、n indicator of power 2J8(P2500J-2)1Outgoing alarm signal + from optically coupled isolator2Outgoing alarm signal - from optically coupled isolatorJ9(P101-8)1To the negative pole of alarm indicator 2Outgoing test signal +3Outgoing test signal -4Outgoing voltage- for mute switch5Outgoing voltage + for
47、 mute switch6To the positive pole of alarm indicator7To the negative pole of work indicator8To the positive pole of work indicatorJ14(P101-4)1Power supply + for alarm board2Power supply - for alarm board from negtative pole of 48V13Reserved4Power supply - for alarm board from negtative pole of 48V2J
48、15(P101-4)1Incoming alarm signal from SPD 12Reference of alarm signal3Incoming alarm signal from SPD 24Reference of alarm signalJ16, J17(P101-3)1Reference of alarm signal2Reference of alarm signal3Reference of alarm signal1.4 Technical SpecificationsEnvironment requirementOperating temperature-540St
49、orage temperature-4070Relative humidity90%RH(40±2)Altitude3000m (derating is required when this altitude is exceeded)OthersNo conductive dust and corrosive gas, no danger of explosionInput parametersInput modeDouble power supplies inputRated voltage40V60VDCBiggest input current1300AOutput param
50、etersRated output voltage40V60VDCRated output current1300AVoltage drop inside cabinet0.5VNumber of branch loads Rated current(A)Rated capacity of circuit breaker(A)Dual 10-circuit branch6363Dual 20-circuit branch3232AlarmIn case any load CB opens, audible and visual alarm will be sent out and respon
51、ding fault branch-circuit will be indicated.Insulation resistanceAt temperature 1535 and relative humidity90%RH, apply test voltage 500Vdc, the resistance of live loops inside cabinet to earth10M.Dielectric strengthThe DC to earth can withstand 50Hz, 1000Vac for one minute, without breakdown or flas
52、hover and with leakage current less than 10mA. The auxiliary circuits not connected with the main loop to earth can withstand 50Hz, 500Vac for one minute, without breakdown or flashover and with leakage current less than 10mA.PD481300-32/63DEP DC Distribution Cabinet User ManualChapter two Installation 17Chapter two Installation2.1 M
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 演员 长期合同范例
- 单位网线铺设合同范例
- 农村住房转让合同范例
- 出版补充协议合同范例
- 武汉混凝土买卖合同范例
- 灌溉工程合同范例
- 文字校对合同范例
- 入城证申请合同范例
- 医疗机构聘用合同范例
- 商业模特合同范例
- 农产品质量安全检测机构考核评审细则
- 单肺通气中的麻醉管理
- 装修申请审批表
- 建筑施工安全检查标准jgj59-2023
- GB/T 3098.1-2010紧固件机械性能螺栓、螺钉和螺柱
- GB/T 14857-1993演播室数字电视编码参数规范
- GB/T 14125-2008机械振动与冲击振动与冲击对建筑物内敏感设备影响的测量和评价
- 中国人民大学组织行为管理学
- 高中美术-美术鉴赏《人间生活》
- 核电质量保证-质量体系培训课件
- 脑电图(图谱)课件
评论
0/150
提交评论