文档简介

1、Network Message ExampleSLC 5/04 to 1756-L1 processor via DHRIO & 2 ENET ModulesThe following illustrates a SLC5/04 processor (CH1 DH+ node 76) sending a message to a 1756-L1ControlLogix processor (slot 0). The message will passthru a DHRIO module, a ControlLogix chassis(Gateway) and a ENET modul

2、e to another ENET module in another ControlLogix chassis. In order for themessage to pass through the network a DHRIO Routing table must exist!DHRIO Routing table creationTo create a DHRIO Routing table open up RSLinx and under Communication select RSWho.Select a driver that will allow you to see an

3、d connect up to the DHRIO module.Right Click your mouse on top of the DHRIO module and a drop down box will open.Select Module Configuration by clicking with the left mouse button.Select DHRIO Routing Table tab. If no routing table has been created the following should appear.Right click on Backplan

4、e and than left click on Edit Module.Enter the Link ID for the ControlLogix Backplane.Click on OK.Right Click on 1756-DHRIO and than Left Click on Edit Module.Enter the slot number for the DHRIO module and a Link ID for each CH.Click on OK.Right Click on Backplane and than Left Click on Add Module.S

5、elect 1756-ENET module.Click on OK.Enter the slot number and a Link ID for the Ethernet module.Click on OK.Right Click on ENET Link and than Left Click on Add Module.Select 1756-ENET Module type and than Click on OK.Enter the IP address of the 2nd ENET module and the backplane of the 2nd ControlLogi

6、x chassis.Click on OK.Click on Apply and select Yes to download changes!Click on OK.The DHRIO Configuration should now resemble the following:RSLogix5000 Tag creation and SLC MappingUsing RSLogix 5000 software create the controller tag slc_data.Double click on Controller Tags, select Edit Tags and e

7、nter the name of the tag to be created.Make sure that the Type is set for INT and Array Dimensions for Dim 0 is set for 5!Select logic from the tool bar in RSlogix 5000 and then Map PLC/SLC Messages from the drop down menu.Enter the file # you wish to associate with tag slc_data.In this example file

8、 9 is used and will be addressed as N9:0-4 in the SLC message.The following ladder program will continuously re-send the MSG instruction.The following is the MSG Setup.In this example 5 words of data will be written from the SLC5/04 processor starting at word N12:50 to the 2nd 1756-L1 processor (100.100.113.2) at address N9:0 - 4.Local Bridge Address: is the DH+ node address of the 1756-DHRIO module.Remote Bridge Address is not required if the target device is remote-capable.Remote Station Address is the slot number of the 17

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论