1、Altivar 12Variable speed drives for asynchronous motorsModbus Communication Manual04/2009BBV28590ContentsImportnformation4Before you begin5 Documentation structure6Presentation7 Connection to RS485 bus8 Configuration of the Modbus serial port9 IO Scanner configuration parameters10 Modbus Functions12

2、 ATV12 state machine17 Application example21 Connection to RS485 bus24BBV28590 04/20093ImportnformationNOTICEthese instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear through

3、out this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in al injury if the instr

4、uctions are not followed.This is the safety alert symbol. It is used to alert you to potential this symbol to avoid poss ble injury or death.al injury hazards. Obey all safety messages that followPLEASE NOTEThe word "drive" as used in this manual refers to the controller portion of the adj

5、ustable speed drive as defined by NEC.Electrical equipment should be installed, operated, serviced, and maintained only by qualified Schneider Electric for any consequences arising out of the use of this material.nel. No respons bility is assumed by© 2009 Schneider Electric.4BBV28590 04/2009CAU

6、TIONCAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, canresult in property damage.CAUTIONCAUTION indicates a potentially hazardous situation, which, if not avoided, can result in minor or moderate injury.WARNINGWARNING indicates a pote

7、ntially hazardous situation, which, if not avoided, can result in death or serious injury.DANGERDANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.Before you beginand understand these instructions before perforany procedure with this dri

8、ve.a. For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adju

9、stable-Speed Drive Systems.”BBV28590 04/20095WARNINGLOSS OF CONTROL The designer of any control scheme must- consider the potential failure modes of control paths and, for certain critical control functions,- provide a means to achieve a safe state during and after a path failure. Examples of critic

10、al control functions are emergency stop and overtravel stop. Separate or redundant control paths must be provided for critical control functions. System control paths may include communication links. Consideration must be given to the implications of unipated transmission delays or failures of the l

11、ink.aFailure to follow these instructions can result in death, serious injury, or equipment damage.WARNINGDAMAGED DRIVE EQUIPMENTDo not operate or install any drive or drive accessory that appears damaged.Failure to follow these instructions can result in death, serious injury, or equipment damage.D

12、ANGERUNINTENDED EQUIPMENT OPERATION and understand this manual before installing or operating the Altivar 12 drive. Any changesto the parameter settings must be performed by qualifiednel.Failure to follow these instructions will result in death or serious injury.DANGERHAZARD OF ELECTRIC SHOCK, EXPLO

13、SION, OR ARC FLASH and understand this manual before installing or operating the Altivar 12 drive. Installation, adjustment, repair, and maintenance must be performed by qualifiednel. The user is responsible for compliance with all international and national electrical code requirements with respect

14、 to grounding of all equipment. Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools. DO NOT touch unshielded components or terminal strip screw connections with voltage present. DO NOT short across terminals

15、 PA/+ and PC/ or across the DC bus capacitors. Before servicing the drive:- Disconnect all power, including external control power that may be present.- Place a “DO NOT TURN ON” label on all power disconnects.- Lock all power disconnects in the open position.- WAIT 15 MINUTES to allow the DC bus cap

16、acitors to discharge. Then follow the “Bus Voltage Measurement Procedure” (see User manual) to verify that the DC voltage is less than 42 V. The drive LEDs are not indicators of the absence of DC bus voltage. Install andall covers before applying power or starting and stopthe drive.Failure to follow

17、 these instructions will result in death or serious injury.Documentation structureThe following Altivar 312 technical documents are available on the Schneider Electric website ( DVD-ROM (reference VW3A8200).) as well as onUser manualThis manual describes how to install, commission, operate and progr

18、am the drive.Simplified manualThis manual is a simplified version of the User manual. This manual is delivered with the drive.Quick Start sheetThe Quick Start descr bes how to wire and configure the drive to start motor quickly and simply for simple applications. This document is delivered with the

19、drive.Modbus Communication manualThis manual describes the assembly, connection to the bus or network, signaling, diagnostics, and configuration of the communication- specific parameters via the 7 segment LED display.It also descr bes the communication services of the Modbus protocol. This manual in

20、cludes the main Modbus addresses.It explains the operating mode specific to communication (state chart).ATV12P manualThis manual describes the features related to products mounted on baseplate.ATV12 Parameters description fileAll the parameters are grouped together in an Excel file available on the

21、Schneider Electric website ( following data:), with theCode NameModbus Addresses Category/write accessType: signed numerical, unsigned numerical, etc. UnitFactory setting Minimum valueum valueDisplay on the 7-segment integrated display terminal RelevantThis file offers the option of sorting and arra

22、nging the data according to any criterion chosen by the user.6BBV28590 04/2009DANGERUNINTENDED EQUIPMENT OPERATION and understand this manual before installing or operating the Altivar 12 drive. Any changesto the parameter settings must be performed by qualifiednel. The excel file does not describe

23、the behaviour of the parameters. Before any modification, refer to the ATV12 User Manual.Failure to follow these instructions will result in death or serious injury.PresentationThe Modbus socket on the Altivar 12 can be used for the following functions:Configuration Settings Control MonitoringThe AT

24、V12 drive supports:The 2-wire RS485 physical layer The RTU transmission modeBBV28590 04/20097Connection to RS485 busConnection to ATV12Connection accessories should be ordered separately (please consult our catalogues).Connect the RJ45 cable connector to the ATV12 connector.Pin out of the ATV12 RJ45

25、 ConnectorView from underneath8.1(1) Modbus signals(2) Supply for RS232 / RS485 converter or a remote terminalinterferenceUse the Schneider Electric cable with 2 pairs of shielded twisted conductors (reference: TSXCSA100, TSXCSA200, TSXCSA500). Keep the Modbus cable separated from the power cables (

26、30 cm (11.8 in.) minimum).Make any crossovers of the Modbus cable and the power cables at right-angles, if necessary.For more information, please refer to the TSX DG KBL E manual: "Electromagnetic compatibility of industrial networks and fieldbuses".RS485 bus schematicThe RS485 standard al

27、lows variants of different characteristics:polarisation line terminatordistribution of a reference potential number of slaveslength of busThe new Modbus specification published on the M site in 2002 contains precises of all these characteristics. They are alsosummarised in Standard schemati

28、c section. The new Schneider Electric devices conform to this specification.8BBV28590 04/2009PinSignal1-2-3-4D1 (1)5D0 (1)6-7VP (2)8Common (1)Configuration of the Modbus serial portCommunicationStructureThe communication parameters are part of the COM- sub.Thisis accessible as follows:Communication

29、configuration - Parameters decriptionThe behaviour of the ATV12 when a time-out occurs is defined by the SLL parameter, this parameter can be found in the (see User Manual).FLt-BBV28590 04/20099WARNINGLOSS OF CONTROLIf Modbus fault management (SLL) = fault ignore (n0), communication control will be

30、inhibited. For safety reasons, inhibition of communication fault should only be used for adjustment or special applications purpose.Failure to follow these instructions can result in death, serious injury, or equipment damage.Parameter descriptionRange or listed valuesdefaultPossible ValueModbus add

31、ressMODBUS address of the driveAdd1 to 2470 : OFF (broadcast only)OFFOFF1 . 24716#1771 = 06001MODBUS baud ratetbr4,8 kbps9,6 kbps19,2 kbps38.4 kbps19,2 kbps4.89.619.238.416#1773 = 06003MODBUS formattFD8O1: 8 bits, odd parity, 1 stop bit. 8E1: 8 bits, even parity, 1 stop bit. 8N1, 8 bits, no parity,

32、1 stop bit 8N2: 8 bits, no parity, 2 stop bits.8E18o1 8E18n1 8n216#1774 = 06004MODBUS Time outttOAdjustable from 0.1 to 30s10,0 sttO16#1775 = 06005ICS-Communication scanner subs :ed in the next chapterDCS-ISA-DSA-IO Scanner configuration parametersIntegrated communication scannerThe communication sc

33、anner is useful when used in combination by the Modbusdevice with the function "/Write Multiple of the functionregisters" : 23 (0x17), which provides in a single telegram a 23 is described in the supported Modbus functionsmultiple registers and a write multiple registers. TheLocal configur

34、ation of the communication scannerThe communication scanner is accessible via the followings : COM- and ICS- OCS- subs.The 4 output variables and the 4 input variables are assigned by means of parameters nCA1 to nCA4 and nMA1 to nMA4. AnnCA or nMA parameter with a value of zero indicates that the pa

35、rameter is not active. These 8 parameters are described in the table.NCA or Nfines the addresses. All these parameters are Modbus eligible addresses.Monitoring the communication scannerIt is also possible to monitor the parameters value that have been configured in the communication scanner. This mo

36、nitored values areaccessible via the followings : COM- andISA- DSA- sub.The 4 output variable values and the 4 input variable values are located into parameters nC1 to nC4 and nM1 to nM4.10BBV28590 04/2009SubOn the local HMI, it is parameter descriptionFactory setting parameterModbus addressISA-NM1

37、(nM1)Source drive value of the 1st input wordETA valueNM1 address 12741 16#31C5NM2 (nM2)Source drive value of the 2nd input wordRFRD valueNM2 address 12742 16#31C6NM3 (nM3)Source drive value of the 3rd input word0NM3 address 12743 16#31C7NM4 (nM4)Source drive value of the 4th input word0NM4 address

38、12744 16#31C8OSA-NC1 (nC1)Destination drive value of the 1st input wordCMD valueNC1 address 12761 16#31D9NC2 (nC2)Destination drive value of the 2nd input wordLFRD valueNC2 address 12762 16#31DANC3 (nC3)Destination drive value of the 3rd input word0NC3 address 12763 16#31DBNC4 (nC4)Destination drive

39、 value of the 4th input word0NC4 address 12764 16#31DCSubOn the local HMI, it is parameter descriptionFactory setting parameterModbus addressICS-NMA1 (nNA1)Source drive address of the 1st input wordAddress of ETA=3201 16#0C81NMA1 address 12701 16#319DNMA2 (nNA2)Source drive address of the 2nd input

40、wordAddress of RFRD=8604 16#219CNMA2 address 12702 16#319ENMA3 (nNA3)Source drive address of the 3rd input word0NMA3 address 12703 16#319FNMA4 (nNA4)Source drive address of the 4th input word0NMA4 address 12704 16#31A0OCS-NCA1 (nCA1)Destination drive address of the 1st output wordAddress of CMD=8501

41、 16#2135NCA1 address 12721 16#31B1NCA2 (nCA2)Destination drive address of the 2nd output wordAddress of LFRD=8602 16#219ANCA2 address 12722 16#31B2NCA3 (nCA3)Destination drive address of the 3rd output word0NCA3 address 12723 16#31B3NCA4 (nCA4)Destination drive address of the 4th output word0NCA3 ad

42、dress 12724 16#31B4IO Scanner configuration parametersConfiguration exampleIn this example the communication scanner is configured as follow, nCA1, nCA2, nMA1, nMA2 are used with their default values. nCA3 is configured with the address of CMI (Modbus 8504 16#2138). nMA3 is is configured with the ad

43、dress of EtI (Modbus 3206 16#0C86).How tothe diagram belowExample for nCA3:nCA3contain the logical address (2138) of CMI12Communication scanner subCOM- COM-, OCS-21The required telegram to perform the exchange is the Modbus function 23, Obviously a sequence of requests based on Modbus functions 03 a

44、nd 16 is also possible.(See also the chapters Modbus Functions and Altivar 12 and M340).BBV28590 04/200911Modbus FunctionsModbus ProtocolThe transmission mode used is RTU mode. The frame contains no message header byte, nor end of message bytes. It is defined as follows:The data is transmitted in bi

45、nary code. CRC16: cyclical redundancy check.The end of the frame is detected on a silence greater than or equal to 3 characters.PrincipleThe Modbus protocol is a master-slave protocol.MasterOnly one device can transmit on the line at any time.The master manages the exchanges and only it can take the

46、 initiative.It interrogates each of the slaves in succession.No slave can send a message unless it is invited to do so. The master repeats the question when there is an incorrect exchange, and declares the interrogated slave absent if no response is received within a given time period.If a slave doe

47、s not understand a message, ids anexception response to the master. The master may or may not repeat the request.Slave iSlave j Slave k Direct slave-to-slave communications are not poss ble.For slave-to-slave communication, the application software must therefore be designed to interrogate a slave a

48、nd send back data received to the other slave.Two types of dialogue are possible between master and slaves: the master sends a request to a slave and waits for its response the master sends a request to all slaves without waiting for a response (broadcasting principle)Addresses The drive Modbus addr

49、ess can be configured from 1 to 247. Address 0 coded in a reques respond to it.t by the master isfor broadcasting. ATV12 drives takeof the request, but do notSupported Modbus functionsThe Altivar 12 supports the following Modbus functions.12BBV28590 04/2009Function nameCodeDescriptionRemarksholding

50、registers0316#03N output wordsMax PDU length : 63 wordsWrite one output word0616#06Write one output wordWrite multiple registers1616#10Write N output wordMax PDU length : 61 words/write Multiple registers2316#17/write multiple registersMax PDU length : 4 words (W), 4 words (R)(Sub-function)device Id

51、entification43/1416#2B16#OEEncapsulated interface transport/device identificationCRC16DataReqodeSlave addressModbus FunctionsThe following paragraphs describes each supported function.Holding registersRequestResponse*N: Quty of RegistersErrorExampleNote: Hi = high order byte, Lo = low order byte.Thi

52、s function can be used toall ATV12 words, both input words and output words.Request1 byte1 byte2 bytes2 bytes2 bytesResponse-1 byte1 byte1 byte2 bytes2 bytes2 bytesExample:4 words W3102 to W3105 (16#0C1E to 16#0C21) in slave 2, using function 3, where:SFr = Switching frequency = 4 kHz (W3102 = 16#00

53、28)tFr =um output frequency = 60 Hz (W3103 = 16#0258)HSP = High speed = 50 Hz (W3104 = 16#01F4) LSP = Low speed = 0 Hz (W3105 = 16#0000)RequestResponseValue of:Parameters:W3102SFrW3103tFrW3104HSPW3105LSPBBV28590 04/2009130203080028025801F4000052B002030C1E0004276CLast word valueCRC16HiLoLoHiSlave no.

54、03Number of bytesFirst word valueHiLoSlave no.03No. of first wordNumber of wordsCRC16HiLoHiLoLoHiError code1 Byte0x83Exception code1 Byte01 or 02 or 03 or 04 (sees onpage 16)Function code1 Byte0x03Byte count1 Byte2 x N*Register valueN* x 2 BytesFunction code1 Byte0x03Starting Address2 Bytes0x0000 to 0xFFFFQuty of Registers2 Bytes1 to 63 (0x 3F)Modbus FunctionsWrite one output wordRequestResponseErrorExampleRequest and resp

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论