1、What is lock out relay function why it is needed?Lock out Relay is the Master Trip relay( It is a latch relay once operated we have to reset it by manual) Which is used for Generator protection, Transformer protection, Turbine protection (Fixed in indoor Panel, Standard manufacturer only making thos

2、e relays) if it operated because of any fault in above the after clearing all the fault we have to reset it by hand(normally available 110Volts or 220Volts DC).Generator lock-out relayThe description of an 86 device is a locking-out or lock-out relay. In general, the 86G-1 and 86G-2 relays on the Ge

3、nerator Protection Panel are actuated by one of several generator protection relays-usually, 87 devices (differential current detection devices-and occasionally, others as specified by the owner, insuring agency/company, local regulations, or utility requirements.Sometimes, numerous devices were gro

4、uped to actuate 86G-1 OR 86G-2 in order to provide some differentiation as to the exact cause of the trip.When an 86G-n relay is actuated by one or more generator protective relays/devices, the device/relay which actuated the lock-out should have a flag or illuminated indicating light to signify whi

5、ch device/relay detected a serious problem which could cause damage to the generator. When the actuating device is identified, the cause should be investigated and understood BEFORE the unit is re-started.When an 86G-n device is actuated, the generator breaker is opened (tripped), excitation is usua

6、lly de-energized, and the turbine is usually tripped (emergency shutdown).The 86G-n relays require a manual reset (they must be manually rotated to return to the reset position) in order to permit a turbine re-start-hence the lock-out function.Refer to the Generator Protection Panel elementary drawi

7、ngs for the exact details of what devices actuate the 86G-n relays at your site.86 Lockout relayis an electrically operated hand or electrically reset auxiliary relay that is operated upon the occurrence of abnormal conditions to maintain associated equipment or devices out of service until it is re

8、set.94 Tripping or trip-free relayFunctions to trip a circuit breaker, contactor, or equipment, or to permit immediate tripping by other devices; or to prevent immediate reclosing of a circuit interrupter if it should open automatically, even though its closing circuit is maintained closed.What is t

9、he difference between the 94 lockout relay and 86 lock out relay ?I have noticed that the 94 lockout relay is activated when the distance relay is activated and 86 is activated when the 87T differential is activated. But why cant the same lockouts be used for both the protection schemes.86 lock out

10、relay is hand reset used for mechanical protection (permanent fault) & 94 lockout relay is self reset used for transient fault (temporary fault condition) this is major different between 86 and 96 lockout relay.94 lockout relay is for line fault only. 86 lockout relay is master trip relay. It trips

11、both primary and secondary of the transformer as the fault is of serious nature.86 lock out relay is an electrically operated hand, or electrically reset relay or device that functions to shut down or hold an equipment out of service, or both, upon the occurrence of abnormal conditions. 94 tripping

12、relay is having function to trip a circuit breaker, contactor or equipment, or to permit immediate tripping by other devices. or to prevent immediate reclosing of a circuit interrupter if it should open automatically even though its closing circuit is maintained closed.Lockout relay is hand reset re

13、lay in this case both the relays are hand reset relay. Only difference is that 94 lockout relay is used for line protection and can also be provided with auto reclosing facility. If the auto reclosing is not successful then in that case 94 goes to Lockout state and shall be manually reset. In case o

14、f 86 there is no Auto reclosing feature available. It goes to lockout state directly.86 is actually an electrically/Hand reset Master trip relay that trips both the primary & Secondary of a Transformer whereas 94 is a lockout relay that is used in transmission line protection eg. in an Autorecloser.

15、 In case of a fault the Autoecloser shall start its O-t-CO-T-CO-T-CO-T-CO operation. After un successfully trying to reclose the line, the 94 Lockout relay shall act after the time duration set & will put the Autorecloser in an Lockout condition so that there are no further reclosing attempts.86 Loc

16、kout relays are used by many utilities in electrical power transmission substations to trip and hold out of equipment service within a protected zone on the occurrence of protection relay operation which requires inspection and/or repair before the zone may be safely placed back in service. The orig

17、inal intent of lockout was that on operation, maintenance or operating personnel would inspect and repair as required the locked-out zone, and when clear, would reset the lockout allowing operators to place the element back in service. However in recent decades, it has become normal to remotely control substations, resulting in the absence of on-site personnel to reset a lockout in a

温馨提示

  • 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
  • 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
  • 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
  • 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
  • 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
  • 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
  • 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。

评论

0/150

提交评论