版权说明:本文档由用户提供并上传,收益归属内容提供方,若内容存在侵权,请进行举报或认领
文档简介
1、摘 要工程概况:该机房制冷系统为四管制系统,即冷却水供/回水管、冷冻水供/回水管系统。经冷水机组制冷后的7的冷冻水通过冷冻水供水管到达分水器,再通过分水器分别送往旅馆的各个区域,经过空调机组后的12的冷冻水回水经集水器再由冷冻水回水管返回冷水机组,通过冷水机组中的蒸发器与制冷剂换热实现降温过程。从冷水机组出来的37的冷却水经冷却水供水管到达冷却塔,经冷却塔冷却后降温后再返回冷水机组冷却制冷剂,如此循环往复。考虑到系统的稳定安全高效地运行,系统中配备补水系统,软化水系统,全程水处理系统等附属系统。关键词:住宅、制冷机房、设计目 录第1章 原始资料····&
2、#183;··························1第2章 方案设计·····················
3、3;·········22.1设计方案································22.2 定压方式······
4、;··························22.3 管材的选择与防腐·····················
5、3;······2第3章 制冷循环系统热力计算···························3第4章 冷水机组的选择············&
6、#183;···············5第5章 管径的确定······························6第6章 水泵的选择·
7、;·····························7 6.1冷冻水泵的选择···················
8、;···········7 6.2冷却水泵的选择······························76.3补水泵的选择·····&
9、#183;·························7第7章 其它设备的选型······················&
10、#183;·····87.1冷却塔的选择·······························97.2分水器与集水器的选择·········&
11、#183;·················97.3软化水箱及补水箱······························9
12、7.4其它附件·································9参考文献···············
13、····················10第1章 原始资料1.1设计题目 苏州市翡翠家园空调用制冷机房设计1.2原始资料 1、建筑物修建地区:苏州市 2、气象资料:查阅规范及相关手册3、空调负荷总计:1300KW4、要求供应的载冷剂温度:冷冻水供水温度7;5、制冷剂种类:R22;。6、冷却介质:采用循环水(补充自来水);7、冷冻站平面图(见附图另发,层高6米)。第2章 方案设计2.1设计方案该机
14、房制冷系统为四管制系统,即冷却水供/回水管、冷冻水供/回水管系统。经冷水机组制冷后的7的冷冻水通过冷冻水供水管到达分水器,再通过分水器分别送往旅馆的各个区域,经过空调机组后的12的冷冻水回水经集水器再由冷冻水回水管返回冷水机组,通过冷水机组中的蒸发器与制冷剂换热实现降温过程。 从冷水机组出来的37的冷却水经冷却水供水管到达冷却塔,经冷却塔冷却后降温后再返回冷水机组冷却制冷剂,如此循环往复。 考虑到系统的稳定安全高效地运行,系统中配备补水系统,软化水系统,全程水处理系统等附属系统。2.2 定压方式本设计采用落地式膨胀水箱来实现冷冻水系统的补水和定压。2.3 管材的选择与防腐空调系统的供回水管采用
15、碳素钢管,公称直径DN50mm,采用无缝钢管,DN50mm,采用普通焊接钢管,DN100时,采用卡箍式连接。冷冻水管保温材料类型为B型,对于水管,DN200-DN300厚度20mm。冷冻水和冷却水都刷双层镀锌层,每层2mm厚。9第3章 制冷循环系统热力计算制冷循环系统的热力计算是根据确定的蒸发温度,冷凝温度,液态制冷剂的再冷度和压缩机的吸气温度等已知条件,通过压焓图,求出各状态点的参数以及相关数值。苏州地区空气湿球温度为29.2,冷却水与空气充分接触,冷却水进口温度t1比空气湿球温度高3-6,冷却水进口温度t1定为33。蒸发温度比冷冻水供水温度低2-3,冷冻水供水温度7,蒸发温度定为4。对于水
16、冷式冷凝器,冷凝温度与冷却水进口温度差取10,冷却水进出口温差取5,冷凝温度tk=40,冷却水出口温度t2=37。定制冷理论循环的热力计算压焓图如下图所示: T=40 T=4计算书的最大负荷乘以冷量损耗系数,冷水机组系统的损耗系数为0.08。空调负荷为1300kw,空调制冷量为1300+1300*0.08=1404kw即o=1404kw单位质量制冷能力qo=h1-h4=406.5-249.7=156.8kj/kg单位容积制冷能力qv=qo/v1=156.8/0.04159=3771.3kj/m3制冷剂质量流量 Mr=o/qo=1404/156.8=8.95kg/s制冷剂体积流量 Vr=Mrv1
17、=8.95*0.04159=0.372m3/s冷凝负荷 k=Mrqk=Mr(h2-h3)=8.95*(431-249.7)=1622.635Kw压缩机理论功率 Pth=Mr(h2-h1)=8.95*(431-406.5)=219.275kw理论制冷系数 th=o/Pth=1404/421.89=3.33制冷效率 R=th/c=3.33*(tk-to)/(to+273.15)=0.433第4章 冷水机组的选择空调负荷1300kw,计算书的最大负荷乘以冷量损耗系数,冷水机组系统的损耗系数为0.08。空调制冷量为1300+1300*0.08=1404kw。选取两台螺杆式冷水机组,型号为LSLXR12
18、3-1300型。冷冻水供回水温度7/12,冷却水供回水温度32/37,制冷量1404kw,输入功率256kW,蒸发水流量67L/s,水压降89Kpa,接管尺寸200mm,冷凝器水流量80L/s,水压降83kPa,接管尺寸200mm。长宽高尺寸为4432*1880*3600。第5章 管径确定管径确定公式:D(m)= (V取11.5m/s)管径小于DN100时水流速度小于1m/s;管径大于DN100时水流速度大于1m/s。(1)冷冻水管 单管冷冻水流量L1=Q/(5*1.163*2)=(1406*2)/(5*1.163*2)=241.79m3/h单管管径D1 = =238mm 取DN250合流管管
19、经D2 = =337mm 取DN350(2)冷却水管单管冷却水流量L=Q*1.2/(5*1.163*2)=(1406*2)*1.2/(5*1.163*2)=580.296m3/h单管管径D3 = =262mm 取DN250合流管管经D4 = =370mm 取DN350(3)补水水管补水流量L=1%*L冷却水=0.01*580.296=5.8m3/hD5 = =37mm 取DN50第6章 水泵的选择6.1 冷冻水泵的选择冷冻水流量:L=Q/(5*1.163)=(1406*2)/(5*1.163)=483.58m3/h制冷机组蒸发器水阻力为55KPa=0.055MPa=5.5mH2O末端设备水阻力
20、为6.2mH2O;回水过滤器为3.4mH2O分水器、集水器水阻力2个为6mH2O制冷系统水管路沿程阻力和局部阻力为90KPa=0.09MPa=9mH2O综上所述,冷冻水泵扬程为30.1mH2O。根据KTZ型直联式空调泵性能表选择KTZ 150-125-410A型,三台,两用一备。此泵转速1480r/min,轴功率40KW,配用功率45KW,效率75%。6.2 冷却水泵的选择冷却水流量:L=Q*1.2/(5*1.163)=(1406*2)*1.2/(5*1.163)=580.296m3/h制冷机组冷凝器水阻力为45KPa=0.045MPa=4.5mH2O冷却塔喷头喷水压力3.8mH2O冷却塔水盘
21、到喷嘴的高差2.2mH2O回水过滤器为3.4mH2O制冷系统水管路沿程阻力和局部阻力为66KPa=0.066MPa=6.6mH2O综上所述,冷冻水泵扬程为20.5mH2O。根据KTZ型直联式空调泵性能表选择KTZ 200-150-320型,三台,两用一备。此泵转速1480r/min,轴功率33.46KW,配用功率45KW,效率82%。6.3 补水泵的选择补水流量:L=1%*L冷却水=0.01*580.296=5.8m3/h系统最高点距补水泵接管处垂直距离为2.3mH2O制冷系统水管路沿程阻力和局部阻力为27KPa=0.027MPa=2.7mH2O综上所述,冷冻水泵扬程为3mH2O。根据KTZ型
22、直联式空调泵性能表选择KTZ 125-100-400B型,2台,一用一备。此泵转速1480r/min,轴功率11.2KW,配用功率18.5KW,效率51%。第7章 其它设备的选型7.1 冷却塔的选择选用方形横流式冷却塔冷却塔的台数根据冷水机组的台数确定,一般应与冷水机组的台数相同,即“一塔对一机”不设置备用冷却塔。从已选定的冷水机组参数中,可知冷却水流量为580.296m3/h,冷却塔处理的水流量应大于冷水机组的冷却水流量,在此我们在已选定的冷水机组的冷却水流量的基础上,考虑1.2富裕系数,冷却塔设计处理水量为:L=580.296×1.2=696.355 m3/h。根据处理水量,以及
23、当地室外湿球温度、水温处理要求,从冷却塔样玻璃钢冷却塔性能曲线空气湿球温度29.2由性能曲线查得750*0.96=720m³/h696.355m³/h由LRT系列低噪音型性能参数表选则LRT-350L/2型,风扇3000mm,电机11Kw,净重2790kg,运行重5920kg,噪音63.0dB,塔身高3680mm,风筒700mm,外形尺寸3600*5590*4080。7.2 分水器与集水器的选择分、集水器的直径按总流量通过时的断面流速(0.5-1.0m/s)初选,并应大于最大接管口直径的2倍。根据公式算出直径。冷冻水流量 L=Q/(5*1.163)=(1406*2)/(5*1.163)= 483.58m3/hD = =414mm 取DN450分水器和集水器的长度计算集水器的长度:D1=450 mm,D2=300mm,D3=300 mm ,D4=200mm(D1为冷冻水泵进水管直径,D2和D3为用户管路直径)L1=D1+60=
温馨提示
- 1. 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
- 2. 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
- 3. 本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
- 4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
- 5. 人人文库网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
- 6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
- 7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 飞机的教案8篇
- 有关市场营销社会实践调查报告(3篇)
- 工程师个人总结工作总结范文6篇
- 校内奖学金获奖感言500字(30篇)
- DB12-1100-2021 平板玻璃工业大气污染物排放标准
- 山东省临沂市(2024年-2025年小学五年级语文)统编版专题练习(上学期)试卷及答案
- 2024年家用电力器具专用配件项目资金需求报告代可行性研究报告
- 水弹性城市道路绿化施工技术规范编制说明
- 上海市县(2024年-2025年小学五年级语文)统编版摸底考试((上下)学期)试卷及答案
- 荆楚理工学院《习近平新时代中国特色社会主义思想概论》2022-2023学年第一学期期末试卷
- 秋冬季安全检查表
- 保利发展控股集团-2022-2023年房地产行业白皮书
- 土力学(二)-课件清华大学-张丙印
- 优化少先队仪式教育的尝试 论文
- 【知识解析】化学促进科学技术的发展
- 小区日常清洁服务项目投标书
- 三国演义第三回读后感100字 三国演义第三回读后感1000字以上(三篇)
- 第三章人本心理治疗
- 双阳区巡游出租汽车驾驶员从业资格考试区域科目考试题库
- 口腔修复学名解及案例分析题
- 带电粒子在电磁场中的运动
评论
0/150
提交评论